Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072621R1 E6.2V 5000 Ekip Dip LI 3p WMP is a 5000 A three-pole withdrawable SACE Emax 2 air circuit breaker with adjustable long-time and instantaneous electronic protection and 150 kA breaking capacity at 400–415 V AC for demanding low-voltage power distribution systems.
£31,280.88
The ABB E6.2V 5000 Ekip Dip LI 3p WMP, order code 1SDA072621R1, is a high-capacity three-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for protection and switching in demanding low-voltage power distribution systems. With a 5000 A rated uninterrupted current and ABB's Ekip Dip LI solid-state electronic trip unit, it provides adjustable long-time overload and instantaneous short-circuit protection.
The E6.2V is engineered for electrical installations with exceptionally high prospective fault currents. Its V-performance level provides a rated ultimate short-circuit breaking capacity of 150 kA at 400–415 V AC, making the breaker particularly suitable for major industrial, infrastructure and high-power distribution systems where reliable interruption of severe short-circuit currents is required.
The 1SDA072621R1 is the moving part of a withdrawable circuit breaker, designed for installation with the appropriate fixed part in compatible ABB SACE Emax 2 switchgear. Its 2000–5000 A adjustable overload setting and 7500–75000 A instantaneous short-circuit setting provide flexibility for coordinating protection with the characteristics of the connected electrical system.
Air circuit breakers such as the ABB SACE Emax 2 provide switching, isolation and circuit protection for high-current low-voltage electrical networks. The E6.2V combines a substantial 5000 A current rating with a 150 kA ultimate short-circuit breaking capacity at 400–415 V AC, making it particularly suitable for major incoming and distribution circuits where exceptionally high prospective fault currents must be safely interrupted.
The Ekip Dip LI electronic trip unit provides long-time overload (L) and instantaneous short-circuit (I) protection. Its adjustable 2000–5000 A overload range and 7500–75000 A instantaneous range enable protection settings to be coordinated with high-current electrical systems, while the withdrawable E6.2 construction supports efficient inspection and servicing within critical switchgear installations.
| Series | SACE Emax 2 |
|---|---|
| Product group | Emax2 Air Circuit Breaker |
| Order code / MPN | 1SDA072621R1 |
| EAN | 8015644764715 |
| Product type | Air circuit breaker |
| Frame | E6.2 |
| Performance level | V |
| Rated uninterrupted current (Iu) | 5000 A |
| Number of poles | 3 |
| Current type | AC |
| Rated voltage | 690 V AC |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz | 150 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 150 kA |
| Protection release | Ekip Dip LI |
| Release type | Solid-state electronic |
| Protection functions | L (long-time), I (instantaneous) |
| Overload release setting | 2000–5000 A |
| Instantaneous short-circuit release setting | 7500–75000 A |
| Integrated earth-fault protection | No |
| Version | Withdrawable |
| Configuration | Moving part |
| Auxiliary contacts | 4 change-over contacts |
| Circuit-breaker position indication | Open / closed |
| Motor drive integrated | No |
| Motor drive | Optional |
| Integrated undervoltage release | No |
| DIN rail mounting | No |
The ABB 1SDA072621R1 is a 5000 A three-pole air circuit breaker designed for switching and protecting high-current low-voltage power distribution systems against overload and short-circuit conditions.
The E6.2V 5000 1SDA072621R1 has a rated uninterrupted current of 5000 A, with its Ekip Dip overload protection adjustable from 2000–5000 A.
The Ekip Dip LI solid-state electronic trip unit provides long-time overload (L) and instantaneous short-circuit (I) protection. The LI configuration does not include integrated short-time or earth-fault protection.
The E6.2V breaker provides a rated ultimate short-circuit breaking capacity of 150 kA at 400–415 V AC, making it suitable for demanding low-voltage installations with exceptionally high prospective fault currents.
Yes. The 1SDA072621R1 is the three-pole moving part of a withdrawable SACE Emax 2 circuit breaker, designed for installation with the appropriate fixed part in a compatible switchgear assembly.
ABB SACE Emax 2 air circuit breakers provide dependable high-current protection and switching for low-voltage power distribution systems, combining high short-circuit performance, advanced electronic protection and flexible withdrawable switchgear integration.
We use cookies