1SDA072618R1 ABB E6.2H 5000 Ekip Hi-Touch LSI 3p WMP Air Circuit Breaker

1SDA072618R1 ABB E6.2H 5000 Ekip Hi-Touch LSI 3p WMP Air Circuit Breaker

ABB 1SDA072618R1 Emax 2 E6.2H 5000 A three-pole withdrawable air circuit breaker moving part with Ekip Hi-Touch LSI electronic protection and 100 kA breaking capacity at 415 V AC for demanding low-voltage power distribution systems.

SKU: 1SDA072618R1MPN: 1SDA072618R1
Price
List Price £36,796.42 ex VAT
Your Price (ex VAT) Save 25%
£27,597.32 25% OFF
You save £9,199.11 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £27,597.32
Trade pricing is personalised to your account

Manufacturer Lead Time

£27,597.32

Why Choose the ABB E6.2H 5000 Ekip Hi-Touch LSI 3p WMP Air Circuit Breaker?

The ABB E6.2H 5000 Ekip Hi-Touch LSI 3p WMP, order code 1SDA072618R1, is a high-performance SACE Emax 2 air circuit breaker moving part designed for protection, monitoring and control of demanding low-voltage electrical distribution systems. Part of the ABB SACE Emax 2 E6.2 series, this three-pole withdrawable breaker combines a 5000 A rated uninterrupted current with the advanced Ekip Hi-Touch LSI electronic trip unit.

The Ekip Hi-Touch LSI release provides long-time overload, short-time selective and instantaneous short-circuit protection. Its advanced electronic platform supports sophisticated protection, measurement and monitoring functions, while the LSI configuration enables effective selectivity and coordination across complex high-current distribution networks without integrated earth-fault protection.

The E6.2H performance level provides an ultimate short-circuit breaking capacity of 100 kA at 415 V AC and 100 kA at 690 V AC. This WMP configuration is the withdrawable moving part, supplied with four auxiliary contacts and designed for installation with a compatible Emax 2 E6.2 fixed part.

Key Advantages

  • High-performance ABB SACE Emax 2 E6.2H air circuit breaker for demanding power distribution.
  • 5000 A rated uninterrupted current for major high-current electrical installations.
  • Three-pole withdrawable design supports efficient inspection, isolation and maintenance.
  • Advanced Ekip Hi-Touch LSI electronic trip unit for sophisticated protection and monitoring.
  • 100 kA breaking capacity at 415 V AC and 690 V AC.
  • LSI protection supports selective coordination between upstream and downstream protective devices.
  • Four auxiliary changeover contacts support switchboard signalling and control.

Key Features

  • ABB SACE Emax 2 E6.2H series.
  • 5000 A rated uninterrupted current.
  • Three-pole configuration.
  • Withdrawable moving-part execution.
  • Ekip Hi-Touch LSI electronic protection release.
  • Long-time overload protection.
  • Short-time selective short-circuit protection.
  • Instantaneous short-circuit protection.
  • 100 kA Icu at 415 V AC.
  • 100 kA Icu at 690 V AC.
  • 690 V AC rated operational voltage.
  • Four auxiliary changeover contacts.

Advanced Selective Protection for High-Current Networks

ABB SACE Emax 2 air circuit breakers are engineered for modern low-voltage networks where high current ratings, strong fault interruption and sophisticated protection are required. The E6.2H frame combines a substantial 5000 A current rating with 100 kA breaking capability, making it suitable for major industrial, infrastructure and critical-power distribution systems.

The Ekip Hi-Touch LSI electronic trip unit combines advanced monitoring capabilities with adjustable long-time, short-time and instantaneous protection. Short-time protection supports selective coordination between circuit breakers, helping isolate faults close to their source while maintaining continuity of supply to unaffected sections of the electrical installation.

Typical Applications

  • Industrial low-voltage main distribution switchboards.
  • Transformer and high-current power distribution systems.
  • Power distribution centres and electrical substations.
  • Manufacturing and process-industry installations.
  • Data centres and critical power infrastructure.
  • Large commercial and infrastructure electrical systems.
  • High-current networks requiring advanced selective protection and monitoring.

Technical Specifications

Series SACE Emax 2 E6.2
ABB order code 1SDA072618R1
Product type Air circuit breaker moving part
Frame E6.2
Performance level H
Rated uninterrupted current Iu 5000 A
Rated operational voltage 690 V AC
Number of poles 3
Execution Withdrawable moving part
Trip unit Ekip Hi-Touch LSI
Release type Electronic
Protection functions LSI
Ultimate breaking capacity Icu at 400 / 415 V AC 100 kA
Ultimate breaking capacity Icu at 690 V AC 100 kA
Overload release adjustment range 2000–5000 A
Short-time delayed short-circuit adjustment range 3000–50000 A
Instantaneous short-circuit adjustment range 7500–75000 A
Earth-fault protection No
Auxiliary contacts 4 changeover contacts
Switched-off indicator Yes
Main-circuit connection Separate chassis / fixed part
Motor drive Optional
Motor drive integrated No
Integrated undervoltage release No
DIN rail mounting No
Electrical durability at ≤440 V 3000 cycles
Electrical durability at 500–690 V 2000 cycles
Mechanical durability 12000 cycles
EAN 8015644764685
Product family Emax 2 Air Circuit Breakers

Frequently Asked Questions

What is the ABB 1SDA072618R1 used for?

The ABB 1SDA072618R1 is a 5000 A three-pole withdrawable Emax 2 air circuit breaker moving part designed for protection, monitoring and control of demanding high-current low-voltage distribution systems.

What protection unit is fitted to this circuit breaker?

The breaker is fitted with an Ekip Hi-Touch LSI electronic trip unit, providing long-time overload, short-time selective and instantaneous short-circuit protection together with advanced monitoring capabilities.

What is the rated current of the E6.2H 1SDA072618R1?

The circuit breaker has a rated uninterrupted current of 5000 A.

What is the breaking capacity of this Emax 2 circuit breaker?

The E6.2H provides an ultimate short-circuit breaking capacity of 100 kA at 415 V AC and 100 kA at 690 V AC.

Is the ABB 1SDA072618R1 a fixed or withdrawable breaker?

This model is the withdrawable moving part of the Emax 2 circuit breaker system and is designed for installation with a compatible E6.2 fixed part.

Trusted Protection for Critical High-Current Networks

ABB SACE Emax 2 air circuit breakers combine high-current capability, advanced electronic protection and robust short-circuit performance, making them a dependable solution for demanding industrial, commercial and infrastructure electrical distribution systems.