Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072615R1 SACE Emax 2 E6.2H 5000 A three-pole withdrawable air circuit breaker moving part with an Ekip Touch LSI electronic trip unit for advanced selective high-current low-voltage AC distribution protection.
£24,966.23
The ABB 1SDA072615R1 is a high-current SACE Emax 2 E6.2H 5000 air circuit breaker moving part designed for protection and switching in demanding low-voltage AC power distribution systems. Configured as an E6.2H 5000 Ekip Touch LSI 3p WMP, it combines a 5000 A rated uninterrupted current, three-pole construction and ABB's Ekip Touch electronic trip unit with LSI protection functions.
The E6.2H frame provides substantial short-circuit performance for major industrial and infrastructure distribution systems. At the 5000 A rating, this configuration provides a rated ultimate short-circuit breaking capacity of 100 kA at 440 V AC together with a rated short-time withstand current of 100 kA for 1 s, supporting installations with very high prospective fault currents.
The Ekip Touch LSI electronic trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection, with a touchscreen interface for protection configuration and operating information. Its three-pole withdrawable moving-part (WMP) architecture connects to a separate matching Emax 2 fixed part, supporting isolation, inspection, servicing and replacement within critical switchboard installations.
Air circuit breakers such as the ABB Emax 2 E6.2H protect major low-voltage networks against overload and short-circuit conditions. With a 5000 A rated uninterrupted current, 100 kA ultimate short-circuit breaking capacity at 440 V AC and 100 kA short-time withstand capability for 1 s, the 1SDA072615R1 is engineered for critical distribution points where substantial current-carrying and fault-management capability is required.
The Ekip Touch LSI trip unit provides three complementary protection functions. Long-time protection responds to sustained overloads, short-time protection provides a delayed short-circuit stage that can assist selective coordination with downstream protection, and instantaneous protection rapidly interrupts severe short circuits. Combined with the E6.2H frame, touchscreen trip-unit platform and withdrawable architecture, this configuration provides a robust and maintainable solution for sophisticated high-current distribution systems.
| Series | SACE Emax 2 |
|---|---|
| Frame | E6.2 |
| Performance level | H |
| Model / configuration | E6.2H 5000 Ekip Touch LSI 3p WMP |
| ABB order code | 1SDA072615R1 |
| Product type | Air circuit breaker moving part |
| Current type | AC |
| Rated uninterrupted current (Iu) | 5000 A |
| Rated operational voltage | 690 V AC |
| Number of poles | 3 |
| Trip unit | Ekip Touch LSI |
| Trip unit type | Electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Long-time protection | L |
| Short-time protection | S |
| Instantaneous protection | I |
| Integrated earth-fault protection | No |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Auxiliary changeover contacts | 4 |
| Switched-off indication | Yes |
| Integrated undervoltage release | No |
| Motor drive | Optional |
| Integrated motor drive | No |
| Degree of protection | IP30 |
| Main-circuit connection | Connection at separate chassis part |
| Control element | Push button |
| Protection unit | Included |
| Power loss | 850 W |
| EAN | 8015644764654 |
| Execution | Withdrawable moving part (WMP) |
| Fixed part | Separate matching Emax 2 fixed part required |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA072615R1 is a SACE Emax 2 E6.2H 5000 three-pole withdrawable air circuit breaker moving part equipped with an Ekip Touch LSI electronic trip unit.
The breaker has a rated uninterrupted current of 5000 A, making it suitable for major high-current low-voltage AC power distribution circuits.
The LSI configuration provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. The short-time function helps support selective coordination with downstream protective devices.
The E6.2H 5000 provides a rated ultimate short-circuit breaking capacity of 100 kA at 440 V AC and a rated short-time withstand current of 100 kA for 1 s.
WMP identifies the withdrawable moving-part execution. The breaker moving part connects to a separate matching Emax 2 fixed part and can be withdrawn to support isolation, inspection, servicing and replacement.
ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, advanced electronic protection and flexible withdrawable architecture for dependable low-voltage power distribution in demanding industrial, commercial and infrastructure systems.
We use cookies