Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072591R1 SACE Emax 2 E6.2V 4000 A three-pole withdrawable air circuit breaker moving part with an Ekip Dip LI electronic trip unit for high-performance low-voltage AC distribution protection.
£23,716.22
The ABB 1SDA072591R1 is a high-performance SACE Emax 2 E6.2V 4000 air circuit breaker moving part designed for protection and switching in demanding high-current low-voltage AC power distribution systems. Configured as an E6.2V 4000 Ekip Dip LI 3p WMP, it combines a 4000 A rated uninterrupted current, three-pole construction and ABB's Ekip Dip electronic trip unit with LI protection functions.
The E6.2V is a very-high-performance configuration within the ABB SACE Emax 2 family. At its 4000 A rating, the V performance level provides a rated ultimate short-circuit breaking capacity of 150 kA at 440 V AC and a rated short-time withstand current of 100 kA for 1 s, making it particularly suitable for installations exposed to exceptionally high prospective fault currents.
The Ekip Dip LI solid-state electronic trip unit provides long-time overload and instantaneous short-circuit protection. Its three-pole withdrawable moving-part (WMP) construction connects to a separate matching Emax 2 fixed chassis, supporting isolation, inspection, servicing and replacement within critical low-voltage switchboards.
Air circuit breakers such as the ABB Emax 2 E6.2V protect high-current low-voltage networks against potentially damaging overload and short-circuit conditions. With a 4000 A rated uninterrupted current, 150 kA ultimate breaking capacity at 440 V AC and 100 kA short-time withstand capability for 1 s, the 1SDA072591R1 is engineered for major distribution points where exceptional fault-current performance is required.
The Ekip Dip LI trip unit provides two fundamental electronic protection functions. Long-time protection responds to sustained overload conditions, while instantaneous protection rapidly trips the breaker during severe short circuits. Combined with the robust E6.2V frame and withdrawable architecture, this configuration provides dependable protection together with practical maintainability for critical high-current switchboards.
| Series | SACE Emax 2 |
|---|---|
| Frame | E6.2 |
| Performance level | V |
| Model / configuration | E6.2V 4000 Ekip Dip LI 3p WMP |
| ABB order code | 1SDA072591R1 |
| Product type | Air circuit breaker moving part |
| Current type | AC |
| Rated uninterrupted current (Iu) | 4000 A |
| Number of poles | 3 |
| Trip unit | Ekip Dip LI |
| Trip unit type | Solid-state electronic |
| Protection functions | Long-time and instantaneous (LI) |
| Long-time protection | L |
| Instantaneous protection | I |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 150 kA |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Auxiliary changeover contacts | 4 |
| Switched-off indication | Yes |
| Integrated undervoltage release | No |
| Motor drive | Optional |
| Integrated motor drive | No |
| Degree of protection | IP30 |
| Main-circuit connection | Connection at separate chassis part |
| Control element | Push button |
| Protection unit | Included |
| DIN rail mounting | No |
| Execution | Withdrawable moving part (WMP) |
| Fixed part | Separate matching Emax 2 fixed part required |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA072591R1 is a SACE Emax 2 E6.2V 4000 three-pole withdrawable air circuit breaker moving part equipped with an Ekip Dip LI solid-state electronic trip unit.
The breaker has a rated uninterrupted current of 4000 A, making it suitable for major high-current low-voltage AC distribution circuits.
The LI configuration provides long-time overload protection and instantaneous short-circuit protection.
The E6.2V 4000 provides a rated ultimate short-circuit breaking capacity of 150 kA at 440 V AC and a rated short-time withstand current of 100 kA for 1 s, making it suitable for installations with exceptionally high prospective fault currents.
WMP identifies the withdrawable moving-part execution. The breaker moving part connects to a separate matching Emax 2 fixed chassis and can be withdrawn to support isolation, inspection, maintenance or replacement.
ABB SACE Emax 2 air circuit breakers combine exceptional short-circuit performance, dependable electronic protection and flexible withdrawable architecture for critical low-voltage power distribution in demanding industrial, commercial and infrastructure systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.