ABB 1SDA072560R1 E4.2S 4000 Ekip G Hi-Touch LSIG 3p WMP is a 4000 A three-pole withdrawable SACE Emax 2 air circuit breaker with advanced long-time, short-time, instantaneous and earth-fault electronic protection for demanding low-voltage power distribution and generator applications.
£22,291.26
The ABB E4.2S 4000 Ekip G Hi-Touch LSIG 3p WMP, order code 1SDA072560R1, is a high-capacity three-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for advanced protection, switching and monitoring in demanding low-voltage power distribution and generator applications. With a 4000 A rated uninterrupted current and ABB's advanced Ekip G Hi-Touch LSIG electronic trip unit, it provides long-time, short-time, instantaneous and earth-fault protection.
The E4.2S combines substantial current-carrying capability with high short-circuit performance. It provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC, while its rated service short-circuit breaking capacity is 100% of Icu. A rated short-time withstand current of 66 kA for 1 s supports selective protection in high-current distribution systems.
The 1SDA072560R1 is the moving part of a withdrawable circuit breaker, designed for installation with the appropriate separate chassis or fixed part. Its Ekip G Hi-Touch release combines sophisticated LSIG protection with generator-oriented functionality, advanced measurement and monitoring capabilities, making this breaker particularly suitable for installations requiring high-current protection, system visibility and serviceable withdrawable switchgear.
Air circuit breakers such as the ABB SACE Emax 2 provide switching, isolation and circuit protection for high-current low-voltage electrical networks. The E4.2S combines a 4000 A current rating with 85 kA breaking capacity at 400–440 V AC and 66 kA at 500–690 V AC, making it suitable for major incoming, generator and distribution circuits where dependable fault interruption and protection coordination are required.
The Ekip G Hi-Touch LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection within ABB's generator-oriented Ekip G platform. Combined with advanced measurement and monitoring capabilities and the withdrawable E4.2 construction, the 1SDA072560R1 is well suited to sophisticated electrical systems where protection selectivity, generator applications, system visibility and maintainability are important.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA072560R1 |
| EAN | 8015644764104 |
| Product type | Air circuit breaker |
| Frame | E4.2 |
| Performance level | S |
| Rated current (In) | 4000 A |
| Rated uninterrupted current (Iu) | 4000 A |
| Number of poles | 3 |
| Current type | AC |
| Rated operational voltage (Ue) | up to 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw) | 66 kA for 1 s |
| Protection release | Ekip G Hi-Touch LSIG |
| Release type | Electronic |
| Protection functions | L (long-time), S (short-time), I (instantaneous), G (earth fault) |
| Integrated earth-fault protection | Yes |
| Overload release setting | from 1600 A |
| Short-time delayed short-circuit setting | from 2400 A |
| Instantaneous short-circuit setting | from 6000 A |
| Version | Withdrawable |
| Configuration | Moving part |
| Main-circuit connection | Connection at separate chassis part |
| Connecting capacity | 4000 mm² |
| Auxiliary contacts | 4 change-over contacts |
| Switched-off indication | Yes |
| Control element | Push button |
| Motor operator | Optional |
| Degree of protection | IP30 |
| Power loss | 900 W |
| Mechanical durability | 15,000 operating cycles |
| Electrical durability at Ue ≤ 440 V | 5,000 operating cycles |
| Electrical durability at Ue 500–690 V | 4,000 operating cycles |
| Dimensions (W × H × D) | 425 × 425 × 383 mm |
| Net weight | 60 kg |
| DIN rail mounting | No |
| Standard | IEC 60947-2 |
The ABB 1SDA072560R1 is a 4000 A three-pole air circuit breaker designed for switching and protecting demanding low-voltage power distribution and generator applications against overload, short-circuit and earth-fault conditions.
The E4.2S 4000 1SDA072560R1 has a rated uninterrupted current of 4000 A.
The Ekip G Hi-Touch LSIG electronic trip unit provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection within ABB's advanced generator-oriented Ekip G platform.
The E4.2S breaker provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC, with a rated short-time withstand current of 66 kA for 1 s.
Yes. The 1SDA072560R1 is the three-pole moving part of a withdrawable SACE Emax 2 circuit breaker, designed for installation with the appropriate separate chassis or fixed part in a compatible switchgear assembly.
ABB SACE Emax 2 air circuit breakers provide dependable high-current protection and switching for low-voltage power distribution systems, combining high short-circuit performance, advanced electronic protection and flexible withdrawable switchgear integration.