ABB 1SDA072555R1 is a SACE Emax 2 E4.2S 4000 A three-pole withdrawable air circuit breaker moving part with an Ekip Touch LSI electronic trip unit for high-current low-voltage power distribution protection.
£18,958.53
The ABB 1SDA072555R1 is a high-performance SACE Emax 2 E4.2S 4000 air circuit breaker moving part designed for protection and switching in demanding low-voltage electrical distribution systems. This three-pole configuration combines a 4000 A rated uninterrupted current with an advanced Ekip Touch LSI electronic trip unit, providing long-time, short-time and instantaneous protection.
As part of the ABB SACE Emax 2 range, the E4.2S combines high-current switching capability with electronic protection and a touchscreen-based Ekip interface. The Ekip Touch LSI release provides adjustable overload and short-circuit protection for applications requiring effective coordination and dependable protection of transformers, feeders and electrical installations.
This model is a 3-pole withdrawable moving part (WMP) rated at 4000 A and 690 V AC. The E4.2S performance level provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC, together with a rated short-time withstand current of 66 kA for 1 s.
Air circuit breakers such as the ABB SACE Emax 2 E4.2S provide switching and protection for high-current low-voltage distribution circuits. The Ekip Touch electronic trip unit monitors circuit conditions and initiates interruption when configured protection thresholds are exceeded, helping protect switchgear, conductors and connected equipment against overload and short-circuit currents.
The Ekip Touch LSI release combines adjustable long-time overload protection with short-time delayed and instantaneous short-circuit protection. Together with the E4.2S frame and withdrawable architecture, the 1SDA072555R1 provides a capable solution for installations where high-current protection, selective coordination, accessible electronic configuration and maintainability are important.
| Series | SACE Emax 2 |
|---|---|
| ABB order code | 1SDA072555R1 |
| EAN | 8015644764050 |
| Product type | Air circuit breaker moving part |
| Frame | E4.2S |
| Short-circuit performance level | S |
| Rated current (In) | 4000 A |
| Rated uninterrupted current (Iu) | 4000 A |
| Number of poles | 3 |
| Trip unit | Ekip Touch LSI |
| Release type | Electronic |
| Protection functions | L, S and I |
| Overload release current setting | 1600–4000 A |
| Short-time delayed short-circuit setting | 2400–40000 A |
| Instantaneous short-circuit setting | 6000–60000 A |
| Integrated earth-fault protection | No |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400–440 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 66 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw), 1 s | 66 kA |
| Rated short-time withstand current (Icw), 3 s | 66 kA |
| Electrical durability at ≤440 V | 5000 cycles |
| Electrical durability at 500–690 V | 4000 cycles |
| Mechanical durability | 15,000 cycles |
| Power loss | 900 W |
| Auxiliary contacts | 4 change-over contacts |
| Motor drive | Optional |
| Degree of protection | IP30 |
| Main-circuit connection | Connection at separate chassis part |
| Configuration | Withdrawable moving part (WMP) |
| Product net dimensions (W × H × D) | 425 × 425 × 383 mm |
| Product net weight | 60 kg |
| Standard | IEC 60947-2 |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA072555R1 is a SACE Emax 2 E4.2S 4000 A three-pole withdrawable air circuit breaker moving part equipped with an Ekip Touch LSI electronic trip unit.
The ABB 1SDA072555R1 has a rated uninterrupted current of 4000 A, making it suitable for demanding high-current low-voltage distribution systems.
The Ekip Touch LSI provides L long-time overload, S short-time delayed short-circuit and I instantaneous short-circuit protection.
The overload release can be set from 1600–4000 A, the short-time delayed short-circuit release from 2400–40000 A, and the instantaneous short-circuit release from 6000–60000 A.
The E4.2S has a rated ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC.
No. This model uses an Ekip Touch LSI release providing long-time, short-time and instantaneous protection; integrated earth-fault protection is not included in this configuration.
This model is supplied as a withdrawable moving part (WMP) for connection through the appropriate separate SACE Emax 2 chassis part.
It is suitable for demanding low-voltage distribution applications including main switchboards, industrial power systems, transformer protection, high-current feeders, infrastructure systems and critical electrical installations.
ABB SACE Emax 2 air circuit breakers are designed for demanding low-voltage power distribution systems where dependable electronic protection, high short-circuit performance and maintainable switchgear architecture are required.