Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072554R1 SACE Emax 2 E4.2S 4000 A three-pole withdrawable air circuit breaker moving part with an Ekip Touch LI electronic trip unit for high-current low-voltage AC distribution protection.
£18,636.99
The ABB 1SDA072554R1 is a high-current SACE Emax 2 E4.2S 4000 air circuit breaker moving part designed for protection and control of demanding low-voltage AC power distribution systems. Configured as an E4.2S 4000 Ekip Touch LI 3p WMP, it combines a 4000 A rated uninterrupted current, three-pole construction and ABB's Ekip Touch electronic trip unit with LI protection functions.
As part of the ABB SACE Emax 2 air circuit breaker series, the E4.2S platform provides robust switching and short-circuit protection for high-current industrial, commercial and infrastructure distribution systems. This S performance configuration provides an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC, with rated service breaking capacity equal to 100% of Icu.
The Ekip Touch LI electronic trip unit provides long-time overload and instantaneous short-circuit protection, combining dependable circuit protection with ABB's touch-interface trip-unit platform. Its three-pole withdrawable moving-part (WMP) configuration connects to the appropriate separate Emax 2 fixed chassis, supporting isolation, inspection and maintenance in compatible switchboards.
Air circuit breakers such as the ABB Emax 2 E4.2S protect high-current low-voltage networks against potentially damaging overload and short-circuit conditions. With a 4000 A rated uninterrupted current, up to 85 kA ultimate breaking capacity and 66 kA short-time withstand capability, this E4.2S configuration is well suited to major distribution points in demanding electrical installations.
The Ekip Touch LI trip unit provides two fundamental protection functions. Long-time protection responds to sustained overload conditions, while instantaneous protection rapidly trips the breaker when severe short-circuit currents occur. Combined with the Emax 2 withdrawable architecture, the 1SDA072554R1 provides dependable high-current protection while supporting practical switchboard maintenance and servicing.
| Series | SACE Emax 2 |
|---|---|
| Frame | E4.2 |
| Performance level | S |
| Model / configuration | E4.2S 4000 Ekip Touch LI 3p WMP |
| ABB order code | 1SDA072554R1 |
| Product type | Air circuit breaker moving part |
| Current type | AC |
| Rated current (In) | 4000 A |
| Rated uninterrupted current (Iu) | 4000 A |
| Number of poles | 3 |
| Trip unit | Ekip Touch LI |
| Release type | Electronic |
| Protection functions | Long-time and instantaneous (LI) |
| Integrated earth-fault protection | No |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 525 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw), 1 s | 66 kA |
| Rated short-time withstand current (Icw), 3 s | 66 kA |
| Overload release adjustment range | 1600–4000 A |
| Instantaneous short-circuit release adjustment range | 6000–60,000 A |
| Electrical durability at Ue ≤ 440 V | 5000 cycles |
| Electrical durability at Ue 500–690 V | 4000 cycles |
| Mechanical durability | 15,000 cycles |
| Power loss | 900 W |
| Degree of protection | IP30 |
| Auxiliary changeover contacts | 4 |
| Motor drive | Optional |
| Main-circuit connection | Separate chassis / fixed part |
| Suitable for IT networks | Yes, up to 690 V |
| Execution | Withdrawable moving part (WMP) |
| Standard | IEC |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA072554R1 is a SACE Emax 2 E4.2S 4000 three-pole withdrawable air circuit breaker moving part equipped with an Ekip Touch LI electronic trip unit.
The breaker has a rated uninterrupted current of 4000 A, making it suitable for high-current low-voltage AC power distribution applications.
The LI configuration provides long-time overload protection and instantaneous short-circuit protection. Integrated earth-fault protection is not included in this configuration.
The E4.2S 4000 provides an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC, with Ics equal to 100% of Icu.
WMP identifies the withdrawable moving-part execution, which connects to the appropriate separate Emax 2 fixed chassis in a compatible withdrawable switchboard.
ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, advanced electronic protection and flexible withdrawable architecture for dependable low-voltage power distribution in demanding industrial, commercial and infrastructure systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.