Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072507R1 E4.2S 3200 Ekip G Touch LSIG 3p WMP is a 3200 A three-pole withdrawable SACE Emax 2 air circuit breaker with long-time, short-time, instantaneous and earth-fault electronic protection for demanding low-voltage power distribution and generator applications.
£16,298.23
The ABB E4.2S 3200 Ekip G Touch LSIG 3p WMP, order code 1SDA072507R1, is a high-performance three-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for protection, switching and monitoring in high-current low-voltage power distribution systems. With a 3200 A rated current and ABB's advanced Ekip G Touch LSIG electronic trip unit, it provides long-time, short-time, instantaneous and earth-fault protection for demanding electrical installations.
The E4.2S combines substantial current-carrying capability with high short-circuit performance. This S-performance model provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–415 V AC and 66 kA at 690 V AC, making it suitable for industrial, commercial and infrastructure distribution systems where dependable fault interruption and selective protection are essential.
The 1SDA072507R1 is the moving part of a withdrawable circuit breaker and features a three-pole configuration with a rated operational voltage up to 690 V AC. It is fitted with four auxiliary change-over contacts and circuit-breaker open/closed position indication, while the Ekip G Touch LSIG release provides comprehensive electronic protection and advanced functionality for generator and power distribution applications.
Air circuit breakers such as the ABB SACE Emax 2 provide switching, isolation and fault protection for high-current low-voltage electrical networks. The E4.2S frame combines a 3200 A current rating with high short-circuit interruption capability, making it suitable for major incoming and distribution circuits where dependable operation and protection coordination are required.
The Ekip G Touch LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection. Combined with the withdrawable construction of the E4.2S, these functions make the 1SDA072507R1 suitable for sophisticated power distribution and generator applications where selectivity, comprehensive fault protection, monitoring and serviceability are important.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA072507R1 |
| EAN | 8015644763572 |
| Product type | Air circuit breaker |
| Frame | E4.2 |
| Performance level | S |
| Rated current (In / Iu) | 3200 A |
| Number of poles | 3 |
| Current type | AC |
| Rated operational voltage | up to 690 V AC |
| Rated voltage | 690 V |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw) | 66 kA for 1 s |
| Protection release | Ekip G Touch LSIG |
| Release type | Solid-state electronic |
| Protection functions | L (long-time), S (short-time), I (instantaneous), G (earth fault) |
| Overload protection setting range | 1280–3200 A |
| Version | Withdrawable |
| Configuration | Moving part |
| Main circuit connection | Connection through separate chassis part |
| Auxiliary contacts | 4 change-over contacts |
| Circuit-breaker position indication | Open / closed |
| Motor operator | Optional |
| Degree of protection | IP30 |
| Power loss | 743 W |
| Mechanical durability | 20,000 operating cycles |
| Electrical durability at Ue ≤ 440 V | 7,000 operating cycles |
| Electrical durability at Ue 500–690 V | 7,000 operating cycles |
| Dimensions (W × H × D) | 425 × 425 × 383 mm |
| Net weight | 60 kg |
The ABB 1SDA072507R1 is a 3200 A three-pole air circuit breaker designed for switching and protecting high-current low-voltage power distribution and generator systems against overload, short-circuit and earth-fault conditions.
The E4.2S 3200 1SDA072507R1 has a rated uninterrupted current of 3200 A.
The Ekip G Touch LSIG electronic trip unit provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.
The E4.2S breaker provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–415 V AC and 66 kA at 690 V AC.
Yes. The 1SDA072507R1 is the three-pole moving part of a withdrawable SACE Emax 2 circuit breaker, designed for installation with the appropriate fixed part in a compatible switchgear assembly.
ABB SACE Emax 2 air circuit breakers provide dependable high-current protection and switching for low-voltage power distribution systems, combining high short-circuit performance, advanced electronic protection and flexible withdrawable switchgear integration.
We use cookies