Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072475R1 is a SACE Emax 2 E4.2V 2500 A three-pole withdrawable air circuit breaker moving part with an Ekip Touch LSI electronic trip unit for high-performance low-voltage power distribution protection.
£12,994.71
The ABB 1SDA072475R1 is a high-performance SACE Emax 2 E4.2V 2500 air circuit breaker moving part designed for protection and switching in demanding low-voltage electrical distribution systems. This three-pole configuration combines a 2500 A rated uninterrupted current with an advanced Ekip Touch LSI electronic trip unit, providing configurable overload and short-circuit protection for industrial, commercial and infrastructure power systems.
As part of the ABB SACE Emax 2 range, the E4.2V is engineered for installations requiring exceptionally high short-circuit performance. The Ekip Touch LSI trip unit provides long-time, short-time and instantaneous protection functions, while its touchscreen interface supports convenient configuration and monitoring of the circuit breaker's protection settings.
This model is a 3-pole withdrawable moving part (WMP) rated at 2500 A. The E4.2V performance level provides a rated ultimate short-circuit breaking capacity of 150 kA at 440 V AC together with a rated short-time withstand current of 100 kA for 1 s, making it particularly suitable for high-fault-level switchboards and critical power distribution installations.
Air circuit breakers such as the ABB SACE Emax 2 E4.2V provide switching and protection for high-current low-voltage distribution circuits. The electronic trip unit monitors circuit conditions and initiates interruption when configured protection thresholds are exceeded, helping protect switchgear, conductors and connected equipment against damaging overload and short-circuit currents.
The Ekip Touch LSI release combines long-time overload protection with short-time and instantaneous short-circuit protection. Together with the E4.2V frame's exceptionally high breaking performance and withdrawable architecture, the 1SDA072475R1 provides a powerful solution for switchboards where high fault-current capability, protection coordination and maintainability are important.
| Series | SACE Emax 2 |
|---|---|
| ABB order code | 1SDA072475R1 |
| Product type | Air circuit breaker moving part |
| Frame | E4.2V |
| Performance level | V |
| Rated uninterrupted current (Iu) | 2500 A |
| Number of poles | 3 |
| Trip unit | Ekip Touch LSI |
| Protection functions | L, S and I |
| Long-time protection | Yes |
| Short-time protection | Yes |
| Instantaneous protection | Yes |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 150 kA |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Configuration | Withdrawable moving part (WMP) |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA072475R1 is a SACE Emax 2 E4.2V 2500 A three-pole withdrawable air circuit breaker moving part equipped with an Ekip Touch LSI electronic trip unit.
The ABB 1SDA072475R1 has a rated uninterrupted current of 2500 A, making it suitable for demanding high-current low-voltage distribution systems.
The Ekip Touch LSI provides L long-time overload, S short-time short-circuit and I instantaneous short-circuit protection.
The E4.2V configuration has a rated ultimate short-circuit breaking capacity of 150 kA at 440 V AC.
The E4.2V 2500 has a rated short-time withstand current of 100 kA for 1 s.
This model is supplied as a withdrawable moving part (WMP) for installation with the appropriate SACE Emax 2 fixed part.
It is suitable for demanding low-voltage distribution applications including main switchboards, industrial power systems, transformer secondary distribution, high-fault-level feeders, infrastructure systems and critical power installations.
ABB SACE Emax 2 air circuit breakers are designed for demanding low-voltage power distribution systems where dependable electronic protection, high short-circuit performance and maintainable switchgear architecture are required.