1SDA072460R1 ABB E4.2V 2000 Ekip G Hi-Touch LSIG 3p WMP Air Circuit Breaker 2000 A

1SDA072460R1 ABB E4.2V 2000 Ekip G Hi-Touch LSIG 3p WMP Air Circuit Breaker 2000 A

ABB 1SDA072460R1 E4.2V 2000 Ekip G Hi-Touch LSIG 3p WMP is a 2000 A three-pole withdrawable SACE Emax 2 air circuit breaker with advanced LSIG electronic protection and 150 kA breaking capacity at 400–415 V AC for demanding low-voltage power distribution systems.

SKU: 1SDA072460R1MPN: 1SDA072460R1
Price
List Price £18,554.14 ex VAT
Your Price (ex VAT) Save 25%
£13,915.61 25% OFF
You save £4,638.54 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £13,915.61
Trade pricing is personalised to your account

Manufacturer Lead Time

£13,915.61

Why Choose the ABB E4.2V 2000 Ekip G Hi-Touch LSIG 3p WMP Air Circuit Breaker?

The ABB E4.2V 2000 Ekip G Hi-Touch LSIG 3p WMP, order code 1SDA072460R1, is a high-performance three-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for advanced protection, switching and monitoring in demanding low-voltage power distribution systems. With a 2000 A rated current and ABB's advanced Ekip G Hi-Touch LSIG electronic trip unit, it provides long-time, short-time, instantaneous and earth-fault protection for critical electrical installations.

The E4.2V is engineered for systems requiring exceptionally high short-circuit performance. This V-performance model provides a rated ultimate short-circuit breaking capacity of 150 kA at 400–415 V AC and 100 kA at 690 V AC, making it suitable for industrial, infrastructure and commercial power networks with high prospective fault currents.

The 1SDA072460R1 is the moving part of a withdrawable circuit breaker in a three-pole configuration and is rated for operation up to 690 V AC. It is supplied with four auxiliary change-over contacts and circuit-breaker open/closed position indication, while the advanced Ekip G Hi-Touch LSIG release supports sophisticated protection, measurement and power-management requirements.

Key Advantages

  • High-performance 2000 A air circuit breaker for demanding low-voltage distribution systems.
  • Exceptional 150 kA ultimate breaking capacity at 400–415 V AC.
  • Advanced Ekip G Hi-Touch LSIG electronic protection with long-time, short-time, instantaneous and earth-fault functions.
  • Three-pole withdrawable moving-part configuration supports serviceable switchgear installations.
  • Rated operational voltage up to 690 V AC.
  • Wide adjustable protection ranges support effective coordination and selectivity within complex distribution networks.

Key Features

  • ABB SACE Emax 2 E4.2V series.
  • 2000 A rated uninterrupted current.
  • Three-pole configuration.
  • Ekip G Hi-Touch LSIG solid-state electronic release.
  • Long-time overload, short-time, instantaneous and earth-fault protection.
  • 150 kA Icu at 400–415 V AC.
  • 100 kA Icu at 690 V AC.
  • Adjustable overload protection from 800–2000 A.
  • Adjustable short-time short-circuit protection from 1200–20000 A.
  • Adjustable instantaneous short-circuit protection from 3000–30000 A.
  • Four auxiliary change-over contacts.
  • Withdrawable moving-part configuration for compatible SACE Emax 2 switchgear.

Advanced Protection for Critical Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 provide switching, isolation and protection for high-current low-voltage electrical networks. The E4.2V performance level is designed for systems with very high prospective short-circuit currents, providing up to 150 kA breaking capacity at 400–415 V AC for robust protection of critical electrical infrastructure.

The Ekip G Hi-Touch LSIG electronic trip unit combines long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection with the advanced functionality associated with ABB's Hi-Touch platform. Together with the withdrawable construction and high breaking performance of the E4.2V, this makes the 1SDA072460R1 suitable for sophisticated power distribution systems where protection coordination, selectivity, monitoring and serviceability are important.

Typical Applications

  • Main low-voltage electrical switchboards.
  • Industrial power distribution systems.
  • Manufacturing and process plant switchgear.
  • Critical infrastructure and utility distribution.
  • Commercial building power distribution.
  • Transformer and installation protection.
  • High-current incoming and distribution feeders.
  • Selective protection systems requiring LSIG functionality.
  • Applications requiring integrated earth-fault protection.
  • Withdrawable switchgear assemblies with high prospective fault currents.

Technical Specifications

Series SACE Emax 2
Order code / MPN 1SDA072460R1
EAN 8015644763107
Product type Air circuit breaker
Frame E4.2
Performance level V
Rated current (In / Iu) 2000 A
Number of poles 3
Current type AC
Rated operational voltage up to 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC 150 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 100 kA
Protection release Ekip G Hi-Touch LSIG
Release type Solid-state electronic
Protection functions L (long-time), S (short-time), I (instantaneous), G (earth fault)
Overload release setting range 800–2000 A
Short-time delayed short-circuit setting range 1200–20000 A
Instantaneous short-circuit setting range 3000–30000 A
Integrated earth-fault protection Yes
Version Withdrawable
Configuration Moving part
Auxiliary contacts 4 change-over contacts
Circuit-breaker position indication Open / closed
Motor operator Optional
DIN rail mounting No

Frequently Asked Questions

What is the ABB 1SDA072460R1 used for?

The ABB 1SDA072460R1 is a 2000 A three-pole air circuit breaker designed for switching and protecting high-current low-voltage power distribution systems against overload, short-circuit and earth-fault conditions.

What is the current rating of the ABB E4.2V 2000?

The E4.2V 2000 1SDA072460R1 has a rated uninterrupted current of 2000 A.

What protection functions does the Ekip G Hi-Touch LSIG provide?

The Ekip G Hi-Touch LSIG electronic trip unit provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.

What is the breaking capacity of the ABB 1SDA072460R1?

The E4.2V breaker provides a rated ultimate short-circuit breaking capacity of 150 kA at 400–415 V AC and 100 kA at 690 V AC.

Is the ABB 1SDA072460R1 a withdrawable circuit breaker?

Yes. The 1SDA072460R1 is the three-pole moving part of a withdrawable SACE Emax 2 circuit breaker, designed for installation with the appropriate fixed part in a compatible switchgear assembly.

Trusted Power Protection from ABB

ABB SACE Emax 2 air circuit breakers provide dependable high-current protection and switching for low-voltage power distribution systems, combining high short-circuit performance, advanced electronic protection and flexible withdrawable switchgear integration.