Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072413R1 E2.2N 2500 Ekip Dip LSIG three-pole withdrawable Emax 2 air circuit breaker moving part with a 2500 A rated current, 66 kA ultimate breaking capacity at 400/415 V AC and integrated LSIG ground-fault protection.
£8,887.28
The ABB E2.2N 2500 Ekip Dip LSIG 3p WMP, order code 1SDA072413R1, is a high-performance three-pole air circuit breaker (ACB) moving part from the ABB SACE Emax 2 range, engineered for protection and switching in demanding low-voltage electrical distribution systems. Combining the E2.2N frame with a 2500 A rated current and ABB's Ekip Dip LSIG solid-state electronic trip unit, it provides comprehensive circuit protection for high-current industrial, commercial and infrastructure power networks.
This breaker uses a withdrawable construction for integration with a compatible Emax 2 fixed part, supporting efficient inspection, servicing and replacement within switchboard installations. Its Ekip Dip LSIG electronic release provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and ground-fault protection, enabling coordinated protection across complex low-voltage distribution networks.
The E2.2N 2500 provides an ultimate short-circuit breaking capacity of 66 kA at 400/415 V AC and a rated short-time withstand current of 66 kA for 1 s. Together with its 2500 A current rating, three-pole configuration, four auxiliary change-over contacts and withdrawable moving-part construction, the 1SDA072413R1 is well suited to main distribution, incomer and high-current feeder applications.
Air circuit breakers such as the ABB SACE Emax 2 protect high-current low-voltage electrical networks by detecting and interrupting overload, short-circuit and ground-fault conditions before they can damage cables, busbars, switchgear or connected equipment. The E2.2N 2500 combines a substantial 2500 A current rating with 66 kA short-circuit breaking capacity at 400/415 V AC and 66 kA short-time withstand capability for 1 s, making it suitable for demanding main distribution systems.
The Ekip Dip LSIG electronic trip unit provides long-time overload, short-time delayed, instantaneous short-circuit and ground-fault protection. With the long-time protection setting adjustable from 1000–2500 A and instantaneous protection adjustable from 1.5–15 × In, the breaker can be configured to support selective coordination with other protective devices throughout a low-voltage electrical network.
| Series | SACE Emax 2 |
|---|---|
| Product group | Emax2 Air Circuit Breaker |
| ABB order code / MPN | 1SDA072413R1 |
| EAN | 8015644762636 |
| Product type | Air circuit breaker moving part |
| Frame | E2.2N |
| Short-circuit performance level | N |
| Rated current | 2500 A |
| Rated operational voltage | 690 V AC |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Dip LSIG |
| Release type | Solid-state electronic |
| Protection functions | LSIG |
| Long-time protection | Overload protection |
| Long-time overload adjustment range | 1000–2500 A |
| Short-time protection | Delayed/selective short-circuit protection |
| Instantaneous protection | Short-circuit protection |
| Instantaneous short-circuit adjustment | 1.5–15 × In |
| Ground-fault protection | Integrated |
| Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 66 kA |
| Rated short-time withstand current (Icw), 1 s | 66 kA |
| Electrical durability at ≤440 V | 8,000 cycles |
| Electrical durability at 500–690 V | 7,000 cycles |
| Mechanical durability | 20,000 cycles |
| Auxiliary contacts | 4 change-over contacts |
| Circuit breaker position indication | Open / closed |
| Degree of protection | IP30 |
| Installation | Withdrawable |
| Configuration | Moving part |
| Main circuit connection | Connection at separate chassis part |
| Control element | Push button |
| Motor drive | Optional |
| Dimensions (W × H × D) | 317 × 425 × 383 mm |
| Net weight | 48 kg |
| Customs tariff number | 85362090 |
The ABB 1SDA072413R1 is a 2500 A three-pole air circuit breaker moving part designed for protection and switching in demanding low-voltage industrial, commercial and infrastructure power distribution systems.
The E2.2N 2500 has a rated current of 2500 A, with long-time overload protection adjustable from 1000–2500 A.
The E2.2N 2500 provides an ultimate short-circuit breaking capacity of 66 kA at 400/415 V AC and a rated short-time withstand current of 66 kA for 1 s.
The Ekip Dip LSIG electronic trip unit provides long-time overload, short-time delayed/selective short-circuit, instantaneous short-circuit and ground-fault protection.
Yes. The 1SDA072413R1 is the withdrawable moving part of an ABB SACE Emax 2 E2.2N air circuit breaker system and is designed for integration with a compatible Emax 2 fixed part within a switchboard assembly.
ABB SACE Emax 2 air circuit breakers are engineered for reliable protection and control of low-voltage power distribution systems, combining high-current switching capability, comprehensive electronic protection and flexible withdrawable switchgear integration for demanding industrial, commercial and infrastructure applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.