1SDA072413R1 ABB E2.2N 2500 Ekip Dip LSIG 3p WMP Air Circuit Breaker

1SDA072413R1 ABB E2.2N 2500 Ekip Dip LSIG 3p WMP Air Circuit Breaker

ABB 1SDA072413R1 E2.2N 2500 Ekip Dip LSIG three-pole withdrawable Emax 2 air circuit breaker moving part with a 2500 A rated current, 66 kA ultimate breaking capacity at 400/415 V AC and integrated LSIG ground-fault protection.

SKU: 1SDA072413R1MPN: 1SDA072413R1
Price
List Price £11,849.71 ex VAT
Your Price (ex VAT) Save 25%
£8,887.28 25% OFF
You save £2,962.43 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,887.28
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,887.28

Why Choose the ABB E2.2N 2500 Ekip Dip LSIG 3p WMP Air Circuit Breaker?

The ABB E2.2N 2500 Ekip Dip LSIG 3p WMP, order code 1SDA072413R1, is a high-performance three-pole air circuit breaker (ACB) moving part from the ABB SACE Emax 2 range, engineered for protection and switching in demanding low-voltage electrical distribution systems. Combining the E2.2N frame with a 2500 A rated current and ABB's Ekip Dip LSIG solid-state electronic trip unit, it provides comprehensive circuit protection for high-current industrial, commercial and infrastructure power networks.

This breaker uses a withdrawable construction for integration with a compatible Emax 2 fixed part, supporting efficient inspection, servicing and replacement within switchboard installations. Its Ekip Dip LSIG electronic release provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and ground-fault protection, enabling coordinated protection across complex low-voltage distribution networks.

The E2.2N 2500 provides an ultimate short-circuit breaking capacity of 66 kA at 400/415 V AC and a rated short-time withstand current of 66 kA for 1 s. Together with its 2500 A current rating, three-pole configuration, four auxiliary change-over contacts and withdrawable moving-part construction, the 1SDA072413R1 is well suited to main distribution, incomer and high-current feeder applications.

Key Advantages

  • High-performance ABB SACE Emax 2 air circuit breaker for demanding low-voltage power distribution.
  • 2500 A rated current for high-current industrial, commercial and infrastructure electrical systems.
  • 66 kA ultimate short-circuit breaking capacity at 400/415 V AC.
  • 66 kA rated short-time withstand current for 1 s.
  • Ekip Dip LSIG electronic trip unit provides comprehensive overcurrent and ground-fault protection.
  • Long-time, short-time, instantaneous and ground-fault protection functions support effective protection coordination.
  • Three-pole configuration for three-phase electrical distribution networks.
  • Withdrawable moving-part design supports efficient switchboard inspection, servicing and maintenance.

Key Features

  • ABB SACE Emax 2 E2.2N air circuit breaker platform.
  • 2500 A rated current.
  • Three-pole circuit breaker configuration.
  • Ekip Dip LSIG solid-state electronic protection release.
  • Long-time (L) overload protection.
  • Short-time (S) delayed/selective short-circuit protection.
  • Instantaneous (I) short-circuit protection.
  • Ground-fault (G) protection.
  • Long-time overload adjustment range: 1000–2500 A.
  • Instantaneous short-circuit adjustment: 1.5–15 × In.
  • 66 kA Icu at 400/415 V AC.
  • 66 kA Icw for 1 s.
  • Withdrawable moving-part construction for compatible Emax 2 switchgear.
  • Four auxiliary change-over contacts fitted.
  • Circuit breaker open/closed position indication.

Advanced LSIG Protection for High-Current Distribution

Air circuit breakers such as the ABB SACE Emax 2 protect high-current low-voltage electrical networks by detecting and interrupting overload, short-circuit and ground-fault conditions before they can damage cables, busbars, switchgear or connected equipment. The E2.2N 2500 combines a substantial 2500 A current rating with 66 kA short-circuit breaking capacity at 400/415 V AC and 66 kA short-time withstand capability for 1 s, making it suitable for demanding main distribution systems.

The Ekip Dip LSIG electronic trip unit provides long-time overload, short-time delayed, instantaneous short-circuit and ground-fault protection. With the long-time protection setting adjustable from 1000–2500 A and instantaneous protection adjustable from 1.5–15 × In, the breaker can be configured to support selective coordination with other protective devices throughout a low-voltage electrical network.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Manufacturing and process plants.
  • Commercial building electrical distribution.
  • Data centres and critical power infrastructure.
  • Utility and infrastructure switchgear.
  • Transformer and generator distribution systems.
  • High-current incomer and feeder protection.

Technical Specifications

Series SACE Emax 2
Product group Emax2 Air Circuit Breaker
ABB order code / MPN 1SDA072413R1
EAN 8015644762636
Product type Air circuit breaker moving part
Frame E2.2N
Short-circuit performance level N
Rated current 2500 A
Rated operational voltage 690 V AC
Number of poles 3
Current type AC
Trip unit Ekip Dip LSIG
Release type Solid-state electronic
Protection functions LSIG
Long-time protection Overload protection
Long-time overload adjustment range 1000–2500 A
Short-time protection Delayed/selective short-circuit protection
Instantaneous protection Short-circuit protection
Instantaneous short-circuit adjustment 1.5–15 × In
Ground-fault protection Integrated
Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC 66 kA
Rated short-time withstand current (Icw), 1 s 66 kA
Electrical durability at ≤440 V 8,000 cycles
Electrical durability at 500–690 V 7,000 cycles
Mechanical durability 20,000 cycles
Auxiliary contacts 4 change-over contacts
Circuit breaker position indication Open / closed
Degree of protection IP30
Installation Withdrawable
Configuration Moving part
Main circuit connection Connection at separate chassis part
Control element Push button
Motor drive Optional
Dimensions (W × H × D) 317 × 425 × 383 mm
Net weight 48 kg
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB 1SDA072413R1 used for?

The ABB 1SDA072413R1 is a 2500 A three-pole air circuit breaker moving part designed for protection and switching in demanding low-voltage industrial, commercial and infrastructure power distribution systems.

What is the current rating of the ABB E2.2N 2500?

The E2.2N 2500 has a rated current of 2500 A, with long-time overload protection adjustable from 1000–2500 A.

What is the short-circuit performance of the ABB 1SDA072413R1?

The E2.2N 2500 provides an ultimate short-circuit breaking capacity of 66 kA at 400/415 V AC and a rated short-time withstand current of 66 kA for 1 s.

What protection functions does the Ekip Dip LSIG trip unit provide?

The Ekip Dip LSIG electronic trip unit provides long-time overload, short-time delayed/selective short-circuit, instantaneous short-circuit and ground-fault protection.

Is the ABB 1SDA072413R1 a withdrawable circuit breaker?

Yes. The 1SDA072413R1 is the withdrawable moving part of an ABB SACE Emax 2 E2.2N air circuit breaker system and is designed for integration with a compatible Emax 2 fixed part within a switchboard assembly.

Trusted by Electrical Engineers Worldwide

ABB SACE Emax 2 air circuit breakers are engineered for reliable protection and control of low-voltage power distribution systems, combining high-current switching capability, comprehensive electronic protection and flexible withdrawable switchgear integration for demanding industrial, commercial and infrastructure applications.