Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072408R1 E2.2H 2000 Ekip Hi-Touch LSI 3p WMP is a three-pole 2000 A withdrawable SACE Emax 2 air circuit breaker moving part with advanced Ekip Hi-Touch LSI electronic protection and 100 kA breaking capacity at 400–440 V AC.
£10,699.84
The ABB E2.2H 2000 Ekip Hi-Touch LSI 3p WMP, order code 1SDA072408R1, is a high-performance SACE Emax 2 air circuit breaker designed for advanced protection and switching in demanding low-voltage power distribution systems. Part of the ABB Emax 2 E2.2 series, this three-pole withdrawable moving part combines a 2000 A rated current with the advanced Ekip Hi-Touch LSI solid-state electronic protection release.
The Ekip Hi-Touch LSI release provides long-time, short-time and instantaneous protection for comprehensive overload and short-circuit protection. Its advanced electronic platform supports sophisticated protection, measurement and monitoring functions, making it well suited to critical industrial, commercial and infrastructure distribution networks.
With a rated operational voltage of 690 V AC, an ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 500–690 V AC, the E2.2H 2000 is engineered for systems with high prospective fault currents. Its withdrawable moving-part construction facilitates inspection, maintenance and replacement within compatible ABB Emax 2 switchgear.
Air circuit breakers such as the ABB Emax 2 E2.2H protect low-voltage electrical distribution systems by interrupting excessive current during overload and short-circuit conditions. The H performance level delivers high fault-breaking capability for installations where substantial prospective short-circuit currents can occur.
The Ekip Hi-Touch LSI release combines advanced long-time, short-time and instantaneous protection with sophisticated electronic monitoring and management capabilities. Together with the withdrawable Emax 2 architecture, it provides a flexible solution for critical switchboards requiring selective protection, operational continuity and efficient servicing.
| Series | SACE Emax 2 |
|---|---|
| Order code | 1SDA072408R1 |
| EAN | 8015644762582 |
| Product type | Air circuit breaker moving part |
| Frame | E2.2 |
| Performance level | H |
| Rated current (In) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Number of poles | 3 |
| Current type | AC |
| Protection release | Ekip Hi-Touch LSI |
| Release type | Electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Overload release setting range | 800–2000 A |
| Short-time short-circuit release setting range | 1200–20000 A |
| Instantaneous short-circuit release setting range | 3000–30000 A |
| Integrated earth-fault protection | No |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate short-circuit breaking capacity (Icu) at 400–440 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Short-time withstand current (Icw) | 85 kA for 1 s; 66 kA for 3 s |
| Construction | Withdrawable moving part |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Motor operator | Optional |
| Power loss | 450 W |
| Electrical durability at ≤440 V AC | 10,000 cycles |
| Electrical durability at 500–690 V AC | 8,000 cycles |
| Mechanical durability | 25,000 cycles |
| Product net weight | 48 kg |
| Standard | IEC 60947-2 |
The ABB 1SDA072408R1 is a 2000 A Emax 2 air circuit breaker moving part designed for advanced switching and protection of demanding low-voltage AC power distribution systems.
This breaker uses the ABB Ekip Hi-Touch LSI electronic release, providing long-time, short-time and instantaneous overcurrent protection functions.
The E2.2H 2000 has an ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 500–690 V AC.
The 1SDA072408R1 is the moving part of a withdrawable Emax 2 air circuit breaker, designed for installation with the appropriate compatible fixed part or chassis.
LSI denotes long-time, short-time and instantaneous protection, providing overload protection together with delayed and instantaneous short-circuit protection functions.
ABB SACE Emax 2 air circuit breakers combine high fault-breaking performance, advanced electronic protection and flexible switchgear integration for demanding industrial, commercial and infrastructure power distribution systems.