Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072405R1 SACE Emax 2 E2.2H 2000 A three-pole withdrawable air circuit breaker moving part with Ekip Touch LSI electronic overload and selective short-circuit protection.
£8,068.72
The ABB E2.2H 2000 Ekip Touch LSI 3p WMP, order code 1SDA072405R1, is a high-performance SACE Emax 2 air circuit breaker moving part designed for protection and switching in demanding low-voltage AC power-distribution systems. This three-pole E2.2H model combines a rated current of 2000 A with ABB's Ekip Touch LSI electronic protection release.
The Ekip Touch LSI trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. Its touchscreen interface supports intuitive configuration and supervision of the protection functions, while the short-time function enables selective coordination with downstream protective devices in complex electrical networks.
Supplied as a withdrawable moving part (WMP), the 1SDA072405R1 is designed for use with the corresponding SACE Emax 2 fixed part. The E2.2H performance level provides an ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 500–690 V AC, together with strong short-time withstand performance for demanding high-current switchboards.
The ABB SACE Emax 2 E2.2H is engineered for high-current low-voltage distribution systems where strong short-circuit performance and selective electronic protection are required. Its Ekip Touch LSI release combines long-time overload protection with short-time delayed and instantaneous short-circuit functions, enabling engineers to coordinate breaker operation and isolate faults while helping maintain continuity elsewhere in the distribution network.
The E2.2H performance level provides substantial fault-interruption capability, while the withdrawable design improves maintainability by allowing the moving part to be separated from its compatible fixed part for inspection, servicing or replacement. Combined with the Ekip Touch interface, auxiliary contacts and breaker-position indication, the 1SDA072405R1 is well suited to critical high-current switchboards requiring dependable protection and operational flexibility.
| Series | SACE Emax 2 E2.2 |
|---|---|
| ABB order code | 1SDA072405R1 |
| Product group | Emax2 Air Circuit Breaker |
| Product type | Air circuit breaker moving part |
| Performance level | H |
| Version | Withdrawable moving part (WMP) |
| Number of poles | 3 |
| Rated current In | 2000 A |
| Current type | AC |
| Rated operational voltage Ue | 690 V AC |
| Rated insulation voltage Ui | 1000 V AC |
| Rated impulse withstand voltage Uimp | 12 kV |
| Frequency | 50/60 Hz |
| Icu at 400 V AC | 100 kA |
| Icu at 415 V AC | 100 kA |
| Icu at 440 V AC | 100 kA |
| Icu at 500 V AC | 85 kA |
| Icu at 525 V AC | 85 kA |
| Icu at 690 V AC | 85 kA |
| Rated service short-circuit breaking capacity Ics | 100% of Icu |
| Rated short-time withstand current Icw (1 s) | 85 kA |
| Rated short-time withstand current Icw (3 s) | 66 kA |
| Protection release | Ekip Touch LSI |
| Release type | Electronic |
| Protection functions | Long-time overload (L), short-time delayed short circuit (S) and instantaneous short circuit (I) |
| Integrated earth-fault protection | No |
| User interface | Touchscreen |
| Auxiliary contacts | 4 |
| Breaker indication | Open / closed |
| Main-circuit connection | Via corresponding fixed part |
| Mechanical durability | 25,000 operating cycles |
| Product net width | 317 mm |
| Product net height | 425 mm |
| Product net depth | 383 mm |
| Product net weight | 48 kg |
| Standard | IEC 60947-2 |
| GTIN / EAN | 8015644762551 |
The ABB 1SDA072405R1 is a SACE Emax 2 E2.2H 2000 A three-pole withdrawable air circuit breaker moving part equipped with an Ekip Touch LSI electronic protection release, four auxiliary contacts and circuit-breaker open/closed indication.
The Ekip Touch LSI release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. This LSI configuration does not include integrated earth-fault protection.
The ABB E2.2H 1SDA072405R1 has a rated current of 2000 A, making it suitable for high-current industrial, commercial and infrastructure distribution circuits.
The E2.2H 2000 provides an ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 500–690 V AC, with short-time withstand ratings of 85 kA for 1 s and 66 kA for 3 s.
This product is a withdrawable moving part (WMP) designed for use with the corresponding ABB SACE Emax 2 fixed part to form a complete withdrawable air circuit breaker installation.
ABB SACE Emax 2 air circuit breakers combine high-current switching, configurable electronic protection and service-friendly withdrawable construction to provide dependable protection for demanding industrial, commercial and infrastructure power-distribution systems.
We use cookies