ABB 1SDA072401R1 is a SACE Emax 2 E2.2H 2000 A three-pole withdrawable air circuit breaker moving part with an Ekip Dip LI electronic trip unit for high-performance low-voltage power distribution protection.
£7,688.67
The ABB 1SDA072401R1 is a high-performance Emax 2 E2.2H 2000 air circuit breaker moving part designed for protection and switching in demanding low-voltage electrical distribution systems. This three-pole configuration combines a 2000 A rated current with an Ekip Dip LI electronic trip unit, providing reliable overload and instantaneous short-circuit protection for industrial, commercial and infrastructure power systems.
As part of the advanced ABB SACE Emax 2 air circuit breaker series, the E2.2H is engineered for high-current distribution applications requiring strong short-circuit performance and dependable operation. The Ekip Dip LI solid-state release provides adjustable protection while the Emax 2 platform supports efficient switchboard integration, maintenance and system protection.
This model is a 3-pole withdrawable moving part (WMP) rated at 2000 A and 690 V AC. The E2.2H performance level provides a rated ultimate short-circuit breaking capacity of up to 100 kA at 400–440 V AC, making the breaker suitable for installations with demanding prospective fault-current levels.
Air circuit breakers such as the ABB SACE Emax 2 E2.2H provide switching and protection for high-current low-voltage distribution circuits. The electronic trip unit monitors circuit conditions and initiates interruption when configured protection thresholds are exceeded, helping protect switchgear, conductors and connected equipment against overloads and severe short-circuit faults.
The Ekip Dip LI release combines long-time overload protection with instantaneous short-circuit protection. Together with the E2.2H frame's high breaking performance and withdrawable architecture, this makes the 1SDA072401R1 well suited to switchboards where dependable protection, high fault-current capability and straightforward maintenance are important.
| Series | SACE Emax 2 |
|---|---|
| ABB order code | 1SDA072401R1 |
| EAN | 8015644762513 |
| Product type | Air circuit breaker moving part |
| Frame | E2.2H |
| Short-circuit performance level | H |
| Rated current (In) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Number of poles | 3 |
| Trip unit | Ekip Dip LI |
| Release type | Electronic |
| Protection functions | L and I |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400–440 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw), 1 s | 85 kA |
| Rated short-time withstand current (Icw), 3 s | 66 kA |
| Current type | AC |
| Configuration | Withdrawable moving part (WMP) |
| Standard | IEC 60947-2 |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA072401R1 is an Emax 2 E2.2H 2000 A three-pole air circuit breaker moving part equipped with an Ekip Dip LI electronic trip unit.
The breaker has a rated current and rated uninterrupted current of 2000 A.
The Ekip Dip LI provides L long-time overload protection and I instantaneous short-circuit protection.
The E2.2H has a rated ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 500–690 V AC.
This model is a withdrawable moving part (WMP) designed for use with the appropriate Emax 2 fixed part in a compatible switchboard installation.
It is suitable for high-current low-voltage distribution applications including main switchboards, industrial power systems, feeder circuits, transformer distribution and commercial or infrastructure installations.
ABB SACE Emax 2 air circuit breakers are designed for demanding low-voltage power distribution systems where dependable protection, high short-circuit performance and maintainable switchgear architecture are required.