Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072389R1 SACE Emax 2 E2.2N 2000 A three-pole withdrawable air circuit breaker moving part with Ekip Hi-Touch LSIG electronic overload, short-circuit and earth-fault protection.
£9,968.97
The ABB E2.2N 2000 Ekip Hi-Touch LSIG 3p WMP, order code 1SDA072389R1, is a high-performance SACE Emax 2 air circuit breaker moving part designed for protection, switching and advanced monitoring in demanding low-voltage AC power-distribution systems. This three-pole E2.2N model combines a rated uninterrupted current of 2000 A with ABB's advanced Ekip Hi-Touch LSIG electronic protection release.
The Ekip Hi-Touch LSIG release provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. The Hi-Touch platform extends the breaker beyond core protection with advanced measurement and monitoring capabilities, supporting detailed supervision and coordinated protection within sophisticated industrial and infrastructure electrical networks.
Supplied as a withdrawable moving part (WMP), the breaker is designed for use with the corresponding SACE Emax 2 fixed part. The E2.2N performance level provides an ultimate short-circuit breaking capacity of 66 kA from 400 V through 690 V AC, together with a rated short-time withstand current of 66 kA for 1 s, making it well suited to high-current distribution systems requiring strong fault performance and maintainability.
The ABB SACE Emax 2 E2.2N is engineered for high-current low-voltage systems requiring comprehensive electronic protection and advanced supervision. Its Ekip Hi-Touch LSIG release combines long-time overload, short-time delayed, instantaneous short-circuit and earth-fault functions, supporting coordinated protection against the principal electrical faults encountered in complex distribution networks.
The E2.2N combines 66 kA short-circuit breaking capability with the maintainability of withdrawable construction. The moving part can be separated from its compatible fixed part for inspection, servicing or replacement, while the Hi-Touch platform's advanced monitoring capabilities make this model particularly suitable for critical switchboards where protection performance, system visibility and continuity of service are important.
| Series | SACE Emax 2 E2.2 |
|---|---|
| ABB order code | 1SDA072389R1 |
| Product group | Emax2 Air Circuit Breaker |
| Product type | Air circuit breaker moving part |
| Performance level | N |
| Version | Withdrawable moving part (WMP) |
| Number of poles | 3 |
| Rated current In | 2000 A |
| Rated uninterrupted current Iu | 2000 A |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage Ui | 1000 V AC |
| Rated impulse withstand voltage Uimp | 12 kV |
| Icu at 400 V AC | 66 kA |
| Icu at 415 V AC | 66 kA |
| Icu at 440 V AC | 66 kA |
| Icu at 500 V AC | 66 kA |
| Icu at 525 V AC | 66 kA |
| Icu at 690 V AC | 66 kA |
| Rated service short-circuit breaking capacity Ics | 100% of Icu |
| Rated short-time withstand current Icw (1 s) | 66 kA |
| Rated short-time withstand current Icw (3 s) | 50 kA |
| Protection release | Ekip Hi-Touch LSIG |
| Release type | Electronic |
| Protection functions | Long-time overload (L), short-time delayed short circuit (S), instantaneous short circuit (I) and earth fault (G) |
| Overload current setting | 800–2000 A |
| Integrated earth-fault protection | Yes |
| Auxiliary contacts | 4 |
| Breaker indication | Open / closed |
| Electrical durability at Ue ≤ 440 V | 10,000 operating cycles |
| Electrical durability at Ue 500–690 V | 8,000 operating cycles |
| Maximum electrical operating frequency | 30 cycles per hour |
| Mechanical durability | 25,000 operating cycles |
| Maximum mechanical operating frequency | 60 cycles per hour |
| Power loss | 450 W |
| Product net width | 317 mm |
| Product net height | 425 mm |
| Product net depth | 383 mm |
| Product net weight | 48 kg |
| Suitable for IT networks | Yes, up to 690 V |
| Standard | IEC |
| EAN | 8015644762391 |
The ABB 1SDA072389R1 is a SACE Emax 2 E2.2N 2000 A three-pole withdrawable air circuit breaker moving part equipped with an Ekip Hi-Touch LSIG electronic protection release, four auxiliary contacts and breaker open/closed indication.
The Ekip Hi-Touch LSIG release provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and integrated earth-fault protection, together with advanced measurement and monitoring capabilities.
The ABB E2.2N 1SDA072389R1 has a rated uninterrupted current of 2000 A, with an overload current setting range of 800–2000 A.
The E2.2N 2000 provides an ultimate short-circuit breaking capacity of 66 kA from 400–690 V AC, with Ics equal to 100% of Icu and short-time withstand ratings of 66 kA for 1 s and 50 kA for 3 s.
This product is a withdrawable moving part (WMP) designed for use with the corresponding ABB SACE Emax 2 fixed part to form a complete withdrawable air circuit breaker installation.
ABB SACE Emax 2 air circuit breakers combine high-current switching, comprehensive electronic protection, advanced monitoring and service-friendly withdrawable construction for dependable protection in demanding low-voltage power-distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.