1SDA072367R1 ABB E2.2H 1600 Ekip G Touch LSIG 3p WMP Air Circuit Breaker 1600 A

1SDA072367R1 ABB E2.2H 1600 Ekip G Touch LSIG 3p WMP Air Circuit Breaker 1600 A

ABB 1SDA072367R1 E2.2H 1600 Ekip G Touch LSIG 3p WMP is a 1600 A three-pole withdrawable SACE Emax 2 air circuit breaker with generator-focused LSIG electronic protection, Ekip Measuring Pro and 100 kA short-circuit breaking capacity at 400–440 V AC.

SKU: 1SDA072367R1MPN: 1SDA072367R1
Price
List Price £12,220.02 ex VAT
Your Price (ex VAT) Save 25%
£9,165.02 25% OFF
You save £3,055.01 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £9,165.02
Trade pricing is personalised to your account

Manufacturer Lead Time

£9,165.02

Why Choose the ABB E2.2H 1600 Ekip G Touch LSIG 3p WMP Air Circuit Breaker?

The ABB E2.2H 1600 Ekip G Touch LSIG 3p WMP, order code 1SDA072367R1, is a high-performance 1600 A three-pole withdrawable air circuit breaker from the ABB SACE Emax 2 range. Designed specifically for demanding generator and low-voltage power distribution applications, it combines the high-breaking-capacity E2.2H frame with ABB's Ekip G Touch LSIG solid-state electronic trip unit.

The Ekip G Touch LSIG release provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection, together with generator-specific protection functions. ABB integrates Ekip Measuring Pro functionality into this configuration, providing advanced electrical measurement alongside the touchscreen-based interface for protection configuration and system supervision.

Rated at 1600 A with a rated operational voltage of 690 V AC, the E2.2H provides rated ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 500–690 V AC. Its withdrawable moving-part construction, substantial short-time withstand capability and generator-focused electronic protection make the 1SDA072367R1 particularly suitable for generator incomers, critical distribution switchboards and high-fault-level electrical installations.

Key Advantages

  • High-performance ABB SACE Emax 2 E2.2H air circuit breaker for generator and power distribution protection.
  • 1600 A rated uninterrupted current for high-current industrial and critical-power systems.
  • Three-pole configuration for three-phase AC electrical networks.
  • Ekip G Touch LSIG electronic trip unit with generator-specific protection functionality.
  • Long-time overload, short-time delayed, instantaneous short-circuit and earth-fault protection.
  • 100 kA Icu at 400–440 V AC for high prospective fault-current installations.
  • 85 kA Icu at 500–690 V AC.
  • Ics equal to 100% of Icu across the specified voltage ratings.
  • 85 kA short-time withstand current for 1 s and 66 kA for 3 s.
  • Integrated Ekip Measuring Pro functionality for advanced electrical measurement.
  • Touchscreen interface supports intuitive protection configuration and monitoring.
  • Withdrawable construction supports efficient switchboard inspection, servicing and replacement.

Key Features

  • ABB SACE Emax 2 E2.2H series.
  • 1600 A rated current.
  • Three-pole (3P) configuration.
  • Withdrawable moving part, version W.
  • Ekip G Touch LSIG solid-state electronic release.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 50/60 Hz operating frequency.
  • 100 kA Icu at 400–440 V AC.
  • 85 kA Icu at 500–690 V AC.
  • 100 kA Ics at 400–440 V AC.
  • 85 kA Ics at 500–690 V AC.
  • 85 kA Icw for 1 s.
  • 66 kA Icw for 3 s.
  • 0.4–1 × In adjustable long-time overload protection.
  • 0.6–10 × In adjustable short-time protection.
  • 1.5–15 × In adjustable instantaneous protection.
  • 0.1–1 × In adjustable earth-fault protection.
  • Integrated generator-specific protection functions.
  • Integrated Ekip Measuring Pro measurement functionality.
  • Four auxiliary contacts with circuit breaker open/closed position indication.

Advanced Generator Protection with High Breaking Capacity

The ABB Ekip G Touch platform is designed for generator and advanced power distribution applications where conventional overcurrent protection must be complemented by generator-specific protection and detailed electrical measurement. The LSIG release provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection, while Ekip Measuring Pro adds advanced measurement functionality for greater visibility of system operating conditions.

Combined with the E2.2H frame, the trip unit provides particularly strong fault-management performance. The breaker offers 100 kA ultimate and service breaking capacity at 400–440 V AC, retaining 85 kA capability at voltages up to 690 V AC. Short-time withstand ratings of 85 kA for 1 s and 66 kA for 3 s further support selective protection strategies in critical generator and distribution switchboards.

Typical Applications

  • Generator protection and generator incomer circuits.
  • Power-generation switchboards.
  • Main low-voltage electrical distribution switchboards.
  • Industrial power distribution systems.
  • Critical and standby power installations.
  • Data centre electrical distribution.
  • Manufacturing and process plant switchgear.
  • Infrastructure and utility installations.
  • High-fault-level three-phase AC distribution systems.
  • Networks requiring generator-specific protection, LSIG functionality and advanced electrical measurement.

Technical Specifications

Product range SACE Emax 2
Series E2.2H
Order code / MPN 1SDA072367R1
Product group Emax2 Air Circuit Breaker
Product type Air circuit breaker
Construction Withdrawable moving part
Version W
Number of poles 3P
Rated current (In) 1600 A
Rated uninterrupted current (Iu) 1600 A
Rated operational voltage (Ue) 690 V AC
Rated voltage (Ur) 690 V
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Frequency 50/60 Hz
Current type AC
Trip unit Ekip G Touch LSIG
Release type Solid-state electronic
Protection functions L (long-time overload), S (short-time delayed short circuit), I (instantaneous short circuit) and G (earth fault)
Application focus Generator and power distribution protection
Short-circuit performance level H
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 85 kA
Rated ultimate short-circuit breaking capacity (Icu) at 525 V AC 85 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 85 kA
Rated service short-circuit breaking capacity (Ics) at 400–440 V AC 100 kA
Rated service short-circuit breaking capacity (Ics) at 500–690 V AC 85 kA
Ics as percentage of Icu 100%
Rated short-time withstand current (Icw) 85 kA for 1 s
Long-time overload protection adjustment 0.4–1 × In
Short-time delayed short-circuit protection adjustment 0.6–10 × In
Instantaneous short-circuit protection adjustment 1.5–15 × In
Earth-fault protection adjustment 0.1–1 × In
Integrated earth-fault protection Yes
Generator-specific protection Yes
Measurement functionality Ekip Measuring Pro
Auxiliary contacts 4
Position indication Circuit breaker open/closed
Connecting capacity 1200 mm²
Power loss 288 W
Mechanical durability 25,000 operating cycles
Electrical durability at Ue ≤ 440 V 12,000 operating cycles
Electrical durability at Ue 500–690 V 10,000 operating cycles
Maximum mechanical operating frequency 60 cycles per hour
Maximum electrical operating frequency 30 cycles per hour
Dimensions (W × H × D) 317 × 425 × 383 mm
Product net weight 48 kg
Standard IEC 60947-2
Country of origin Italy
EAN 8015644762179

Frequently Asked Questions

What is the ABB 1SDA072367R1 used for?

The ABB 1SDA072367R1 is a 1600 A three-pole withdrawable air circuit breaker designed for demanding generator and low-voltage power distribution applications, including generator incomers, industrial switchboards, critical power systems and main distribution boards.

What protection does the Ekip G Touch LSIG trip unit provide?

The Ekip G Touch LSIG electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. This generator-focused version also incorporates specific generator protection functionality and Ekip Measuring Pro measurement capabilities.

What is the breaking capacity of the ABB E2.2H 1600?

The E2.2H 1600 provides rated ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 500–690 V AC. Its rated service breaking capacity is 100% of Icu.

What are the adjustable protection ranges of the ABB 1SDA072367R1?

The Ekip G Touch LSIG provides long-time overload adjustment of 0.4–1 × In, short-time protection adjustment of 0.6–10 × In, instantaneous protection adjustment of 1.5–15 × In and earth-fault protection adjustment of 0.1–1 × In.

Is the ABB 1SDA072367R1 fixed or withdrawable?

The 1SDA072367R1 is a withdrawable moving part designed for installation with a compatible ABB SACE Emax 2 E2.2 fixed part, facilitating inspection, servicing and replacement within the switchboard.

Trusted Protection from ABB

ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, advanced electronic protection, generator-specific functionality and comprehensive electrical measurement for demanding industrial, infrastructure and critical power distribution systems.