Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072360R1 SACE Emax 2 E2.2S 1600 A three-pole withdrawable air circuit breaker moving part with Ekip G Hi-Touch LSIG electronic protection for generator and advanced power-distribution applications.
£9,325.82
The ABB E2.2S 1600 Ekip G Hi-Touch LSIG 3p WMP, order code 1SDA072360R1, is a high-performance SACE Emax 2 air circuit breaker moving part designed for advanced protection, switching and power management in demanding low-voltage power-distribution and generator applications. This three-pole E2.2S model combines a rated uninterrupted current of 1600 A with ABB's advanced Ekip G Hi-Touch LSIG electronic protection release.
The Ekip G Hi-Touch LSIG release combines generator-oriented functionality with long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. The Hi-Touch platform also supports advanced electrical measurement, monitoring and network-analysis capabilities, making this configuration particularly suitable for sophisticated generation, critical-power and industrial distribution systems.
This version is supplied as a withdrawable moving part (WMP) for use with the corresponding SACE Emax 2 fixed part. The E2.2S performance level provides an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC, together with a rated short-time withstand current of 66 kA for 1 s.
The ABB SACE Emax 2 E2.2S provides comprehensive protection for high-current low-voltage power systems. Its Ekip G Hi-Touch LSIG release combines long-time overload, short-time delayed, instantaneous short-circuit and earth-fault protection with generator-oriented functionality, helping coordinate protection across generation equipment and downstream distribution networks.
The E2.2S frame combines strong short-circuit breaking and withstand performance with the maintainability of a withdrawable design. The moving part can be separated from its compatible fixed part for inspection, servicing or replacement, while the advanced Hi-Touch platform supports detailed monitoring and network analysis for critical industrial, infrastructure and power-generation installations.
| Series | SACE Emax 2 E2.2 |
|---|---|
| ABB order code | 1SDA072360R1 |
| Product group | Emax2 Air Circuit Breaker |
| Product type | Air circuit breaker moving part |
| Performance level | S |
| Version | Withdrawable moving part (WMP) |
| Number of poles | 3 |
| Rated current In | 1600 A |
| Rated uninterrupted current Iu | 1600 A |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage Ui | 1000 V AC |
| Rated impulse withstand voltage Uimp | 12 kV |
| Icu at 400 V AC | 85 kA |
| Icu at 415 V AC | 85 kA |
| Icu at 440 V AC | 85 kA |
| Icu at 500 V AC | 66 kA |
| Icu at 525 V AC | 66 kA |
| Icu at 690 V AC | 66 kA |
| Rated service short-circuit breaking capacity Ics | 100% of Icu |
| Rated short-time withstand current Icw (1 s) | 66 kA |
| Rated short-time withstand current Icw (3 s) | 50 kA |
| Protection release | Ekip G Hi-Touch LSIG |
| Release type | Electronic |
| Protection functions | Long-time overload (L), short-time delayed short circuit (S), instantaneous short circuit (I) and earth fault (G) |
| Integrated earth-fault protection | Yes |
| Generator-oriented protection | Ekip G platform |
| Connecting capacity | 1200 mm² |
| Electrical durability at Ue ≤ 440 V | 12,000 operating cycles |
| Electrical durability at Ue 500–690 V | 10,000 operating cycles |
| Maximum electrical operating frequency | 30 cycles per hour |
| Mechanical durability | 25,000 operating cycles |
| Maximum mechanical operating frequency | 60 cycles per hour |
| Power loss | 288 W |
| Suitable for IT networks | Yes, up to 690 V |
| Standard | IEC |
| EAN | 8015644762100 |
The ABB 1SDA072360R1 is a SACE Emax 2 E2.2S 1600 A three-pole withdrawable air circuit breaker moving part equipped with an Ekip G Hi-Touch LSIG electronic protection release.
The Ekip G Hi-Touch LSIG release provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and integrated earth-fault protection, together with advanced generator-oriented protection, monitoring and network-analysis functionality.
The ABB E2.2S 1SDA072360R1 has a rated uninterrupted current of 1600 A, making it suitable for substantial industrial, infrastructure, generator and critical-power distribution systems.
The E2.2S 1600 provides an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC, together with short-time withstand ratings of 66 kA for 1 s and 50 kA for 3 s.
This product is a withdrawable moving part (WMP) designed for use with the corresponding ABB SACE Emax 2 fixed part to form a complete withdrawable air circuit breaker installation.
ABB SACE Emax 2 air circuit breakers combine high-current switching, comprehensive electronic protection, generator-focused functionality and advanced power management with flexible withdrawable switchgear integration for demanding low-voltage electrical systems.