1SDA072320R1 ABB E2.2S 1250 Ekip G Hi-Touch LSIG 3p WMP Air Circuit Breaker 1250 A

1SDA072320R1 ABB E2.2S 1250 Ekip G Hi-Touch LSIG 3p WMP Air Circuit Breaker 1250 A

ABB 1SDA072320R1 E2.2S 1250 Ekip G Hi-Touch LSIG 3p WMP is a 1250 A three-pole withdrawable SACE Emax 2 air circuit breaker with generator-focused LSIG electronic protection, advanced monitoring and 85 kA short-circuit breaking capacity at 400 V AC.

SKU: 1SDA072320R1MPN: 1SDA072320R1
Price
List Price £11,654.81 ex VAT
Your Price (ex VAT) Save 25%
£8,741.11 25% OFF
You save £2,913.70 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,741.11
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,741.11

Why Choose the ABB E2.2S 1250 Ekip G Hi-Touch LSIG 3p WMP Air Circuit Breaker?

The ABB E2.2S 1250 Ekip G Hi-Touch LSIG 3p WMP, order code 1SDA072320R1, is a high-performance three-pole air circuit breaker from the ABB SACE Emax 2 range, designed for demanding low-voltage power distribution and generator protection applications. Rated at 1250 A, it combines the E2.2S frame with ABB's advanced Ekip G Hi-Touch LSIG solid-state electronic trip unit for comprehensive overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection.

The Ekip G Hi-Touch platform combines generator-focused protection with advanced measurement, monitoring and network-analysis capabilities. Its LSIG protection functions help safeguard cables, busbars, switchgear, generators and connected equipment against overloads, short circuits and earth faults, while advanced monitoring capabilities provide greater visibility of electrical network performance.

With a rated uninterrupted current of 1250 A, rated voltage of 690 V AC and rated ultimate short-circuit breaking capacity of 85 kA at 400 V AC, 50 Hz, the 1SDA072320R1 provides substantial fault interruption capability for critical electrical installations. Its withdrawable moving-part construction enables installation with a compatible E2.2 fixed part and supports efficient inspection, servicing and replacement within electrical switchboards.

Key Advantages

  • High-performance ABB SACE Emax 2 air circuit breaker for demanding generator and power distribution applications.
  • 1250 A rated uninterrupted current for industrial, infrastructure and critical-power installations.
  • Three-pole configuration for three-phase AC electrical systems.
  • Ekip G Hi-Touch LSIG electronic trip unit combining generator-focused protection with advanced monitoring.
  • LSIG functions provide long-time overload, short-time delayed, instantaneous short-circuit and earth-fault protection.
  • 85 kA rated ultimate short-circuit breaking capacity at 400 V AC, 50 Hz.
  • 500–1250 A adjustable overload release range.
  • 750–12500 A adjustable short-time delayed short-circuit release range.
  • 1875–18750 A adjustable instantaneous short-circuit release range.
  • Four change-over auxiliary contacts support signalling and control integration.
  • Withdrawable moving-part construction facilitates switchgear servicing and maintenance.

Key Features

  • ABB SACE Emax 2 E2.2S series.
  • 1250 A rated current.
  • Three-pole (3P) configuration.
  • Ekip G Hi-Touch LSIG solid-state electronic release.
  • 690 V AC rated voltage.
  • 85 kA Icu at 400 V AC, 50 Hz.
  • 500–1250 A overload protection adjustment range.
  • 750–12500 A short-time delayed protection adjustment range.
  • 1875–18750 A instantaneous protection adjustment range.
  • Integrated G earth-fault protection.
  • Four change-over auxiliary contacts.
  • Circuit breaker open/closed position indication.
  • Optional motor operator for remote or automated operation.
  • Advanced generator protection, measurement and network-analysis functionality through the Ekip G Hi-Touch platform.
  • Withdrawable moving-part design for compatible ABB Emax 2 E2.2 switchgear.

Advanced Generator Protection and Power Monitoring

The ABB Ekip G Hi-Touch platform is designed for sophisticated generator and power distribution applications where advanced protection and detailed electrical system information are required. In addition to the core LSIG functions, the platform supports generator-focused protection, advanced measurement and network-analysis capabilities, helping operators supervise electrical conditions and assess power-system performance.

Combined with the E2.2S frame, the Ekip G Hi-Touch LSIG release provides comprehensive long-time, short-time delayed, instantaneous and earth-fault protection. Its 85 kA short-circuit breaking capacity at 400 V AC makes the 1SDA072320R1 particularly suitable for generator incomers, critical distribution boards and other installations where high fault levels, protection selectivity and continuity of service are important design considerations.

Typical Applications

  • Generator protection and generator incomer circuits.
  • Power-generation switchboards.
  • Main low-voltage electrical distribution switchboards.
  • Industrial power distribution systems.
  • Critical and standby power systems.
  • Data centre electrical distribution.
  • Manufacturing and process plant switchgear.
  • Infrastructure and utility installations.
  • Three-phase AC networks requiring high breaking capacity and comprehensive LSIG protection.
  • Electrical systems requiring advanced generator protection, measurement and network monitoring.

Technical Specifications

Product range SACE Emax 2
Series E2.2S
Order code / MPN 1SDA072320R1
Product group Emax2 Air Circuit Breaker
Product type Air circuit breaker
Construction Withdrawable moving part
Number of poles 3P
Rated current (In) 1250 A
Rated uninterrupted current (Iu) 1250 A
Rated voltage 690 V AC
Current type AC
Trip unit Ekip G Hi-Touch LSIG
Release type Solid-state electronic
Protection functions L (long-time overload), S (short-time delayed short circuit), I (instantaneous short circuit) and G (earth fault)
Application focus Generator and power distribution protection
Short-circuit performance level S
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz 85 kA
Overload release adjustment range 500–1250 A
Short-time delayed short-circuit release adjustment range 750–12500 A
Instantaneous short-circuit release adjustment range 1875–18750 A
Integrated earth-fault protection Yes
Complete device with protection unit Yes
Auxiliary contacts 4 change-over contacts
Position indication Circuit breaker open/closed
Control element Push button
Main circuit connection Via separate fixed part / chassis
Motor operator Optional
Integrated motor operator No
Integrated undervoltage release No
DIN rail mounting No
DIN rail mounting optional No
Degree of protection IP30
Power loss 176 W
Dimensions 383 × 425 × 317 mm
Product net weight 53 kg
Standard / approval IEC
Country of origin Italy
EAN 8015644761707

Frequently Asked Questions

What is the ABB 1SDA072320R1 used for?

The ABB 1SDA072320R1 is a 1250 A three-pole air circuit breaker designed for demanding low-voltage power distribution and generator protection applications, including generator incomers, industrial switchboards, critical power systems and main distribution boards.

What protection does the Ekip G Hi-Touch LSIG trip unit provide?

The Ekip G Hi-Touch LSIG electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection, together with advanced generator protection, measurement and network-monitoring capabilities.

What is the breaking capacity of the ABB E2.2S 1250?

The ABB E2.2S 1250 has a rated ultimate short-circuit breaking capacity of 85 kA at 400 V AC, 50 Hz, providing high fault interruption capability for demanding low-voltage electrical systems.

What are the adjustable protection ranges of the ABB 1SDA072320R1?

The overload release can be adjusted from 500–1250 A, the short-time delayed short-circuit release from 750–12500 A, and the instantaneous short-circuit release from 1875–18750 A. The LSIG configuration also provides integrated earth-fault protection.

Is the ABB 1SDA072320R1 a fixed or withdrawable circuit breaker?

The 1SDA072320R1 is a withdrawable moving part designed for installation with a compatible ABB SACE Emax 2 E2.2 fixed part.

Trusted Protection from ABB

ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, advanced electronic protection, generator-focused functionality and comprehensive power monitoring for demanding industrial, infrastructure and critical power distribution systems.