ABB 1SDA072319R1 E2.2S 1250 Ekip Hi-Touch LSIG 3p WMP is a 1250 A three-pole withdrawable SACE Emax 2 air circuit breaker with advanced LSIG electronic protection, power monitoring and 85 kA short-circuit breaking capacity at 400 V AC.
£8,346.45
The ABB E2.2S 1250 Ekip Hi-Touch LSIG 3p WMP, order code 1SDA072319R1, is a high-performance three-pole air circuit breaker from the ABB SACE Emax 2 range, designed for advanced protection and switching in demanding low-voltage electrical distribution systems. Rated at 1250 A, it combines the E2.2S frame with ABB's advanced Ekip Hi-Touch LSIG electronic trip unit for long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection.
The Ekip Hi-Touch platform provides sophisticated protection alongside advanced measurement, monitoring and power-quality capabilities. Its LSIG protection functions help protect cables, busbars, switchgear and connected equipment against overloads, short circuits and earth faults, while the short-time protection function supports selective coordination between protective devices.
With a rated uninterrupted current of 1250 A, rated operational voltage up to 690 V AC and rated ultimate short-circuit breaking capacity of 85 kA at 400 V AC, the 1SDA072319R1 is suited to demanding industrial, commercial, infrastructure and critical-power applications. Its withdrawable moving-part construction enables installation with a compatible E2.2 fixed part and supports efficient inspection, servicing and replacement within electrical switchboards.
Air circuit breakers such as the ABB SACE Emax 2 provide switching and protection for high-current low-voltage distribution circuits. The E2.2S performance level provides substantial short-circuit interruption capability, while the Ekip Hi-Touch electronic trip unit adds sophisticated protection and system monitoring for installations where selectivity, continuity of service and detailed electrical information are important.
The Ekip Hi-Touch LSIG release combines long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. Beyond these core protection functions, the Hi-Touch platform supports advanced electrical measurement, monitoring and power-quality analysis, making the 1SDA072319R1 particularly suitable for sophisticated distribution systems where comprehensive protection and visibility of network performance are required.
| Product range | SACE Emax 2 |
|---|---|
| Series | E2.2S |
| Order code / MPN | 1SDA072319R1 |
| Product group | Emax2 Air Circuit Breaker |
| Product type | Air circuit breaker |
| Construction | Withdrawable moving part |
| Number of poles | 3P |
| Rated current (In) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated voltage | 690 V AC |
| Current type | AC |
| Trip unit | Ekip Hi-Touch LSIG |
| Release type | Solid-state electronic |
| Protection functions | L (long-time overload), S (short-time delayed short circuit), I (instantaneous short circuit) and G (earth fault) |
| Short-circuit performance level | S |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz | 85 kA |
| Overload release adjustment range | 500–1250 A |
| Short-time delayed short-circuit release adjustment range | 750–12500 A |
| Instantaneous short-circuit release adjustment range | 1875–18750 A |
| Integrated earth-fault protection | Yes |
| Complete device with protection unit | Yes |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open/closed |
| Motor operator | Optional |
| Integrated motor operator | No |
| Integrated undervoltage release | No |
| DIN rail mounting | No |
| DIN rail mounting optional | No |
| Standard | IEC 60947-2 |
| EAN | 8015644761684 |
The ABB 1SDA072319R1 is a 1250 A three-pole air circuit breaker used for switching, protection and advanced monitoring in demanding low-voltage power distribution systems, including industrial plants, commercial infrastructure, data centres and main distribution switchboards.
The Ekip Hi-Touch LSIG electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection, together with advanced measurement, monitoring and power-quality capabilities.
The ABB E2.2S 1250 has a rated ultimate short-circuit breaking capacity of 85 kA at 400 V AC, 50 Hz, providing high fault interruption capability for demanding low-voltage distribution systems.
The overload release can be adjusted from 500–1250 A, the short-time delayed short-circuit release from 750–12500 A, and the instantaneous short-circuit release from 1875–18750 A. The LSIG configuration also provides earth-fault protection.
The 1SDA072319R1 is a withdrawable moving part designed for installation with a compatible ABB SACE Emax 2 E2.2 fixed part.
ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, advanced electronic protection, power monitoring capabilities and service-friendly withdrawable construction for demanding industrial, commercial and critical power distribution systems.