1SDA072313R1 ABB E2.2S 1250 Ekip Dip LSIG 3p WMP Air Circuit Breaker

1SDA072313R1 ABB E2.2S 1250 Ekip Dip LSIG 3p WMP Air Circuit Breaker

ABB 1SDA072313R1 E2.2S 1250 Ekip Dip LSIG 3p WMP is a 1250 A three-pole withdrawable SACE Emax 2 air circuit breaker moving part with Ekip Dip LSIG electronic overload, short-circuit and ground-fault protection.

SKU: 1SDA072313R1MPN: 1SDA072313R1
Price
List Price £7,776.40 ex VAT
Your Price (ex VAT) Save 25%
£5,832.30 25% OFF
You save £1,944.10 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,832.30
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,832.30

Why Choose the ABB E2.2S 1250 Ekip Dip LSIG 3p WMP Air Circuit Breaker?

The ABB E2.2S 1250 Ekip Dip LSIG 3p WMP, order code 1SDA072313R1, is a high-performance three-pole withdrawable air circuit breaker moving part from the ABB SACE Emax 2 range. Rated at 1250 A, it combines the E2.2S frame with an Ekip Dip LSIG solid-state electronic trip unit for comprehensive overload, short-circuit and ground-fault protection in demanding low-voltage distribution systems.

The Ekip Dip LSIG release provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and ground-fault protection. DIP-switch configuration provides straightforward local adjustment of the principal protection parameters, making this breaker particularly suitable for industrial and infrastructure applications requiring dependable protection without the additional interface features of a touchscreen trip unit.

The E2.2S performance class provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–415 V AC and 66 kA at 690 V AC. It also offers a rated short-time withstand current of 66 kA for 1 s and 50 kA for 3 s, supporting selective protection schemes in networks with substantial prospective fault currents.

Key Advantages

  • ABB SACE Emax 2 air circuit breaker for demanding low-voltage power distribution.
  • 1250 A rated uninterrupted current for substantial industrial and infrastructure loads.
  • Ekip Dip LSIG electronic trip unit with straightforward DIP-switch configuration.
  • LSIG functionality provides long-time, short-time, instantaneous and ground-fault protection.
  • 85 kA Icu at 400–415 V AC provides strong fault-clearing performance.
  • 66 kA Icu at 690 V AC supports higher-voltage low-voltage distribution networks.
  • 66 kA Icw for 1 s supports selective protection and system coordination.
  • Three-pole withdrawable construction facilitates servicing, inspection and replacement.

Key Features

  • ABB SACE Emax 2 E2.2S air circuit breaker platform.
  • 1250 A rated uninterrupted current.
  • Three-pole configuration.
  • Withdrawable moving-part design.
  • Ekip Dip LSIG solid-state electronic protection release.
  • L – long-time overload protection.
  • S – short-time delayed short-circuit protection.
  • I – instantaneous short-circuit protection.
  • G – integrated ground-fault protection.
  • Overload release adjustment range of 500–1250 A.
  • 85 kA breaking capacity at 400–415 V AC.
  • 66 kA short-time withstand current for 1 s.
  • Four auxiliary contacts for breaker status and control integration.
  • Open/closed circuit-breaker position indication.

Comprehensive Protection for Low-Voltage Power Distribution

ABB SACE Emax 2 air circuit breakers combine high short-circuit performance with electronic protection for modern low-voltage networks. The E2.2S frame provides 85 kA ultimate breaking capacity at 400–415 V AC and 66 kA at 690 V AC, while its substantial short-time withstand capability supports selective coordination in industrial and infrastructure distribution systems.

The Ekip Dip LSIG release provides the principal protection functions required for comprehensive distribution-system protection while retaining straightforward local configuration. Combined with the withdrawable Emax 2 construction, the 1SDA072313R1 provides a practical solution for switchboards requiring high fault-clearing capability, ground-fault protection, selectivity and convenient maintenance.

Typical Applications

  • Industrial low-voltage switchboards and distribution panels.
  • Main and sub-main electrical distribution systems.
  • Manufacturing and process plants.
  • Commercial buildings and major infrastructure.
  • Data centres and critical power installations.
  • Transformer-fed distribution systems.
  • Utilities and energy infrastructure.
  • OEM switchgear and electrical panel assemblies.

Technical Specifications

Series SACE Emax 2
Frame E2.2S
ABB order code 1SDA072313R1
Product group Emax2 Air Circuit Breaker
Product type Air circuit breaker moving part
Rated uninterrupted current (Iu) 1250 A
Number of poles 3
Current type AC
Trip unit Ekip Dip LSIG
Release technology Solid-state electronic
Protection functions Long-time, short-time, instantaneous and ground-fault
Overload release setting range 500–1250 A
Integrated ground-fault protection Yes
Rated operational voltage Up to 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC 85 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 66 kA
Rated service short-circuit breaking capacity (Ics) 100% of Icu
Rated short-time withstand current (Icw), 1 s 66 kA
Rated short-time withstand current (Icw), 3 s 50 kA
Utilisation category Category B
Installation Withdrawable / draw-out moving part
Main-circuit connection Via separate fixed chassis part
Auxiliary contacts 4
Circuit-breaker indication Open / closed
Product width 317 mm
Product length 383 mm
Product depth 383 mm
EAN 8015644761639
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA072313R1 used for?

The ABB 1SDA072313R1 is a 1250 A three-pole withdrawable Emax 2 air circuit breaker moving part designed for switching and comprehensive protection in demanding low-voltage electrical distribution systems.

What protection unit is fitted to the ABB 1SDA072313R1?

It is fitted with an ABB Ekip Dip LSIG electronic trip unit, providing long-time overload, short-time delayed short-circuit, instantaneous short-circuit and ground-fault protection.

What is the rated current of the E2.2S 1250?

The ABB E2.2S 1250 has a rated uninterrupted current of 1250 A, with an overload release setting range of 500–1250 A.

What is the breaking capacity of the ABB E2.2S 1250?

The E2.2S performance class provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–415 V AC and 66 kA at 690 V AC, with a short-time withstand current of 66 kA for 1 s.

Does the ABB 1SDA072313R1 provide ground-fault protection?

Yes. The Ekip Dip LSIG release includes integrated ground-fault protection in addition to long-time overload, short-time delayed and instantaneous short-circuit protection.

Trusted Power Protection from ABB

ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, comprehensive electronic protection and flexible withdrawable construction for reliable operation in demanding low-voltage power distribution systems.