ABB 1SDA072313R1 E2.2S 1250 Ekip Dip LSIG 3p WMP is a 1250 A three-pole withdrawable SACE Emax 2 air circuit breaker moving part with Ekip Dip LSIG electronic overload, short-circuit and ground-fault protection.
£5,832.30
The ABB E2.2S 1250 Ekip Dip LSIG 3p WMP, order code 1SDA072313R1, is a high-performance three-pole withdrawable air circuit breaker moving part from the ABB SACE Emax 2 range. Rated at 1250 A, it combines the E2.2S frame with an Ekip Dip LSIG solid-state electronic trip unit for comprehensive overload, short-circuit and ground-fault protection in demanding low-voltage distribution systems.
The Ekip Dip LSIG release provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and ground-fault protection. DIP-switch configuration provides straightforward local adjustment of the principal protection parameters, making this breaker particularly suitable for industrial and infrastructure applications requiring dependable protection without the additional interface features of a touchscreen trip unit.
The E2.2S performance class provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–415 V AC and 66 kA at 690 V AC. It also offers a rated short-time withstand current of 66 kA for 1 s and 50 kA for 3 s, supporting selective protection schemes in networks with substantial prospective fault currents.
ABB SACE Emax 2 air circuit breakers combine high short-circuit performance with electronic protection for modern low-voltage networks. The E2.2S frame provides 85 kA ultimate breaking capacity at 400–415 V AC and 66 kA at 690 V AC, while its substantial short-time withstand capability supports selective coordination in industrial and infrastructure distribution systems.
The Ekip Dip LSIG release provides the principal protection functions required for comprehensive distribution-system protection while retaining straightforward local configuration. Combined with the withdrawable Emax 2 construction, the 1SDA072313R1 provides a practical solution for switchboards requiring high fault-clearing capability, ground-fault protection, selectivity and convenient maintenance.
| Series | SACE Emax 2 |
|---|---|
| Frame | E2.2S |
| ABB order code | 1SDA072313R1 |
| Product group | Emax2 Air Circuit Breaker |
| Product type | Air circuit breaker moving part |
| Rated uninterrupted current (Iu) | 1250 A |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Dip LSIG |
| Release technology | Solid-state electronic |
| Protection functions | Long-time, short-time, instantaneous and ground-fault |
| Overload release setting range | 500–1250 A |
| Integrated ground-fault protection | Yes |
| Rated operational voltage | Up to 690 V AC |
| Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw), 1 s | 66 kA |
| Rated short-time withstand current (Icw), 3 s | 50 kA |
| Utilisation category | Category B |
| Installation | Withdrawable / draw-out moving part |
| Main-circuit connection | Via separate fixed chassis part |
| Auxiliary contacts | 4 |
| Circuit-breaker indication | Open / closed |
| Product width | 317 mm |
| Product length | 383 mm |
| Product depth | 383 mm |
| EAN | 8015644761639 |
| Standard | IEC 60947-2 |
The ABB 1SDA072313R1 is a 1250 A three-pole withdrawable Emax 2 air circuit breaker moving part designed for switching and comprehensive protection in demanding low-voltage electrical distribution systems.
It is fitted with an ABB Ekip Dip LSIG electronic trip unit, providing long-time overload, short-time delayed short-circuit, instantaneous short-circuit and ground-fault protection.
The ABB E2.2S 1250 has a rated uninterrupted current of 1250 A, with an overload release setting range of 500–1250 A.
The E2.2S performance class provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–415 V AC and 66 kA at 690 V AC, with a short-time withstand current of 66 kA for 1 s.
Yes. The Ekip Dip LSIG release includes integrated ground-fault protection in addition to long-time overload, short-time delayed and instantaneous short-circuit protection.
ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, comprehensive electronic protection and flexible withdrawable construction for reliable operation in demanding low-voltage power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.