1SDA072305R1 ABB E2.2N 1250 Ekip Touch LSI 3p WMP Air Circuit Breaker

1SDA072305R1 ABB E2.2N 1250 Ekip Touch LSI 3p WMP Air Circuit Breaker

ABB 1SDA072305R1 SACE Emax 2 E2.2N 1250 A three-pole withdrawable air circuit breaker moving part with Ekip Touch LSI electronic overload and selective short-circuit protection.

SKU: 1SDA072305R1MPN: 1SDA072305R1
Price
List Price £6,509.56 ex VAT
Your Price (ex VAT) Save 25%
£4,882.17 25% OFF
You save £1,627.39 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £4,882.17
Trade pricing is personalised to your account

Manufacturer Lead Time

£4,882.17

Why Choose the ABB E2.2N 1250 Ekip Touch LSI 3p WMP Air Circuit Breaker?

The ABB E2.2N 1250 Ekip Touch LSI 3p WMP, order code 1SDA072305R1, is a SACE Emax 2 air circuit breaker moving part designed for protection, switching and control in low-voltage AC power distribution systems. This three-pole E2.2N model combines a rated uninterrupted current of 1250 A with ABB's advanced Ekip Touch LSI solid-state electronic protection release.

The Ekip Touch LSI trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. Its touchscreen-based interface supports intuitive configuration and access to protection and operating information, while the LSI protection architecture enables effective coordination and selective fault isolation in complex distribution networks.

This version is supplied as a withdrawable moving part (WMP) for use with the corresponding Emax 2 fixed chassis. It is rated for 690 V AC operation and provides an ultimate short-circuit breaking capacity of 66 kA at 400 V AC, making it suitable for substantial industrial, commercial and infrastructure power-distribution duties.

Key Advantages

  • ABB SACE Emax 2 E2.2N air circuit breaker platform for low-voltage power distribution.
  • 1250 A rated uninterrupted current for high-current circuits.
  • Three-pole configuration for three-phase AC networks.
  • Ekip Touch LSI electronic trip unit with advanced protection functionality.
  • Long-time, short-time delayed and instantaneous short-circuit protection.
  • 66 kA ultimate short-circuit breaking capacity at 400 V AC, 50 Hz.
  • Adjustable protection settings support coordination with upstream and downstream protective devices.
  • Withdrawable construction simplifies breaker inspection, servicing and replacement.
  • Four auxiliary change-over contacts provide useful breaker-status signalling.

Key Features

  • ABB SACE Emax 2 E2.2N series.
  • 1250 A rated uninterrupted current.
  • 3-pole configuration.
  • Ekip Touch LSI solid-state electronic release.
  • Long-time overload protection (L).
  • Short-time delayed short-circuit protection (S).
  • Instantaneous short-circuit protection (I).
  • 500–1250 A overload release adjustment range.
  • 750–12500 A short-time delayed short-circuit adjustment range.
  • 1875–18750 A instantaneous short-circuit adjustment range.
  • 690 V AC rated voltage.
  • 66 kA Icu at 400 V AC, 50 Hz.
  • Withdrawable moving part (WMP) construction.
  • Four auxiliary change-over contacts.
  • Open/closed circuit-breaker position indication.
  • Optional motor drive capability.

Reliable and Selective Protection for Power Distribution

The ABB SACE Emax 2 E2.2N provides dependable protection for high-current low-voltage distribution circuits. Its Ekip Touch LSI release combines long-time overload protection with short-time delayed and instantaneous short-circuit functions, allowing protection thresholds to be coordinated with other protective devices and helping limit unnecessary interruption to unaffected sections of an electrical installation.

The withdrawable design allows the breaker moving part to be removed from its compatible fixed chassis for maintenance, inspection or replacement. Combined with four auxiliary change-over contacts, open/closed status indication and optional motor operation, the E2.2N is well suited to modern switchboards requiring maintainability, automation capability and dependable electrical protection.

Typical Applications

  • Industrial low-voltage power distribution switchboards.
  • Main incomer and high-current feeder protection.
  • Manufacturing and process-industry electrical systems.
  • Commercial building power distribution.
  • Transformer secondary distribution systems.
  • Data centres and critical power infrastructure.
  • Utility and infrastructure electrical installations.
  • Three-phase AC networks requiring selective LSI protection.
  • Withdrawable switchgear requiring maintainable high-current circuit protection.

Technical Specifications

Series SACE Emax 2 E2.2
ABB order code 1SDA072305R1
Product type Air circuit breaker moving part
Performance level N
Version Withdrawable moving part (WMP)
Number of poles 3
Rated uninterrupted current Iu 1250 A
Current type AC
Rated voltage 690 V
Rated ultimate short-circuit breaking capacity Icu at 400 V, 50 Hz 66 kA
Protection release Ekip Touch LSI
Release technology Solid-state electronic
Protection functions Long-time overload (L), short-time delayed short circuit (S) and instantaneous short circuit (I)
Overload release adjustment range 500–1250 A
Short-time delayed short-circuit adjustment range 750–12500 A
Instantaneous short-circuit adjustment range 1875–18750 A
Integrated earth-fault protection No
Auxiliary contacts 4 change-over contacts
Breaker position indication Open / closed
Main-circuit connection Separate chassis / fixed part
Operating control Push button
Motor drive Optional
Protection rating IP30
Mechanical durability 25,000 operating cycles
Electrical durability 15,000 operating cycles
Dimensions (W × H × D) 317 × 425 × 383 mm
Net weight 49 kg
EAN 8015644761554

Frequently Asked Questions

What is the ABB 1SDA072305R1?

The ABB 1SDA072305R1 is a SACE Emax 2 E2.2N 1250 A three-pole withdrawable air circuit breaker moving part fitted with an Ekip Touch LSI solid-state electronic protection release and four auxiliary change-over contacts.

What protection functions does the Ekip Touch LSI release provide?

The Ekip Touch LSI release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. This model does not include the integrated earth-fault protection provided by LSIG variants.

What is the rated current of the ABB E2.2N 1SDA072305R1?

The circuit breaker has a rated uninterrupted current of 1250 A, with an overload release adjustment range of 500–1250 A.

What is the short-circuit breaking capacity of the E2.2N 1250?

The E2.2N 1250 has an ultimate short-circuit breaking capacity of 66 kA at 400 V AC, 50 Hz, providing robust fault interruption for demanding low-voltage distribution systems.

Is the ABB 1SDA072305R1 a fixed or withdrawable circuit breaker?

This product is a withdrawable moving part (WMP) designed for use with the corresponding ABB SACE Emax 2 fixed chassis to form a complete withdrawable air circuit breaker installation.

Trusted Protection from ABB

ABB SACE Emax 2 air circuit breakers combine high-current switching, configurable electronic protection and flexible withdrawable switchgear integration to provide dependable protection for industrial, commercial and infrastructure power-distribution systems.