Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072275R1 E2.2N 1000 Ekip Touch LSI 3p WMP is a 1000 A three-pole withdrawable SACE Emax 2 air circuit breaker moving part with adjustable Ekip Touch LSI electronic protection, a 690 V AC rated voltage and 66 kA ultimate short-circuit breaking capacity.
£4,677.52
The ABB E2.2N 1000 Ekip Touch LSI 3p WMP, order code 1SDA072275R1, is a high-performance three-pole withdrawable air circuit breaker moving part designed for protection and control within demanding low-voltage electrical distribution systems. Part of the ABB SACE Emax 2 range, it combines the E2.2N frame with a 1000 A rated uninterrupted current and an advanced Ekip Touch LSI electronic trip unit.
The Ekip Touch LSI release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. Adjustable protection settings allow the breaker to be coordinated with upstream and downstream protective devices, while the Ekip Touch platform provides an intuitive interface for configuring and managing protection functions.
With a rated voltage of 690 V AC and rated ultimate short-circuit breaking capacity of 66 kA at 400 V AC, the E2.2N 1000 provides robust fault-interruption performance for industrial, commercial and infrastructure applications. Its withdrawable moving-part configuration supports efficient inspection and servicing, with the compatible Emax 2 fixed part ordered separately.
Air circuit breakers such as the ABB SACE Emax 2 protect low-voltage electrical networks against potentially damaging overload and short-circuit conditions. The E2.2N 1000 combines a 1000 A current rating with 66 kA short-circuit performance, making it suitable for demanding main distribution, feeder and transformer-fed switchboard applications.
The Ekip Touch LSI electronic trip unit provides separate long-time, short-time and instantaneous protection functions, allowing protection characteristics to be coordinated with other devices throughout the electrical network. Its adjustable settings and withdrawable Emax 2 architecture provide a flexible solution for dependable protection, selectivity, operational continuity and maintainability.
| Series | SACE Emax 2 |
|---|---|
| Frame | E2.2N |
| ABB order code | 1SDA072275R1 |
| EAN | 8015644761257 |
| Product group | Emax2 Air Circuit Breaker |
| Product type | Air circuit breaker moving part |
| Configuration | Withdrawable moving part (WMP) |
| Number of poles | 3 |
| Current type | AC |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated voltage | 690 V AC |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz | 66 kA |
| E2.2N ultimate breaking capacity at 440 V AC | 66 kA |
| Rated short-time withstand current (Icw) for 1 s | 66 kA |
| Short-circuit performance level | N |
| Trip unit | Ekip Touch LSI |
| Release technology | Solid-state electronic |
| Protection functions | Long-time (L), short-time (S) and instantaneous (I) |
| Overload release adjustment | 400–1000 A |
| Short-time delayed short-circuit release adjustment | 600–10000 A |
| Instantaneous short-circuit release adjustment | 1500–15000 A |
| Integrated ground-fault protection | No |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Main circuit connection | Via separate chassis / fixed part |
| Complete device with protection unit | Yes |
| Motor drive integrated | No |
| Motor drive optional | Yes |
| DIN rail mounting | No |
| Fixed part | Ordered separately |
| Product net weight | 48 kg |
The ABB 1SDA072275R1 is an E2.2N 1000 Ekip Touch LSI three-pole withdrawable moving part from the SACE Emax 2 air circuit breaker range, designed for protection of demanding low-voltage AC power-distribution systems.
The E2.2N 1000 has a rated uninterrupted current of 1000 A. Its overload protection can be adjusted across a range of 400–1000 A.
The E2.2N 1000 has a rated ultimate short-circuit breaking capacity of 66 kA at 400 V AC, 50 Hz, with the E2.2N performance class also rated at 66 kA at 440 V AC.
The Ekip Touch LSI electronic trip unit provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. This version does not include integrated ground-fault protection.
The 1SDA072275R1 is a three-pole withdrawable moving part (WMP). It is designed for installation with the appropriate ABB SACE Emax 2 fixed part, which is ordered separately.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, robust short-circuit performance and maintainable withdrawable construction, providing dependable circuit protection for demanding industrial, commercial and infrastructure low-voltage power-distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.