Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072272R1 E2.2N 1000 Ekip Dip LSI 3p WMP is a 1000 A three-pole withdrawable SACE Emax 2 air circuit breaker with electronic LSI protection and 66 kA short-circuit breaking capacity for low-voltage AC power distribution systems.
£4,619.06
The ABB E2.2N 1000 Ekip Dip LSI 3p WMP, order code 1SDA072272R1, is a high-performance three-pole air circuit breaker from the ABB SACE Emax 2 range, designed for protection and switching in low-voltage electrical distribution systems. Rated at 1000 A, it combines the E2.2N frame with ABB's solid-state Ekip Dip LSI electronic trip unit for dependable long-time overload, short-time delayed and instantaneous short-circuit protection.
The Ekip Dip LSI release provides three fundamental protection functions for effective coordination within industrial and commercial power networks. Long-time protection safeguards against sustained overloads, short-time delayed protection supports selectivity between upstream and downstream protective devices, and instantaneous protection responds rapidly to severe short-circuit faults.
With a rated uninterrupted current of 1000 A, rated operational voltage of 690 V AC and rated ultimate short-circuit breaking capacity of 66 kA at 400 V AC, the 1SDA072272R1 is suited to demanding power distribution applications. Its withdrawable moving-part construction enables installation with a compatible Emax 2 E2.2 fixed part and facilitates inspection, servicing and replacement within electrical switchboards.
Air circuit breakers such as the ABB SACE Emax 2 provide switching and protection for high-current low-voltage distribution circuits. The E2.2N combines substantial short-circuit interruption capability with electronic protection, helping safeguard cables, busbars, switchgear and connected equipment against damaging overload and short-circuit conditions.
The Ekip Dip LSI release combines long-time overload protection with short-time delayed and instantaneous short-circuit protection. The short-time delay function enables improved coordination between protective devices, helping isolate a fault at the appropriate point in the distribution network while maintaining supply to unaffected circuits where the system has been designed for selectivity.
| Product range | SACE Emax 2 |
|---|---|
| Series | E2.2N |
| Order code / MPN | 1SDA072272R1 |
| Product type | Air circuit breaker |
| Construction | Withdrawable moving part |
| Version | W |
| Number of poles | 3P |
| Rated current (In) | 1000 A |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Current type | AC |
| Trip unit | Ekip Dip LSI |
| Release type | Solid-state electronic |
| Protection functions | L (long-time overload), S (short-time delayed short circuit) and I (instantaneous short circuit) |
| Short-circuit performance level | N |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz | 66 kA |
| Rated service short-circuit breaking capacity (Ics) at 220–440 V AC | 66 kA |
| Overload release adjustment range | 400–1000 A |
| Short-time delayed short-circuit release adjustment range | 600–10000 A |
| Instantaneous short-circuit release adjustment range | 1500–15000 A |
| Integrated earth-fault protection | No |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open/closed |
| Main circuit connection | Separate chassis / fixed part |
| Control element | Push button |
| Motor operator | Optional |
| Integrated motor operator | No |
| Integrated undervoltage release | No |
| DIN rail mounting | No |
| Degree of protection | IP30 |
| Connecting capacity | 600 mm² |
| Power loss | 113 W |
| Mechanical durability | 25,000 operating cycles |
| Electrical durability at Ue ≤ 440 V | 15,000 operating cycles |
| Electrical durability at Ue 500–690 V | 15,000 operating cycles |
| Maximum mechanical operating frequency | 60 cycles per hour |
| Maximum electrical operating frequency | 30 cycles per hour |
| Product net weight | approx. 48 kg |
| Standard | IEC 60947-2 |
| EAN | 8015644761226 |
The ABB 1SDA072272R1 is a 1000 A three-pole air circuit breaker used for switching and protecting low-voltage AC power distribution circuits in industrial, commercial and infrastructure electrical systems.
The Ekip Dip LSI solid-state electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.
The E2.2N 1000 has a rated ultimate short-circuit breaking capacity of 66 kA at 400 V AC, 50 Hz.
The overload release can be adjusted from 400–1000 A, the short-time delayed short-circuit release from 600–10000 A, and the instantaneous short-circuit release from 1500–15000 A.
The 1SDA072272R1 is a withdrawable moving part designed for installation with a compatible ABB SACE Emax 2 E2.2 fixed part.
ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, configurable electronic protection and service-friendly withdrawable construction for demanding industrial, commercial and infrastructure power distribution systems.
We use cookies