ABB 1SDA072254R1 E2.2S 800 Ekip Touch LI 3p WMP is an 800 A three-pole withdrawable SACE Emax 2 air circuit breaker moving part with Ekip Touch LI electronic long-time overload and instantaneous short-circuit protection.
£4,838.31
The ABB E2.2S 800 Ekip Touch LI 3p WMP, order code 1SDA072254R1, is a high-performance three-pole withdrawable air circuit breaker moving part from the ABB SACE Emax 2 range, designed for dependable switching and protection in demanding low-voltage power distribution systems. Rated at 800 A, it combines the E2.2S frame with an advanced Ekip Touch LI electronic trip unit.
The Ekip Touch LI release provides long-time overload and instantaneous short-circuit protection, combining configurable electronic protection with an intuitive touchscreen interface. This configuration is well suited to distribution applications requiring reliable overload protection and rapid interruption of high-level short-circuit faults without short-time or ground-fault protection functions.
The E2.2S performance class delivers a rated ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC, while the breaker is rated for operation at up to 690 V AC. Its withdrawable moving-part construction supports efficient inspection, replacement and maintenance within compatible ABB Emax 2 switchgear.
ABB SACE Emax 2 air circuit breakers combine robust fault-interruption performance with advanced electronic protection for modern low-voltage electrical networks. The E2.2S frame provides an 800 A current rating and high short-circuit breaking capability, making it suitable for industrial plants, commercial infrastructure and critical electrical distribution systems.
The Ekip Touch LI release combines electronic long-time overload protection with instantaneous short-circuit protection and an accessible touchscreen interface. Together with the withdrawable Emax 2 construction, the 1SDA072254R1 provides a practical solution for switchboards requiring strong fault-clearing performance, convenient protection configuration and efficient maintenance.
| Series | SACE Emax 2 |
|---|---|
| Frame | E2.2S |
| ABB order code | 1SDA072254R1 |
| Product type | Air circuit breaker moving part |
| Rated current (In) | 800 A |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Touch LI |
| Protection functions | Long-time and instantaneous |
| Overload release current setting | 320 A |
| Undelayed short-circuit release adjustment | 1200 A |
| Integrated earth-fault protection | No |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) at 400–440 V AC | 85 kA |
| Installation | Withdrawable / draw-out moving part |
| Main-circuit connection | Connection at separate chassis part |
| Auxiliary change-over contacts | 4 |
| Switched-off indicator | Yes |
| Motor drive | Optional |
| Degree of protection | IP30 |
| Power loss | 72 W |
| Mechanical durability | 25,000 cycles |
| Electrical durability at ≤440 V | 15,000 cycles |
| Electrical durability at 500–690 V | 15,000 cycles |
| Product width | 317 mm |
| Product height | 425 mm |
| Product depth | 383 mm |
| EAN | 8015644761042 |
| Standard | IEC 60947-2 |
The ABB 1SDA072254R1 is an 800 A three-pole withdrawable Emax 2 air circuit breaker moving part designed for switching and protecting demanding low-voltage electrical distribution systems.
It is fitted with an ABB Ekip Touch LI electronic trip unit, providing long-time overload and instantaneous short-circuit protection.
The ABB E2.2S 800 has a rated current of 800 A and a rated operational voltage of 690 V AC.
The E2.2S version provides a rated ultimate short-circuit breaking capacity of 85 kA at 400 V AC, with a rated service short-circuit breaking capacity of 85 kA through 440 V AC.
No. This model uses an Ekip Touch LI release providing long-time overload and instantaneous short-circuit protection; integrated ground-fault protection is not included in this configuration.
ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, advanced electronic protection and flexible withdrawable construction for reliable switching and protection in demanding low-voltage power distribution systems.