Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072234R1 SACE Emax 2 E1.2N 1600 A three-pole withdrawable air circuit breaker moving part with Ekip Touch LI electronic overload and instantaneous short-circuit protection.
£4,965.58
The ABB E1.2N 1600 Ekip Touch LI 3p WMP, order code 1SDA072234R1, is a high-performance SACE Emax 2 air circuit breaker moving part designed for protection and switching in low-voltage AC power distribution systems. As part of the ABB Emax 2 E1.2 series, this three-pole breaker combines a rated current of 1600 A with the advanced Ekip Touch LI electronic protection release.
The Ekip Touch LI trip unit provides long-time overload and instantaneous short-circuit protection, with settings and operating information accessible through its touchscreen interface. This protection combination is well suited to distribution applications requiring configurable electronic protection without the additional short-time or earth-fault functions of LSIG releases.
This version is a withdrawable moving part (WMP) for compatible Emax 2 fixed parts. With a 690 V AC rated voltage and an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC, the E1.2N 1600 provides robust protection for demanding industrial, commercial and infrastructure power-distribution installations.
Air circuit breakers such as the ABB SACE Emax 2 protect high-current electrical distribution circuits against damaging overloads and short circuits. The Ekip Touch LI release combines adjustable long-time overload protection with instantaneous short-circuit protection, allowing the breaker to disconnect a circuit when electrical conditions exceed its configured protection thresholds.
The withdrawable E1.2 construction is particularly useful in switchboards where inspection, maintenance and equipment replacement need to be carried out efficiently. The moving part interfaces with the appropriate Emax 2 fixed part, while the electronic Ekip Touch platform provides intuitive touchscreen configuration for protection settings and circuit-breaker operation.
| Series | SACE Emax 2 E1.2 |
|---|---|
| ABB order code | 1SDA072234R1 |
| Product type | Air circuit breaker moving part |
| Version | Withdrawable (WMP) |
| Number of poles | 3 |
| Rated current | 1600 A |
| Rated voltage | 690 V AC |
| Rated ultimate short-circuit breaking capacity Icu at 400 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity Icu at 440 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity Icu at 500 V AC | 50 kA |
| Protection release | Ekip Touch LI |
| Protection functions | Long-time overload (L) and instantaneous short circuit (I) |
| Overload protection setting range | 640–1600 A |
| Instantaneous short-circuit setting range | 1.5–15 × In |
| Auxiliary contacts | 4 change-over contacts |
| Earth-fault protection | No |
| Main-circuit connection | Connection at separate chassis / fixed part |
| Operating control | Push button |
| Motor drive | Optional |
| Protection rating | IP30 |
The ABB 1SDA072234R1 is a SACE Emax 2 E1.2N 1600 A three-pole withdrawable air circuit breaker moving part equipped with an Ekip Touch LI electronic protection release.
The Ekip Touch LI release provides long-time overload protection and instantaneous short-circuit protection, with settings configured through the Ekip Touch interface.
The circuit breaker has a rated current of 1600 A, with an overload protection setting range of 640–1600 A.
The E1.2N 1600 has a rated ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC.
This model is a withdrawable moving part (WMP) and is designed for use with the corresponding ABB SACE Emax 2 fixed part to form a complete withdrawable circuit-breaker installation.
ABB SACE Emax 2 air circuit breakers combine high-current switching, configurable electronic protection and flexible switchgear integration, providing dependable protection for demanding industrial, commercial and infrastructure power-distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.