1SDA072230R1 ABB E1.2C 1600 Ekip G Hi-Touch LSIG 3p WMP Air Circuit Breaker

1SDA072230R1 ABB E1.2C 1600 Ekip G Hi-Touch LSIG 3p WMP Air Circuit Breaker

ABB 1SDA072230R1 E1.2C 1600 Ekip G Hi-Touch LSIG 3p WMP is a 1600 A three-pole withdrawable SACE Emax 2 air circuit breaker moving part with advanced Ekip G Hi-Touch LSIG protection for generator and low-voltage power distribution applications.

SKU: 1SDA072230R1MPN: 1SDA072230R1
Price
List Price £9,409.47 ex VAT
Your Price (ex VAT) Save 25%
£7,057.10 25% OFF
You save £2,352.37 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,057.10
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,057.10

Why Choose the ABB E1.2C 1600 Ekip G Hi-Touch LSIG 3p WMP Air Circuit Breaker?

The ABB E1.2C 1600 Ekip G Hi-Touch LSIG 3p WMP, order code 1SDA072230R1, is a high-performance three-pole withdrawable air circuit breaker moving part from the ABB SACE Emax 2 range, designed for generator protection and demanding low-voltage power distribution applications. Rated at 1600 A, it combines the compact E1.2C frame with the advanced Ekip G Hi-Touch LSIG electronic trip unit for comprehensive protection, measurement and generator-oriented power management.

The Ekip G Hi-Touch release provides advanced protection functions tailored to generator and power-generation applications. Its LSIG functionality includes long-time overload, short-time delayed short-circuit, instantaneous short-circuit and ground-fault protection, helping safeguard generators, conductors, switchgear and connected equipment while supporting selective coordination throughout the electrical network.

This version is a three-pole withdrawable moving part with a 1600 A rated uninterrupted current. The E1.2C performance class provides a rated ultimate short-circuit breaking capacity of 50 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s, making it a robust solution for generator switchboards, industrial power systems and critical electrical infrastructure.

Key Advantages

  • Advanced ABB SACE Emax 2 air circuit breaker for generator and low-voltage distribution applications.
  • 1600 A rated uninterrupted current for high-current power systems.
  • Ekip G Hi-Touch LSIG electronic trip unit for advanced generator protection and supervision.
  • LSIG functionality provides long-time, short-time, instantaneous and ground-fault protection.
  • Three-pole withdrawable construction facilitates switchboard servicing and maintenance.
  • E1.2C performance class provides 50 kA Icu at 440 V AC.
  • 42 kA short-time withstand current for 1 s supports selective protection schemes.
  • Four auxiliary contacts provide circuit-breaker open/closed status signalling.

Key Features

  • ABB SACE Emax 2 E1.2C air circuit breaker platform.
  • 1600 A rated uninterrupted current.
  • Three-pole configuration.
  • Withdrawable moving-part design.
  • Advanced Ekip G Hi-Touch LSIG solid-state electronic protection release.
  • L – long-time overload protection.
  • S – short-time delayed short-circuit protection.
  • I – instantaneous short-circuit protection.
  • G – ground-fault protection.
  • Generator-oriented protection and power-management functionality.
  • 50 kA Icu at 440 V AC.
  • 42 kA Icw for 1 s.
  • Four auxiliary contacts with circuit-breaker open/closed position indication.

Advanced Generator and Power Distribution Protection

ABB SACE Emax 2 air circuit breakers provide reliable switching and fault protection for demanding low-voltage electrical networks. The compact E1.2C frame supports currents up to 1600 A while delivering strong short-circuit performance, helping engineers develop efficient generator and distribution switchboards without compromising protection capability.

The Ekip G Hi-Touch LSIG release extends the breaker into advanced generator protection and power-management applications, combining comprehensive electronic protection with measurement and supervision capabilities. Together with the withdrawable Emax 2 construction, the 1SDA072230R1 provides a flexible solution for critical switchboards where generator protection, operational visibility and convenient maintenance are priorities.

Typical Applications

  • Generator protection and generator switchboards.
  • Power generation and standby power systems.
  • Industrial low-voltage switchboards and distribution panels.
  • Main and sub-main electrical distribution systems.
  • Manufacturing and process plants.
  • Data centres and critical power infrastructure.
  • Utilities and energy infrastructure.
  • OEM switchgear and electrical panel assemblies.

Technical Specifications

Series SACE Emax 2
Frame E1.2C
ABB order code 1SDA072230R1
Product type Air circuit breaker moving part
Application Generator and low-voltage circuit protection
Rated uninterrupted current (Iu) 1600 A
Number of poles 3
Current type AC
Trip unit Ekip G Hi-Touch LSIG
Protection functions Long-time, short-time, instantaneous and ground-fault
Rated operational voltage Up to 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 50 kA
Rated short-time withstand current (Icw), 1 s 42 kA
Installation Withdrawable / draw-out moving part
Auxiliary contacts 4
Circuit-breaker indication Open / closed
Motor operation Optional
Degree of protection IP30
Product net width 278 mm
Product net height 363.5 mm
Product net depth 271 mm
Product net weight approx. 14 kg
EAN 8015644760809

Frequently Asked Questions

What is the ABB 1SDA072230R1 used for?

The ABB 1SDA072230R1 is a 1600 A three-pole withdrawable Emax 2 air circuit breaker moving part designed for generator protection and demanding low-voltage power distribution applications.

What protection unit is fitted to the ABB 1SDA072230R1?

It is fitted with an ABB Ekip G Hi-Touch LSIG electronic trip unit, providing advanced generator-oriented protection together with long-time overload, short-time delayed short-circuit, instantaneous short-circuit and ground-fault protection.

What is the rated current of the E1.2C 1600?

The ABB E1.2C 1600 has a rated uninterrupted current of 1600 A and is suitable for low-voltage systems operating at up to 690 V AC.

What is the breaking capacity of the ABB E1.2C 1600?

The E1.2C version provides a rated ultimate short-circuit breaking capacity of 50 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s.

Is the ABB 1SDA072230R1 a fixed or withdrawable breaker?

The 1SDA072230R1 is the withdrawable moving-part version, designed for installation with the corresponding Emax 2 fixed switchboard section.

Trusted Generator Protection from ABB

ABB SACE Emax 2 air circuit breakers with Ekip G protection releases combine robust short-circuit performance, advanced generator protection and flexible withdrawable construction for reliable operation in power generation and critical low-voltage distribution systems.