1SDA072228R1 ABB E1.2C 1600 Ekip Hi-Touch LSI 3p WMP Air Circuit Breaker 1600 A

1SDA072228R1 ABB E1.2C 1600 Ekip Hi-Touch LSI 3p WMP Air Circuit Breaker 1600 A

ABB 1SDA072228R1 E1.2C 1600 Ekip Hi-Touch LSI 3p WMP is a 1600 A three-pole withdrawable SACE Emax 2 air circuit breaker with advanced electronic LSI protection for low-voltage power distribution systems.

SKU: 1SDA072228R1MPN: 1SDA072228R1
Price
List Price £8,265.93 ex VAT
Your Price (ex VAT) Save 25%
£6,199.45 25% OFF
You save £2,066.48 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £6,199.45
Trade pricing is personalised to your account

Manufacturer Lead Time

£6,199.45

Why Choose the ABB E1.2C 1600 Ekip Hi-Touch LSI 3p WMP Air Circuit Breaker?

The ABB E1.2C 1600 Ekip Hi-Touch LSI 3p WMP, order code 1SDA072228R1, is a high-performance three-pole air circuit breaker from the ABB SACE Emax 2 range, designed for advanced protection and switching in low-voltage electrical distribution systems. Rated at 1600 A, it combines the compact E1.2C frame with ABB's sophisticated Ekip Hi-Touch LSI electronic trip unit for comprehensive overload and short-circuit protection.

The Ekip Hi-Touch platform provides advanced protection, measurement and monitoring capabilities for demanding power distribution applications. Its LSI protection functions provide long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection, supporting selective coordination and dependable fault isolation within complex electrical networks.

With a rated uninterrupted current of 1600 A, rated operational voltage of 690 V AC and rated ultimate short-circuit breaking capacity of 50 kA at 400–440 V AC, the 1SDA072228R1 is suitable for demanding industrial, commercial and infrastructure installations. Its withdrawable moving-part construction allows integration with a compatible E1.2 fixed part and supports efficient inspection, maintenance and replacement within electrical switchboards.

Key Advantages

  • Advanced ABB SACE Emax 2 air circuit breaker for low-voltage power distribution.
  • 1600 A rated uninterrupted current for high-current electrical installations.
  • Three-pole configuration for three-phase power distribution systems.
  • Ekip Hi-Touch LSI electronic trip unit providing advanced overload and short-circuit protection.
  • Rated ultimate short-circuit breaking capacity of 50 kA at 400–440 V AC.
  • Rated operational voltage of 690 V AC.
  • Adjustable overload, short-time delayed and instantaneous protection settings support effective system coordination.
  • Withdrawable moving-part construction supports efficient switchgear servicing and maintenance.

Key Features

  • ABB SACE Emax 2 E1.2C series.
  • 1600 A rated uninterrupted current.
  • Three-pole (3P) configuration.
  • Ekip Hi-Touch LSI solid-state electronic release.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 50 kA Icu at 400–440 V AC.
  • 42 kA Icu at 500–690 V AC.
  • 42 kA short-time withstand current for 1 s.
  • 640–1600 A adjustable overload release range.
  • 960–16000 A adjustable short-time delayed short-circuit release range.
  • 2400–24000 A adjustable instantaneous short-circuit release range.
  • Withdrawable moving-part design for compatible Emax 2 switchgear.
  • Supplied with four change-over auxiliary contacts and circuit breaker open/closed position indication.

Advanced Protection for Low-Voltage Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 provide switching and protection for high-current low-voltage distribution circuits. The Ekip Hi-Touch electronic platform adds sophisticated protection and monitoring capabilities, helping electrical systems respond effectively to overload and short-circuit conditions while supporting improved coordination between protective devices.

The LSI protection package combines long-time overload protection with short-time delayed and instantaneous short-circuit protection. This combination supports selective fault protection within complex distribution networks, helping isolate affected circuits while maintaining continuity of supply to unaffected parts of the installation wherever system coordination permits.

Typical Applications

  • Main low-voltage electrical distribution switchboards.
  • Industrial power distribution systems.
  • Transformer and installation protection.
  • Commercial building electrical infrastructure.
  • Manufacturing and process plant switchgear.
  • Critical power distribution systems.
  • Infrastructure and utility installations.
  • Three-phase distribution networks requiring advanced LSI protection and selective coordination.

Technical Specifications

Product range SACE Emax 2
Series E1.2C
Order code / MPN 1SDA072228R1
Product type Air circuit breaker
Construction Withdrawable moving part
Number of poles 3P
Rated current (In) 1600 A
Rated uninterrupted current (Iu) 1600 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Current type AC
Trip unit Ekip Hi-Touch LSI
Release type Electronic / solid-state
Protection functions L (overload), S (short-time delayed short circuit) and I (instantaneous short circuit)
Short-circuit performance level C
Rated ultimate short-circuit breaking capacity (Icu) at 400–440 V AC 50 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC 42 kA
Rated service short-circuit breaking capacity (Ics) at 400–440 V AC 50 kA
Rated service short-circuit breaking capacity (Ics) at 500–690 V AC 42 kA
Ics as percentage of Icu 100%
Rated short-time withstand current (Icw) 42 kA for 1 s
Overload release adjustment range 640–1600 A
Short-time delayed short-circuit release adjustment range 960–16000 A
Instantaneous short-circuit release adjustment range 2400–24000 A
Auxiliary contacts 4 change-over contacts
Motor operator Optional
Integrated motor operator No
Integrated undervoltage release No
DIN rail mounting No
Power loss 400 W
Mechanical durability 20,000 operating cycles
Electrical durability at Ue ≤ 440 V 3,000 operating cycles
Electrical durability at Ue 500–690 V 6,500 operating cycles
Standard IEC 60947-2
EAN 8015644760786

Frequently Asked Questions

What is the ABB 1SDA072228R1 used for?

The ABB 1SDA072228R1 is a 1600 A three-pole air circuit breaker used for advanced switching and protection of low-voltage electrical distribution circuits, including transformer, installation and industrial power applications.

What protection does the Ekip Hi-Touch LSI trip unit provide?

The Ekip Hi-Touch LSI electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection, together with advanced monitoring and protection capabilities.

What is the breaking capacity of the ABB 1SDA072228R1?

The E1.2C breaker has a rated ultimate short-circuit breaking capacity of 50 kA at 400–440 V AC and 42 kA at 500–690 V AC.

What are the adjustable protection ranges?

The overload release can be adjusted from 640–1600 A, the short-time delayed short-circuit release from 960–16000 A, and the instantaneous short-circuit release from 2400–24000 A.

Is the ABB 1SDA072228R1 a fixed or withdrawable circuit breaker?

The 1SDA072228R1 is the withdrawable moving part of the Emax 2 circuit breaker system and is designed for use with a compatible E1.2 fixed part.

Trusted Protection from ABB

ABB SACE Emax 2 air circuit breakers combine high-performance circuit protection, advanced electronic trip technology and service-friendly construction for demanding low-voltage power distribution applications.