Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072186R1 is an Emax 2 E1.2C 1250 A three-pole withdrawable air circuit breaker moving part with an Ekip Touch LSIG electronic trip unit for long-time, short-time, instantaneous and earth-fault protection.
£3,686.57
The ABB 1SDA072186R1 is an Emax 2 E1.2C air circuit breaker designed for protection, switching and isolation in low-voltage electrical distribution systems. This three-pole withdrawable circuit breaker moving part has a rated uninterrupted current of 1250 A and incorporates an Ekip Touch LSIG solid-state electronic trip unit providing long-time, short-time, instantaneous and earth-fault protection.
As part of the ABB SACE Emax 2 series, the E1.2C platform combines compact construction with dependable short-circuit performance. The E1.2C 1250 provides an ultimate short-circuit breaking capacity of 50 kA at 400–440 V AC and 42 kA at 690 V AC, with a rated service short-circuit breaking capacity equal to 100% of Icu.
The E1.2C 1250 Ekip Touch LSIG 3p WMP is supplied as the moving part of a withdrawable circuit-breaker system for use with a compatible Emax 2 E1.2 fixed part. Its comprehensive LSIG protection, electronic Ekip Touch release and withdrawable construction make it particularly suitable for main incomers, transformer secondary circuits and critical distribution feeders where protection selectivity and maintainability are important.
The ABB Ekip Touch LSIG electronic trip unit combines long-time overload, short-time delayed, instantaneous short-circuit and earth-fault protection. This comprehensive protection architecture enables the E1.2C circuit breaker to safeguard cables, busbars, transformers and downstream electrical equipment while supporting selective coordination across low-voltage distribution networks.
The withdrawable E1.2C platform is particularly useful in switchboards where serviceability and operational flexibility are important. The circuit breaker moving part interfaces with a compatible separate fixed part and can be withdrawn for inspection or maintenance while the permanent switchboard connections remain installed.
| Series | SACE Emax 2 |
|---|---|
| ABB order code | 1SDA072186R1 |
| EAN / GTIN | 8015644760366 |
| Product type | Air circuit breaker |
| Frame | E1.2 |
| Performance level | C |
| Rated uninterrupted current | 1250 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V AC |
| Rated impulse withstand voltage | 12 kV |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Touch LSIG |
| Release technology | Solid-state electronic |
| Protection functions | L, S, I, G |
| Overload protection adjustment range | 500–1250 A |
| Instantaneous short-circuit protection adjustment range | 1875–18,750 A |
| Integrated earth-fault protection | Yes |
| Ultimate short-circuit breaking capacity | 50 kA at 400–440 V AC |
| Service short-circuit breaking capacity | 100% of Icu |
| Rated short-time withstand current | 42 kA for 1 s; 24 kA for 3 s |
| Execution | Withdrawable moving part |
| Version | W |
| Main circuit connection | Through compatible separate fixed part |
| Auxiliary contacts | 4 |
| Circuit-breaker indication | Open / closed position |
| Electrical durability | 8000 cycles at ≤440 V; 6500 cycles at 500–690 V |
| Mechanical durability | 20,000 cycles |
| Power loss | 244 W |
| Product net depth | 271 mm |
| Product net weight | 18 kg |
| Country of origin | Italy |
| Standard | IEC 60947-2 |
The ABB 1SDA072186R1 is an Emax 2 E1.2C three-pole withdrawable air circuit breaker moving part rated at 1250 A and equipped with an Ekip Touch LSIG solid-state electronic trip unit.
The Ekip Touch LSIG release provides long-time (L), short-time (S), instantaneous (I) and earth-fault (G) protection functions for comprehensive low-voltage distribution protection.
The E1.2C 1250 provides an ultimate short-circuit breaking capacity of 50 kA at 400–440 V AC and 42 kA at 500–690 V AC.
The 1SDA072186R1 is a withdrawable moving-part air circuit breaker designed for use with a compatible separate ABB Emax 2 E1.2 fixed part.
Yes. Its Ekip Touch LSIG electronic trip unit includes earth-fault protection in addition to long-time, short-time and instantaneous overcurrent protection.
ABB Emax 2 air circuit breakers are widely specified for industrial, commercial and infrastructure electrical systems where dependable switching, advanced electronic protection, high short-circuit performance and maintainable low-voltage distribution equipment are required.
We use cookies