1SDA072160R1 ABB E1.2N 1000 Ekip G Hi-Touch LSIG 3p WMP Air Circuit Breaker

1SDA072160R1 ABB E1.2N 1000 Ekip G Hi-Touch LSIG 3p WMP Air Circuit Breaker

ABB 1SDA072160R1 E1.2N 1000 Ekip G Hi-Touch LSIG 3p WMP is a 1000 A three-pole withdrawable SACE Emax 2 air circuit breaker moving part with advanced Ekip G Hi-Touch LSIG protection for generator and low-voltage power distribution applications.

SKU: 1SDA072160R1MPN: 1SDA072160R1
Price
List Price £10,713.60 ex VAT
Your Price (ex VAT) Save 25%
£8,035.20 25% OFF
You save £2,678.40 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,035.20
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,035.20

Why Choose the ABB E1.2N 1000 Ekip G Hi-Touch LSIG 3p WMP Air Circuit Breaker?

The ABB E1.2N 1000 Ekip G Hi-Touch LSIG 3p WMP, order code 1SDA072160R1, is a high-performance three-pole withdrawable air circuit breaker moving part from the ABB SACE Emax 2 range, developed for generator protection and demanding low-voltage power distribution applications. Rated at 1000 A, it combines the compact E1.2N frame with the advanced Ekip G Hi-Touch LSIG electronic trip unit for comprehensive protection, measurement and generator-oriented power management.

The Ekip G Hi-Touch release combines advanced electronic protection with functions intended for generator and power-generation applications. Its LSIG protection provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection, helping safeguard generators, conductors, switchgear and connected equipment while supporting coordinated electrical distribution systems.

This version is a three-pole withdrawable moving part with a 1000 A rated uninterrupted current and E1.2N breaking-performance class. With an ultimate short-circuit breaking capacity of 66 kA at 400–415 V AC and 50 kA at 690 V AC, it provides robust protection for generator switchboards, industrial power systems and critical electrical infrastructure.

Key Advantages

  • Advanced ABB SACE Emax 2 air circuit breaker for generator and low-voltage distribution applications.
  • 1000 A rated uninterrupted current for substantial electrical loads.
  • Ekip G Hi-Touch LSIG electronic trip unit designed for advanced generator protection and monitoring.
  • LSIG functions provide long-time, short-time, instantaneous and ground-fault protection.
  • Three-pole withdrawable construction supports efficient switchboard servicing and maintenance.
  • E1.2N performance class provides 66 kA ultimate short-circuit breaking capacity at 400–415 V AC.
  • Provides 50 kA ultimate short-circuit breaking capacity at 690 V AC.
  • Supplied with four auxiliary contacts and circuit-breaker open/closed position indication.

Key Features

  • ABB SACE Emax 2 E1.2N air circuit breaker platform.
  • 1000 A rated uninterrupted current.
  • Three-pole configuration.
  • Withdrawable moving-part design.
  • Advanced Ekip G Hi-Touch LSIG solid-state electronic protection release.
  • L – long-time overload protection.
  • S – short-time short-circuit protection.
  • I – instantaneous short-circuit protection.
  • G – ground-fault protection.
  • 66 kA Icu at 400–415 V AC.
  • 50 kA Icu at 690 V AC.
  • Four auxiliary contacts for circuit-breaker status signalling.

Advanced Generator and Power Distribution Protection

ABB SACE Emax 2 air circuit breakers provide reliable switching and protection for demanding low-voltage electrical networks. The E1.2N frame combines compact dimensions with high short-circuit performance, making it suitable for generator switchboards, industrial distribution systems and installations where continuity and dependable fault protection are essential.

The Ekip G Hi-Touch LSIG release is specifically suited to applications requiring advanced generator protection, measurement and supervision. Combined with the withdrawable Emax 2 construction, it provides a flexible solution for critical switchboards where protection performance, system visibility and straightforward maintenance are important.

Typical Applications

  • Generator protection and generator switchboards.
  • Industrial low-voltage switchboards and distribution panels.
  • Power generation and standby power systems.
  • Main and sub-main electrical distribution systems.
  • Manufacturing and process plants.
  • Data centres and critical power infrastructure.
  • OEM switchgear and electrical panel assemblies.

Technical Specifications

Series SACE Emax 2
Frame E1.2N
ABB order code 1SDA072160R1
Product type Air circuit breaker moving part
Application Generator and low-voltage circuit protection
Rated uninterrupted current (Iu) 1000 A
Number of poles 3
Current type AC
Trip unit Ekip G Hi-Touch LSIG
Protection functions Long-time, short-time, instantaneous and ground-fault
Rated operational voltage 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 50 kA
Rated short-time withstand current (Icw), 1 s 50 kA
Overload release setting range 400–1000 A
Short-time delayed short-circuit setting range 600–10000 A
Installation Withdrawable / draw-out moving part
Auxiliary contacts 4
Product net weight approx. 18 kg
EAN 8015644760106

Frequently Asked Questions

What is the ABB 1SDA072160R1 used for?

The ABB 1SDA072160R1 is a 1000 A three-pole withdrawable Emax 2 air circuit breaker moving part designed for generator protection and demanding low-voltage power distribution applications.

What protection unit is fitted to this circuit breaker?

It is fitted with an ABB Ekip G Hi-Touch LSIG electronic trip unit, providing advanced generator-oriented protection together with long-time, short-time, instantaneous and ground-fault protection functions.

What is the rated current of the E1.2N 1000?

This version has a rated uninterrupted current of 1000 A.

What is the breaking capacity of this Emax 2 circuit breaker?

The E1.2N version provides a rated ultimate short-circuit breaking capacity of 66 kA at 400–415 V AC and 50 kA at 690 V AC.

Is the ABB 1SDA072160R1 a fixed or withdrawable breaker?

The 1SDA072160R1 is the withdrawable moving-part version, designed for use with the corresponding Emax 2 fixed switchboard section.

Trusted Generator Protection from ABB

ABB SACE Emax 2 air circuit breakers with Ekip G protection releases combine high breaking performance, advanced generator protection and flexible integration for reliable operation in power generation and critical low-voltage distribution systems.