Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072155R1 is an Emax 2 E1.2N 1000 A three-pole withdrawable air circuit breaker moving part with an Ekip Touch LSI electronic trip unit for long-time, short-time and instantaneous overcurrent protection.
£4,574.35
The ABB 1SDA072155R1 is an Emax 2 E1.2N air circuit breaker designed for protection, switching and isolation in demanding low-voltage electrical distribution systems. This three-pole withdrawable circuit breaker moving part has a rated uninterrupted current of 1000 A and incorporates an Ekip Touch LSI solid-state electronic trip unit providing long-time, short-time and instantaneous overcurrent protection.
As part of the ABB Emax 2 series, the E1.2N platform combines compact construction with high short-circuit performance. The N performance level provides an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 690 V AC, together with a rated short-time withstand current of 50 kA for 1 s.
The E1.2N 1000 Ekip Touch LSI 3p WMP is supplied as the moving part of a withdrawable circuit-breaker system and connects through a compatible separate fixed chassis. Its Ekip Touch interface, adjustable LSI protection and withdrawable construction make it particularly suitable for main incomers, transformer secondary circuits and critical distribution feeders where protection selectivity and maintainability are important.
The ABB Ekip Touch LSI electronic trip unit provides long-time overload, short-time delayed and instantaneous short-circuit protection. This combination enables the E1.2N circuit breaker to protect cables, busbars, transformers and downstream electrical equipment while supporting selective coordination across low-voltage distribution networks.
The withdrawable E1.2N platform is particularly useful in switchboards where serviceability and operational flexibility are important. The circuit breaker moving part connects to the main circuit through a compatible separate chassis and can be withdrawn for inspection or maintenance while the permanent switchboard connections remain installed.
| Series | Emax 2 |
|---|---|
| ABB order code | 1SDA072155R1 |
| EAN / GTIN | 8015644760052 |
| Product type | Air circuit breaker |
| Frame | E1.2 |
| Performance level | N |
| Rated uninterrupted current | 1000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V AC |
| Rated impulse withstand voltage | 12 kV |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Touch LSI |
| Release technology | Solid-state electronic |
| Protection functions | L, S, I |
| Overload protection adjustment range | 400–1000 A |
| Instantaneous short-circuit protection adjustment range | 1500–15,000 A |
| Integrated earth-fault protection | No |
| Ultimate short-circuit breaking capacity | 66 kA at 400–440 V AC |
| Service short-circuit breaking capacity | 100% of Icu |
| Rated short-time withstand current | 50 kA for 1 s; 30 kA for 3 s |
| Execution | Withdrawable moving part |
| Main circuit connection | Connection at separate chassis part |
| Auxiliary contacts | 4 change-over contacts |
| Switched-off indicator | Yes |
| Control element | Push button |
| Motor drive | Optional |
| Degree of protection | IP30 |
| Electrical durability | 8000 operating cycles at ≤440 V; 8000 operating cycles at 500–690 V |
| Mechanical durability | 20,000 operating cycles |
| Power loss | 156 W |
| Product net width | 278 mm |
| Product net height | 363.5 mm |
| Product net depth | 271 mm |
| Product net weight | 18 kg |
| Standard | IEC 60947-2 |
The ABB 1SDA072155R1 is an Emax 2 E1.2N three-pole withdrawable air circuit breaker moving part rated at 1000 A and equipped with an Ekip Touch LSI solid-state electronic trip unit.
The Ekip Touch LSI release provides long-time (L), short-time (S) and instantaneous (I) overcurrent protection functions.
The E1.2N 1000 provides an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC.
The 1SDA072155R1 is a withdrawable moving-part air circuit breaker with its main circuit connection made through a compatible separate fixed chassis part.
No. This model uses an Ekip Touch LSI trip unit providing long-time, short-time and instantaneous protection; integrated earth-fault protection is not included in this LSI configuration.
ABB Emax 2 air circuit breakers are widely specified for industrial, commercial and infrastructure electrical systems where dependable switching, advanced electronic protection, high short-circuit performance and maintainable low-voltage distribution equipment are required.
We use cookies