ABB 1SDA072141R1 E1.2C 1000 Ekip Dip LI three-pole moving part for a withdrawable SACE Emax 2 air circuit breaker, rated at 1000 A and 690 V AC with electronic LI protection and 50 kA ultimate short-circuit breaking capacity at 400–415 V AC.
£2,558.06
The ABB E1.2C 1000 Ekip Dip LI 3p WMP, order code 1SDA072141R1, is the three-pole moving part of a withdrawable SACE Emax 2 air circuit breaker, designed for reliable switching and protection in low-voltage power distribution systems. Rated at 1000 A, it combines the compact E1.2C breaker platform with ABB's Ekip Dip electronic protection technology.
The breaker is equipped with an Ekip Dip LI solid-state electronic trip unit, providing long-time overload (L) and instantaneous short-circuit (I) protection. The long-time protection setting covers 400–1000 A, while the instantaneous protection setting extends from 1500–15000 A, allowing the protection response to be matched to the characteristics of the distribution circuit.
As a WMP moving part, the 1SDA072141R1 is designed for use with the corresponding ABB Emax 2 fixed part or cradle, which is ordered separately. The E1.2C platform provides a rated ultimate short-circuit breaking capacity of 50 kA at 400–415 V AC and 42 kA at 690 V AC, providing robust fault interruption for industrial and commercial distribution systems.
Withdrawable air circuit breakers allow the active breaker assembly to be separated from its fixed chassis, helping simplify inspection, servicing and replacement while permanent switchboard connections remain installed. The ABB Emax 2 E1.2 platform combines this service-friendly arrangement with compact construction and high short-circuit performance for modern low-voltage distribution systems.
The Ekip Dip LI release protects the circuit against sustained overloads and severe instantaneous short-circuit faults. Combined with the E1.2C frame's 50 kA breaking capacity at 400–415 V AC and operation at up to 690 V AC, the 1SDA072141R1 provides dependable protection for appropriately coordinated industrial and commercial electrical networks.
| Series | SACE Emax 2 |
|---|---|
| ABB order code | 1SDA072141R1 |
| Product type | Air circuit breaker moving part |
| Frame | E1.2 |
| Performance level | C |
| Rated current (In) | 1000 A |
| Rated uninterrupted current (Iu) | 1000 A |
| Current type | AC |
| Number of poles | 3 |
| Version | Withdrawable moving part (WMP) |
| Trip unit | Ekip Dip LI |
| Release technology | Solid-state electronic |
| Protection functions | Long-time overload (L) and instantaneous short-circuit (I) |
| Long-time protection adjustment range | 400–1000 A |
| Instantaneous protection adjustment range | 1500–15000 A |
| Integrated ground-fault protection | No |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 42 kA |
| Rated service short-circuit breaking capacity (Ics) at 400–415 V AC | 50 kA |
| Auxiliary contacts | 4 change-over contacts |
| Open/closed indication | Yes |
| Control element | Push button |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| Main-circuit connection | Connection at separate chassis part |
| Protection rating | IP30 |
| Power loss | 156 W |
| Electrical endurance | 8000 cycles at up to 690 V |
| Mechanical endurance | 20000 cycles |
| Net weight | 18 kg |
| Package EAN | 8015644759919 |
| Country of origin | Italy |
| Reference standard | IEC 60947-2 |
The ABB 1SDA072141R1 is the 1000 A three-pole moving part of a SACE Emax 2 E1.2C withdrawable air circuit breaker, equipped with an Ekip Dip LI solid-state electronic trip unit.
The Ekip Dip LI trip unit provides long-time overload (L) and instantaneous short-circuit (I) protection, with a long-time adjustment range of 400–1000 A and instantaneous adjustment from 1500–15000 A.
The E1.2C 1000 provides a rated ultimate short-circuit breaking capacity of 50 kA at 400–415 V AC and 42 kA at 690 V AC.
The 1SDA072141R1 is the moving part of a withdrawable air circuit breaker. It is designed for use with the corresponding ABB Emax 2 fixed part or cradle, which is ordered separately.
No. The Ekip Dip LI release provides long-time overload and instantaneous short-circuit protection. Applications requiring integrated ground-fault protection should use an appropriate LSIG protection configuration.
ABB SACE Emax 2 withdrawable air circuit breakers combine electronic circuit protection, robust short-circuit performance and service-friendly construction for dependable operation in modern low-voltage power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.