Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072135R1 E1.2B 1000 Ekip Touch LSI three-pole withdrawable air circuit breaker moving part with a 1000 A rated current, 42 kA breaking capacity at 440 V AC and touchscreen-configurable long-time, short-time and instantaneous protection.
£2,798.79
The ABB E1.2B 1000 Ekip Touch LSI 3p WMP, order code 1SDA072135R1, is a compact air circuit breaker (ACB) moving part from the ABB SACE Emax 2 series, designed for switching and protection in low-voltage power distribution systems. With a rated uninterrupted current of 1000 A, three-pole construction and ABB's Ekip Touch electronic trip technology, it provides dependable protection for industrial, commercial and infrastructure electrical installations.
The Ekip Touch LSI electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. Its touchscreen interface supports intuitive configuration and access to protection information, while the short-time function provides additional flexibility for selective coordination between upstream and downstream protective devices.
The 1SDA072135R1 is the withdrawable moving part (WMP) of the Emax 2 E1.2 circuit breaker system and is designed for use with the corresponding fixed part. The E1.2B performance level provides a rated ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s, combining compact construction with dependable fault protection and convenient maintainability.
Air circuit breakers such as the ABB SACE Emax 2 E1.2B provide switching, isolation and protection for low-voltage electrical distribution circuits. The compact E1.2 architecture combines substantial fault-clearing capability with a withdrawable construction, allowing the breaker moving part to be disconnected from its corresponding fixed part for inspection, servicing or replacement.
The Ekip Touch LSI electronic trip unit combines adjustable long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. The short-time function provides additional flexibility for selective coordination, while the touchscreen interface simplifies access to protection settings and operating information for modern power distribution applications.
| Series | SACE Emax 2 |
|---|---|
| Product group | Emax2 Air Circuit Breaker |
| Order code / MPN | 1SDA072135R1 |
| Product type | Air circuit breaker moving part |
| Frame | E1.2 |
| Performance level | B |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 42 kA |
| Rated short-time withstand current (Icw) | 42 kA for 1 s |
| Number of poles | 3 |
| Trip unit | Ekip Touch LSI |
| Release type | Electronic trip unit |
| Protection functions | LSI (long-time, short-time and instantaneous) |
| Long-time overload adjustment | 0.4–1 × In |
| Long-time overload adjustment range | 400–1000 A |
| Long-time overload protection | Yes |
| Short-time delayed short-circuit protection | Yes |
| Instantaneous short-circuit protection | Yes |
| Integrated earth-fault protection | No |
| Configuration interface | Touchscreen |
| Installation | Withdrawable |
| Component type | Moving part (WMP) |
| Applicable standard | IEC 60947-2 |
The ABB 1SDA072135R1 is the withdrawable moving part of an Emax 2 E1.2B air circuit breaker, designed for switching and protecting three-phase low-voltage power distribution circuits.
The circuit breaker has a rated uninterrupted current of 1000 A, with long-time overload protection adjustable from 400–1000 A.
The Ekip Touch LSI electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection, with settings accessible through its touchscreen interface.
The E1.2B 1000 has a rated ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s.
The 1SDA072135R1 is a withdrawable moving part (WMP) designed for installation with the corresponding ABB Emax 2 fixed part.
ABB SACE Emax 2 air circuit breakers provide reliable switching and electronic protection for modern low-voltage power distribution systems, combining compact construction, flexible installation and advanced protection technology.