1SDA072118R1 ABB E1.2N 800 Ekip Hi-Touch LSI 3p WMP Air Circuit Breaker Moving Part

1SDA072118R1 ABB E1.2N 800 Ekip Hi-Touch LSI 3p WMP Air Circuit Breaker Moving Part

ABB 1SDA072118R1 E1.2N 800 Ekip Hi-Touch LSI three-pole moving part for a withdrawable SACE Emax 2 air circuit breaker, rated at 800 A and 690 V AC with advanced LSI electronic protection and 66 kA breaking capacity.

SKU: 1SDA072118R1MPN: 1SDA072118R1
Price
List Price £9,449.65 ex VAT
Your Price (ex VAT) Save 25%
£7,087.24 25% OFF
You save £2,362.41 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,087.24
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,087.24

Why Choose the ABB E1.2N 800 Ekip Hi-Touch LSI 3p WMP Air Circuit Breaker Moving Part?

The ABB E1.2N 800 Ekip Hi-Touch LSI 3p WMP, order code 1SDA072118R1, is the three-pole moving part of a withdrawable SACE Emax 2 air circuit breaker, designed for advanced protection and management of low-voltage power distribution systems. Rated at 800 A, this E1.2N configuration combines ABB's compact withdrawable breaker architecture with the advanced Ekip Hi-Touch electronic trip unit.

The Ekip Hi-Touch LSI release provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. The Hi-Touch platform extends conventional circuit protection with advanced measurement, monitoring and power-management capabilities, while its touchscreen interface provides intuitive access to protection settings and electrical-system information.

As a WMP moving part, the 1SDA072118R1 is intended for installation with the corresponding ABB Emax 2 fixed chassis. The E1.2N platform is rated at 690 V AC and provides a short-circuit breaking capacity of up to 66 kA, making this configuration suitable for demanding industrial, commercial and infrastructure distribution systems.

Key Advantages

  • 800 A three-pole Emax 2 moving part for withdrawable circuit breaker installations.
  • Ekip Hi-Touch LSI electronic trip unit provides advanced protection and power-system management.
  • Long-time, short-time and instantaneous protection supports selective coordination.
  • 66 kA short-circuit breaking capacity for demanding low-voltage distribution systems.
  • 690 V AC rated voltage supports a broad range of industrial applications.
  • Large touchscreen interface provides intuitive access to settings and measurements.
  • Advanced measurement and monitoring capabilities support energy-management strategies.
  • Withdrawable construction facilitates inspection, maintenance and replacement.
  • Designed for integration into automation and energy-management systems.

Key Features

  • ABB SACE Emax 2 E1.2N series.
  • 800 A current rating.
  • Three-pole configuration.
  • Withdrawable moving-part construction.
  • Ekip Hi-Touch LSI electronic protection release.
  • Long-time overload (L) protection.
  • Short-time short-circuit (S) protection.
  • Instantaneous short-circuit (I) protection.
  • 320–800 A long-time protection adjustment range.
  • 1200–12000 A instantaneous protection adjustment range.
  • 690 V AC rated voltage.
  • 66 kA breaking capacity.
  • Advanced touchscreen-based configuration and monitoring.
  • Compatible with Emax 2 communication and automation architecture.
  • Designed for use with the corresponding Emax 2 withdrawable fixed part.

Advanced Hi-Touch Protection for Power Distribution

The ABB Ekip Hi-Touch platform extends the role of an air circuit breaker beyond basic fault interruption by combining electronic protection with advanced measurement, monitoring and power-management functions. Its touchscreen interface provides direct access to protection parameters and electrical information, supporting efficient commissioning and operation of sophisticated distribution systems.

Combined with the E1.2N frame's 800 A rating and 66 kA breaking capability, the 1SDA072118R1 provides a high-performance protection platform for installations requiring selective LSI protection and advanced system visibility. Withdrawable construction further supports maintenance by allowing the moving breaker assembly to be removed from its corresponding fixed chassis.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Commercial and infrastructure electrical distribution.
  • Manufacturing and process plant switchboards.
  • Transformer secondary distribution systems.
  • Incoming and high-current feeder protection.
  • Data centres and critical power installations.
  • Withdrawable switchgear requiring advanced electronic protection.
  • Automation and energy-management applications.

Technical Specifications

Series SACE Emax 2
ABB order code 1SDA072118R1
Product type Air circuit breaker moving part
Frame E1.2
Performance level N
Rated current 800 A
Number of poles 3
Construction Moving part for withdrawable circuit breaker
Trip unit Ekip Hi-Touch LSI
Release type Electronic
Protection functions Long-time (L), short-time (S) and instantaneous (I)
Long-time protection adjustment range 320–800 A
Instantaneous short-circuit adjustment range 1200–12000 A
Rated voltage 690 V AC
Breaking capacity 66 kA
User interface Touchscreen
Communication capability Expandable through Emax 2 communication modules
Automation integration Supported
Energy-management integration Supported
Dimensions 363.5 × 278 × 330 mm
Net weight 20 kg
EAN / GTIN 8015644759681
Country of origin Italy
Reference standard IEC

Frequently Asked Questions

What is the ABB 1SDA072118R1?

The ABB 1SDA072118R1 is the 800 A three-pole moving part of a SACE Emax 2 E1.2N withdrawable air circuit breaker, equipped with an Ekip Hi-Touch LSI electronic trip unit.

What protection does the Ekip Hi-Touch LSI trip unit provide?

The Ekip Hi-Touch LSI release provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection, together with advanced measurement and power-management capabilities.

What is the current and breaking capacity of the ABB E1.2N 800?

The breaker is rated at 800 A and provides a short-circuit breaking capacity of up to 66 kA.

Is the ABB 1SDA072118R1 fixed or withdrawable?

The 1SDA072118R1 is the moving part of a withdrawable air circuit breaker and is designed for use with the corresponding ABB Emax 2 fixed chassis.

What is the difference between Ekip Hi-Touch LSI and LSIG?

The Ekip Hi-Touch LSI version provides long-time, short-time and instantaneous overcurrent protection. An LSIG version additionally incorporates a dedicated ground-fault protection function.

Advanced Protection for Modern Power Systems

ABB SACE Emax 2 circuit breakers with Ekip Hi-Touch protection combine sophisticated electronic protection, measurement, system integration and service-friendly withdrawable construction for modern low-voltage power distribution.