1SDA072102R1 ABB E1.2C 800 Ekip Dip LSI 3p WMP Air Circuit Breaker Moving Part

1SDA072102R1 ABB E1.2C 800 Ekip Dip LSI 3p WMP Air Circuit Breaker Moving Part

ABB 1SDA072102R1 E1.2C 800 Ekip Dip LSI three-pole moving part for a withdrawable SACE Emax 2 air circuit breaker, rated at 800 A and 690 V AC with electronic LSI protection and 50 kA short-circuit breaking capacity.

SKU: 1SDA072102R1MPN: 1SDA072102R1
Price
List Price £3,591.27 ex VAT
Your Price (ex VAT) Save 25%
£2,693.45 25% OFF
You save £897.82 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £2,693.45
Trade pricing is personalised to your account

Manufacturer Lead Time

£2,693.45

Why Choose the ABB E1.2C 800 Ekip Dip LSI 3p WMP Air Circuit Breaker Moving Part?

The ABB E1.2C 800 Ekip Dip LSI 3p WMP, order code 1SDA072102R1, is the three-pole moving part of a withdrawable SACE Emax 2 air circuit breaker, engineered for protection and switching in demanding low-voltage power distribution systems. Rated at 800 A, this E1.2C assembly combines ABB's compact withdrawable Emax 2 architecture with an Ekip Dip solid-state electronic protection release.

The breaker is equipped with an Ekip Dip LSI electronic trip unit, providing long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. The addition of adjustable short-time protection makes the LSI configuration particularly useful in distribution systems where selective coordination between upstream and downstream protective devices is required.

As a WMP moving part, the 1SDA072102R1 is designed for use with the corresponding Emax 2 fixed part or cradle. The E1.2C performance level provides a rated ultimate short-circuit breaking capacity of 50 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s, providing dependable protection for industrial, commercial and infrastructure switchboards.

Key Advantages

  • 800 A three-pole Emax 2 moving part for withdrawable air circuit breaker installations.
  • Ekip Dip LSI electronic trip unit provides three-stage overcurrent protection.
  • Long-time, short-time and instantaneous functions support selective protection coordination.
  • 50 kA ultimate short-circuit breaking capacity at 440 V AC.
  • 42 kA short-time withstand current for 1 s supports demanding distribution applications.
  • Withdrawable architecture facilitates breaker inspection, maintenance and replacement.
  • Supplied with four auxiliary contacts for status and control integration.
  • Part of ABB's compact and versatile SACE Emax 2 E1.2 platform.

Key Features

  • ABB SACE Emax 2 E1.2C series.
  • 800 A rated current.
  • Three-pole configuration.
  • Withdrawable moving-part construction.
  • Ekip Dip LSI solid-state electronic release.
  • Long-time overload (L) protection.
  • Short-time short-circuit (S) protection.
  • Instantaneous short-circuit (I) protection.
  • 690 V AC rated operational voltage.
  • 50 kA breaking capacity.
  • 42 kA short-time withstand current for 1 s.
  • Four auxiliary contacts fitted.
  • Circuit-breaker open/closed position indication.
  • Designed for use with the corresponding Emax 2 fixed chassis.

Selective LSI Protection for Withdrawable Power Distribution

Withdrawable air circuit breakers allow the active breaker assembly to be separated from its fixed chassis, simplifying inspection, maintenance and replacement while permanent switchboard connections remain installed. The ABB Emax 2 E1.2 platform combines this service-friendly architecture with compact construction and strong short-circuit performance for modern low-voltage distribution systems.

The Ekip Dip LSI release protects against sustained overloads, delayed short-circuit conditions and severe instantaneous faults. Its combination of L, S and I protection functions supports coordinated tripping within multi-level distribution networks, while the E1.2C frame's 50 kA breaking capacity and 42 kA short-time withstand capability provide robust performance under high fault-current conditions.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Commercial building electrical distribution.
  • Manufacturing and process plant switchboards.
  • Transformer secondary distribution systems.
  • Incoming and feeder circuit protection.
  • Withdrawable switchgear requiring convenient breaker servicing.
  • Distribution networks requiring adjustable LSI overcurrent protection.
  • Systems requiring coordinated short-time and instantaneous fault protection.

Technical Specifications

Series SACE Emax 2
ABB order code 1SDA072102R1
EAN 8015644759520
Product type Air circuit breaker moving part
Frame E1.2
Performance level C
Rated current 800 A
Rated uninterrupted current (Iu) 800 A
Number of poles 3
Construction Moving part for withdrawable circuit breaker
Trip unit Ekip Dip LSI
Release technology Solid-state electronic
Protection functions Long-time (L), short-time (S) and instantaneous (I)
Long-time protection adjustment range 320–800 A
Instantaneous protection adjustment range 1200–12000 A
Rated operational voltage 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 50 kA
Rated short-time withstand current (Icw), 1 s 42 kA
Auxiliary contacts 4
Position indication Circuit breaker open/closed
Length 363.5 mm
Width 278 mm
Depth 271 mm
Net weight 20 kg
Country of origin Italy
Reference standard IEC

Frequently Asked Questions

What is the ABB 1SDA072102R1?

The ABB 1SDA072102R1 is the 800 A three-pole moving part of a SACE Emax 2 E1.2C withdrawable air circuit breaker, equipped with an Ekip Dip LSI electronic trip unit.

What protection does the Ekip Dip LSI trip unit provide?

The Ekip Dip LSI solid-state release provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection.

What is the breaking capacity of the ABB E1.2C 800?

The E1.2C 800 has a rated ultimate short-circuit breaking capacity of 50 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s.

Is the ABB 1SDA072102R1 fixed or withdrawable?

The 1SDA072102R1 is the moving part of a withdrawable air circuit breaker and is intended for use with the corresponding ABB Emax 2 fixed part or cradle.

What accessories are fitted to the ABB 1SDA072102R1?

The moving part is supplied with four auxiliary contacts and circuit-breaker open/closed position indication for integration into switchboard control and monitoring systems.

Dependable Protection with Emax 2 Flexibility

ABB SACE Emax 2 withdrawable air circuit breakers combine configurable electronic protection, robust short-circuit performance and service-friendly construction for dependable operation in modern low-voltage power distribution systems.