Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072093R1 E1.2B 800 Ekip Dip LSIG three-pole withdrawable air circuit breaker moving part with an 800 A rated current, 42 kA breaking capacity and electronic long-time, short-time, instantaneous and earth-fault protection.
£3,069.63
The ABB E1.2B 800 Ekip Dip LSIG 3p WMP, order code 1SDA072093R1, is a compact air circuit breaker (ACB) moving part from the ABB SACE Emax 2 series, designed for switching and protection in low-voltage power distribution systems. With a rated current of 800 A, three-pole construction and ABB's Ekip Dip LSIG electronic trip technology, it provides comprehensive circuit protection for industrial, commercial and infrastructure electrical installations.
The Ekip Dip LSIG electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. Protection thresholds are configured using DIP switches, providing a straightforward interface while supporting the principal protection functions required for selective and dependable low-voltage power distribution.
The 1SDA072093R1 is a withdrawable moving part (WMP) designed for use with the corresponding Emax 2 E1.2 fixed part. The E1.2B performance level provides a rated ultimate short-circuit breaking capacity of 42 kA across 380–690 V AC, combining compact construction with comprehensive LSIG protection and convenient maintainability.
Air circuit breakers such as the ABB SACE Emax 2 E1.2B provide switching, isolation and protection for low-voltage electrical distribution circuits. The compact E1.2 architecture combines dependable short-circuit performance with a withdrawable design, allowing the breaker moving part to be disconnected from its corresponding fixed part for inspection, maintenance or replacement.
The Ekip Dip LSIG electronic trip unit combines adjustable long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection with integrated earth-fault protection. This comprehensive protection package supports selective distribution system design while protecting electrical circuits against overloads, severe short circuits and earth-fault conditions.
| Series | SACE Emax 2 |
|---|---|
| Product group | Emax2 Air Circuit Breaker |
| Order code / MPN | 1SDA072093R1 |
| Product type | Air circuit breaker moving part |
| Frame | E1.2 |
| Performance level | B |
| Rated current (In) | 800 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50 / 60 Hz |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 / 415 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 / 525 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 42 kA |
| Number of poles | 3 |
| Trip unit | Ekip Dip LSIG |
| Release type | Electronic trip unit |
| Protection functions | LSIG (long-time, short-time, instantaneous and earth-fault) |
| Long-time overload protection adjustment | 320–800 A (0.4–1 × In) |
| Short-time selective protection adjustment | 0.6–10 × In |
| Instantaneous protection adjustment | 1200–12000 A (1.5–15 × In) |
| Earth-fault protection adjustment | 0.1–1 × In |
| Integrated earth-fault protection | Yes |
| Configuration method | DIP switches |
| Current type | AC |
| Installation | Withdrawable |
| Component type | Moving part (WMP) |
| Applicable standard | IEC 60947-2 |
The ABB 1SDA072093R1 is the withdrawable moving part of an Emax 2 E1.2B air circuit breaker, designed for switching and protecting three-phase low-voltage power distribution circuits.
The circuit breaker has a rated current of 800 A, with long-time overload protection adjustable from 320–800 A.
The Ekip Dip LSIG electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection.
The E1.2B 800 provides a rated ultimate short-circuit breaking capacity of 42 kA across 380–690 V AC.
The 1SDA072093R1 is a withdrawable moving part (WMP) designed for installation with the corresponding ABB Emax 2 fixed part.
ABB SACE Emax 2 air circuit breakers provide reliable switching and electronic protection for modern low-voltage power distribution systems, combining compact construction, flexible installation and comprehensive circuit protection technology.