Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072075R1 E1.2N 630 Ekip Touch LSI three-pole moving part for a withdrawable SACE Emax 2 air circuit breaker, rated at 630 A with electronic LSI protection and 66 kA ultimate short-circuit breaking capacity at 400 V AC.
£4,273.40
The ABB E1.2N 630 Ekip Touch LSI 3p WMP, order code 1SDA072075R1, is the three-pole moving part of a withdrawable SACE Emax 2 air circuit breaker, designed for transformer, generator and installation protection in demanding low-voltage power distribution systems. Rated at 630 A, this E1.2N assembly combines ABB's compact withdrawable Emax 2 architecture with advanced electronic protection.
The breaker incorporates an Ekip Touch LSI electronic trip unit, providing long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. The Ekip Touch platform provides configurable electronic protection for effective coordination with other protective devices, helping maintain reliable and selective operation throughout modern electrical distribution networks.
As a WMP moving part, the 1SDA072075R1 is intended for installation with the corresponding ABB Emax 2 fixed part or cradle. The E1.2N performance level provides a rated ultimate short-circuit breaking capacity of 66 kA at 400 V AC and a rated short-time withstand current of 50 kA for 1 s, providing robust fault-handling capability for industrial and commercial switchboards.
Withdrawable air circuit breakers allow the active breaker assembly to be removed from its fixed chassis, supporting inspection, maintenance and replacement while the switchboard's fixed connections remain installed. The ABB Emax 2 E1.2 platform combines this service-friendly architecture with compact construction and robust electrical performance for modern low-voltage distribution systems.
The Ekip Touch LSI electronic release protects against sustained overloads, delayed short-circuit conditions and severe instantaneous faults. Its configurable protection functions help engineers coordinate the breaker with upstream and downstream devices, while the E1.2N frame provides the breaking and short-time withstand capability required for dependable and selective power distribution.
| Series | SACE Emax 2 |
|---|---|
| ABB order code | 1SDA072075R1 |
| Product type | Air circuit breaker moving part |
| Frame | E1.2 |
| Performance level | N |
| Rated uninterrupted current (Iu) | 630 A |
| Number of poles | 3 |
| Construction | Moving part for withdrawable circuit breaker |
| Trip unit | Ekip Touch LSI |
| Release type | Electronic / solid-state |
| Protection functions | Long-time (L), short-time (S) and instantaneous (I) |
| Integrated earth-fault protection | No |
| Rated voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 66 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw), 1 s | 50 kA |
| Overload release current setting | from 252 A |
| Short-time delayed short-circuit setting | from 378 A |
| Instantaneous short-circuit setting | from 945 A |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open/closed |
| Control element | Push button |
| Motor drive | Optional |
| Main-circuit connection | Connection at separate fixed chassis |
| Protection rating | IP30 |
| Power loss | 62 W |
| Electrical endurance | 8000 cycles at Ue ≤ 440 V |
| Mechanical endurance | 20000 cycles |
| Net weight | 18 kg |
| GTIN / EAN | 8015644759254 |
| Reference standard | IEC 60947-2 |
The ABB 1SDA072075R1 is the 630 A three-pole moving part of a SACE Emax 2 E1.2N withdrawable air circuit breaker, equipped with an Ekip Touch LSI electronic trip unit.
The Ekip Touch LSI electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S) and instantaneous short-circuit (I) protection.
The E1.2N 630 provides a rated ultimate short-circuit breaking capacity of 66 kA at 400 V AC and a rated short-time withstand current of 50 kA for 1 s.
This product is the moving part of a withdrawable air circuit breaker and is intended for use with the corresponding ABB Emax 2 fixed chassis or cradle.
No. The Ekip Touch LSI release provides long-time, short-time and instantaneous overcurrent protection but does not include integrated ground-fault protection.
ABB SACE Emax 2 withdrawable air circuit breakers combine advanced electronic protection with service-friendly switchgear architecture, providing dependable switching, selective protection and flexible maintenance for modern low-voltage power distribution systems.