ABB 1SDA072055R1 E1.2B 630 Ekip Touch LSI three-pole withdrawable air circuit breaker moving part with a 630 A rated current, 690 V AC operational voltage, 42 kA breaking capacity at 440 V AC and electronic LSI protection.
£2,452.69
The ABB E1.2B 630 Ekip Touch LSI 3p WMP, order code 1SDA072055R1, is a compact air circuit breaker (ACB) moving part from the ABB SACE Emax 2 series, designed for protection and switching in low-voltage power distribution systems. With a rated uninterrupted current of 630 A, three-pole construction and ABB's advanced Ekip Touch electronic trip technology, it provides dependable protection for industrial, commercial and infrastructure electrical installations.
The Ekip Touch LSI electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. Its touchscreen interface enables straightforward configuration of protection settings, while the LSI functionality supports effective coordination and selectivity between protective devices in appropriately engineered low-voltage distribution networks.
The 1SDA072055R1 is the withdrawable moving part (WMP) of the Emax 2 E1.2 circuit breaker system and is designed for use with a compatible fixed part. The E1.2B platform provides a rated ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s, combining compact construction with dependable fault protection and convenient maintainability.
Air circuit breakers such as the ABB SACE Emax 2 E1.2B provide switching, isolation and protection for low-voltage electrical distribution circuits. The compact E1.2 frame combines dependable short-circuit performance with a withdrawable architecture, allowing the moving part to be disconnected from its corresponding fixed part for inspection, maintenance or replacement.
The Ekip Touch LSI electronic trip unit combines adjustable long-time, short-time and instantaneous protection with a touchscreen configuration interface. The short-time protection function provides additional flexibility for selective protection schemes, helping engineers coordinate the breaker with downstream protective devices while maintaining rapid response to severe short-circuit conditions.
| Series | SACE Emax 2 |
|---|---|
| Product group | Emax2 Air Circuit Breaker |
| Order code / MPN | 1SDA072055R1 |
| Product type | Air circuit breaker moving part |
| Frame | E1.2 |
| Performance level | B |
| Rated uninterrupted current (Iu) | 630 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50 / 60 Hz |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 / 415 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 / 525 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 42 kA |
| Rated short-time withstand current (Icw), 1 s | 42 kA |
| Number of poles | 3 |
| Trip unit | Ekip Touch LSI |
| Release type | Electronic trip unit |
| Protection functions | LSI (long-time, short-time and instantaneous) |
| Long-time protection adjustment range | 252–630 A (0.4–1 × In) |
| Instantaneous protection adjustment range | 945–9450 A (1.5–15 × In) |
| Integrated earth-fault protection | No |
| Configuration interface | Touchscreen |
| Current type | AC |
| Installation | Withdrawable |
| Component type | Moving part (WMP) |
| Applicable standard | IEC 60947-2 |
The ABB 1SDA072055R1 is the withdrawable moving part of an Emax 2 E1.2B air circuit breaker, designed for switching and protecting three-phase low-voltage power distribution circuits.
The circuit breaker has a rated uninterrupted current of 630 A, with adjustable long-time protection over a 252–630 A range.
The Ekip Touch LSI electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection, with protection settings accessible through its touchscreen interface.
The E1.2B 630 provides a rated ultimate short-circuit breaking capacity of 42 kA at 380–690 V AC and a rated short-time withstand current of 42 kA for 1 s.
The 1SDA072055R1 is a withdrawable moving part (WMP) designed for installation with the corresponding ABB Emax 2 fixed part.
ABB SACE Emax 2 air circuit breakers provide reliable switching and electronic protection for modern low-voltage power distribution systems, combining compact construction, flexible installation and advanced protection technology.