1SDA072052R1 ABB E1.2B 630 Ekip Dip LSI 3p WMP Air Circuit Breaker Moving Part

1SDA072052R1 ABB E1.2B 630 Ekip Dip LSI 3p WMP Air Circuit Breaker Moving Part

ABB 1SDA072052R1 E1.2B 630 Ekip Dip LSI three-pole moving part for a withdrawable SACE Emax 2 air circuit breaker, rated at 630 A with adjustable LSI electronic protection and 42 kA short-circuit breaking capacity.

SKU: 1SDA072052R1MPN: 1SDA072052R1
Price
List Price £3,210.06 ex VAT
Your Price (ex VAT) Save 25%
£2,407.55 25% OFF
You save £802.52 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £2,407.55
Trade pricing is personalised to your account

Manufacturer Lead Time

£2,407.55

Why Choose the ABB E1.2B 630 Ekip Dip LSI 3p WMP Air Circuit Breaker Moving Part?

The ABB E1.2B 630 Ekip Dip LSI 3p WMP, order code 1SDA072052R1, is the three-pole moving part of a withdrawable SACE Emax 2 air circuit breaker, designed for protection and switching in low-voltage power distribution systems. Rated at 630 A, this compact E1.2B assembly combines ABB's withdrawable Emax 2 architecture with an Ekip Dip LSI electronic trip unit.

The Ekip Dip LSI release provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. Adjustable protection settings allow the breaker to be coordinated with other protective devices in the distribution network, while the absence of integrated ground-fault protection makes this LSI version suitable where earth-fault protection is provided separately or is not required at the breaker.

As a WMP moving part, the 1SDA072052R1 is designed for use with the corresponding Emax 2 fixed part or cradle. The E1.2B platform provides a rated ultimate short-circuit breaking capacity of 42 kA at 400–690 V AC and a rated short-time withstand current of 42 kA for 1 s, supporting dependable protection in industrial and commercial distribution switchboards.

Key Advantages

  • 630 A three-pole Emax 2 moving part for withdrawable air circuit breaker installations.
  • Ekip Dip LSI electronic trip unit provides three-stage overcurrent protection.
  • Long-time, short-time and instantaneous functions support effective protection coordination.
  • 42 kA ultimate short-circuit breaking capacity for robust fault interruption.
  • 42 kA short-time withstand current for 1 s.
  • Withdrawable architecture simplifies breaker inspection, servicing and replacement.
  • Equipped with four auxiliary change-over contacts for control and status integration.
  • Part of ABB's established SACE Emax 2 E1.2 air circuit breaker platform.

Key Features

  • ABB SACE Emax 2 E1.2B series.
  • 630 A rated uninterrupted current (Iu).
  • Three-pole configuration.
  • Moving part for withdrawable circuit breaker.
  • Ekip Dip LSI solid-state electronic release.
  • Long-time overload (L) protection.
  • Short-time delayed short-circuit (S) protection.
  • Instantaneous short-circuit (I) protection.
  • 42 kA Icu at 400–690 V AC.
  • Ics equal to 100% of Icu.
  • 42 kA Icw for 1 s.
  • Four auxiliary change-over contacts.
  • Breaker open/closed position indication.
  • Optional motor operating mechanism.

Reliable LSI Protection for Withdrawable Power Distribution

Withdrawable air circuit breakers allow the active breaker assembly to be removed from its fixed cradle, providing practical advantages for maintenance, inspection and replacement in electrical switchboards. The ABB Emax 2 E1.2 platform combines this service-friendly architecture with compact construction and dependable high-current switching performance.

The Ekip Dip LSI release protects the circuit against sustained overloads and both delayed and instantaneous short-circuit conditions. Its adjustable long-time, short-time and instantaneous settings allow protection to be coordinated with other devices in the electrical network, helping maintain selectivity while providing rapid interruption of severe faults.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Commercial building electrical distribution.
  • Manufacturing and process plant switchboards.
  • Transformer and installation protection.
  • Incoming and feeder circuit protection.
  • Withdrawable switchgear requiring convenient breaker servicing.
  • Distribution networks requiring adjustable LSI overcurrent protection.

Technical Specifications

Series SACE Emax 2
ABB order code 1SDA072052R1
Product type Air circuit breaker moving part
Frame E1.2
Performance level B
Rated uninterrupted current (Iu) 630 A
Number of poles 3
Construction Moving part for withdrawable circuit breaker
Trip unit Ekip Dip LSI
Release type Electronic / solid-state
Protection functions Long-time (L), short-time (S) and instantaneous (I)
Rated voltage 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 42 kA
Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC 42 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 42 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 42 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 42 kA
Rated service short-circuit breaking capacity (Ics) 100% of Icu
Rated short-time withstand current (Icw), 1 s 42 kA
Rated short-time withstand current (Icw), 3 s 24 kA
Overload release adjustment range 252–630 A
Short-time delayed short-circuit adjustment range 378–6300 A
Instantaneous short-circuit adjustment range 945–9450 A
Integrated ground-fault protection No
Auxiliary contacts 4 change-over contacts
Trip contact Yes
Position indication Circuit breaker open/closed
Motor drive Optional
Protection rating IP30
Power loss 62 W
Net weight 18 kg
GTIN / EAN 8015644759025

Frequently Asked Questions

What is the ABB 1SDA072052R1?

The ABB 1SDA072052R1 is the 630 A three-pole moving part of a SACE Emax 2 E1.2B withdrawable air circuit breaker, equipped with an Ekip Dip LSI electronic trip unit.

What protection does the Ekip Dip LSI trip unit provide?

The Ekip Dip LSI electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S) and instantaneous short-circuit (I) protection.

What is the breaking capacity of the ABB E1.2B 630?

The E1.2B 630 provides a rated ultimate short-circuit breaking capacity of 42 kA at 400–690 V AC and a rated short-time withstand current of 42 kA for 1 s.

Is the ABB 1SDA072052R1 fixed or withdrawable?

This product is the moving part of a withdrawable air circuit breaker and is intended for use with the corresponding ABB Emax 2 fixed part or cradle.

Does the ABB 1SDA072052R1 include ground-fault protection?

No. The Ekip Dip LSI release provides long-time, short-time and instantaneous overcurrent protection but does not include integrated ground-fault protection.

Dependable Protection with Emax 2 Flexibility

ABB SACE Emax 2 withdrawable air circuit breakers combine configurable electronic protection with service-friendly switchgear architecture, providing dependable switching and coordinated protection for modern low-voltage power distribution systems.