ABB 1SDA072043R1 Emax 2 E1.2N 250 three-pole withdrawable air circuit breaker moving part with a 250 A rated current, 66 kA breaking capacity at 400–440 V AC and Ekip Dip LSIG electronic protection.
£4,950.50
The ABB E1.2N 250 Ekip Dip LSIG 3p WMP, order code 1SDA072043R1, is a withdrawable Emax 2 air circuit breaker (ACB) designed for protection and switching in low-voltage electrical distribution systems. As part of the ABB SACE Emax 2 series, this three-pole breaker combines a 250 A rated uninterrupted current with an Ekip Dip LSIG electronic trip unit for dependable overload, short-circuit and earth-fault protection.
The E1.2N platform combines compact construction with high electrical and mechanical performance. Its Ekip Dip LSIG solid-state release provides long-time, short-time, instantaneous and ground-fault protection functions, enabling comprehensive protection of feeders and distribution circuits while supporting selective coordination within low-voltage networks.
With a rated uninterrupted current of 250 A, a three-pole configuration and an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC, the E1.2N 250 is suitable for industrial and commercial switchboards. The WMP configuration is the moving part of the withdrawable circuit breaker, allowing convenient isolation, inspection and maintenance when installed with the appropriate fixed part.
Air circuit breakers such as the ABB Emax 2 E1.2N provide switching, isolation and protection for electrical distribution circuits. By continuously monitoring current through the Ekip Dip electronic release, the breaker can respond to overloads, delayed and instantaneous short circuits and ground faults, helping protect cables, switchgear and connected equipment against potentially damaging electrical conditions.
The withdrawable moving-part configuration is particularly useful in switchboards where maintainability and continuity of service are important. When paired with the appropriate fixed part, the breaker can be moved between operating, test and disconnected positions, simplifying inspection and maintenance while the Ekip Dip LSIG release provides adjustable electronic protection for coordinated electrical distribution systems.
| Product group | Emax2 Air Circuit Breaker |
|---|---|
| Series | SACE Emax 2 |
| ABB order code | 1SDA072043R1 |
| Product type | Air circuit breaker |
| Frame | E1.2 |
| Performance level | N |
| Rated current (In) | 250 A |
| Rated uninterrupted current (Iu) | 250 A |
| Number of poles | 3 |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate short-circuit breaking capacity (Icu) | 66 kA at 400–440 V AC |
| Service short-circuit breaking capacity (Ics) | 50 kA at 400–690 V AC |
| Rated short-time withstand current (Icw) | 50 kA for 1 s |
| Trip unit | Ekip Dip LSIG |
| Release type | Electronic / solid-state |
| Protection functions | Long-time, short-time, instantaneous and ground fault (LSIG) |
| Overload release setting range | 100–250 A |
| Short-time delayed short-circuit setting range | 150–2500 A |
| Instantaneous short-circuit setting range | 375–3750 A |
| Integrated earth-fault protection | Yes |
| Execution | Withdrawable moving part (WMP) |
| Auxiliary contacts | 4 change-over contacts |
| Mechanical durability | 20,000 operating cycles |
| Electrical durability | 8,000 operating cycles |
| Power loss | 62 W |
| Protection rating | IP30 |
| Motor drive | Optional |
The ABB 1SDA072043R1 is an Emax 2 air circuit breaker moving part designed for switching and protecting three-phase low-voltage electrical distribution circuits in industrial and commercial switchboards.
The circuit breaker has a rated uninterrupted current of 250 A.
The breaker uses an Ekip Dip LSIG electronic trip unit providing long-time, short-time, instantaneous and ground-fault protection.
The E1.2N 250 has an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC.
WMP identifies the withdrawable moving part of the circuit breaker, designed for use with the appropriate fixed part in a withdrawable Emax 2 switchgear installation.
ABB SACE Emax 2 air circuit breakers combine dependable low-voltage circuit protection with electronic trip technology and flexible switchboard integration, providing an effective solution for modern industrial and commercial power distribution systems.