1SDA072000R1 ABB E6.2V/f 5000 Ekip G Hi-Touch LSIG 4p F HR Air Circuit Breaker

1SDA072000R1 ABB E6.2V/f 5000 Ekip G Hi-Touch LSIG 4p F HR Air Circuit Breaker

ABB 1SDA072000R1 E6.2V/f 5000 four-pole fixed air circuit breaker with a 5000 A rated current, Ekip G Hi-Touch LSIG electronic generator protection and up to 150 kA short-circuit breaking capacity.

SKU: 1SDA072000R1MPN: 1SDA072000R1
Price
List Price £57,065.65 ex VAT
Your Price (ex VAT) Save 25%
£42,799.24 25% OFF
You save £14,266.41 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £42,799.24
Trade pricing is personalised to your account

Manufacturer Lead Time

£42,799.24

Why Choose the ABB E6.2V/f 5000 Ekip G Hi-Touch LSIG 4p F HR Air Circuit Breaker?

The ABB E6.2V/f 5000 Ekip G Hi-Touch LSIG 4p F HR, order code 1SDA072000R1, is a high-performance four-pole fixed air circuit breaker (ACB) from the ABB SACE Emax 2 range, engineered for generator protection and demanding low-voltage power distribution systems. With a rated uninterrupted current of 5000 A, it provides advanced protection, switching and monitoring for major industrial and infrastructure electrical installations.

This E6.2V/f breaker incorporates the advanced Ekip G Hi-Touch LSIG electronic trip unit. Designed particularly for generator applications, the release combines long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection with the enhanced functionality of ABB's Hi-Touch electronic protection platform.

The breaker is supplied in a fixed four-pole configuration with full-size neutral and orientable rear horizontal terminals. The E6.2V performance level provides an exceptional ultimate short-circuit breaking capacity of 150 kA at 415 V AC, while maintaining 100 kA at 690 V AC, making this model suitable for electrical systems with very high prospective fault currents.

Key Advantages

  • Heavy-duty 5000 A air circuit breaker for high-current power distribution and generator protection.
  • High-performance E6.2V breaking capacity for installations with substantial prospective fault currents.
  • Ekip G Hi-Touch LSIG electronic trip unit provides comprehensive generator and circuit protection.
  • LSIG functionality combines overload, short-time, instantaneous and earth-fault protection.
  • 150 kA ultimate short-circuit breaking capacity at 415 V AC.
  • 100 kA short-time withstand current supports selective protection in complex distribution systems.
  • Fixed four-pole construction with full-size neutral and rear horizontal terminals.
  • Part of ABB's advanced SACE Emax 2 air circuit breaker platform.

Key Features

  • ABB SACE Emax 2 E6.2V/f series.
  • 5000 A rated uninterrupted current (Iu).
  • Four-pole configuration with full-size neutral.
  • Fixed (F) circuit breaker version.
  • Ekip G Hi-Touch LSIG electronic protection release.
  • Long-time (L), short-time (S), instantaneous (I) and ground-fault (G) protection functions.
  • Generator-oriented protection functionality for demanding generating applications.
  • 150 kA Icu at 400–440 V AC.
  • 130 kA Icu at 500–525 V AC.
  • 100 kA Icu at 690 V AC.
  • 100 kA rated short-time withstand current (Icw).
  • Rear horizontal terminal connections for switchboard integration.

Advanced Generator and Power Distribution Protection

Air circuit breakers such as the ABB Emax 2 E6.2V/f provide the switching and fault-interruption capability required at critical points in high-current low-voltage systems. The V performance level gives this breaker particularly high short-circuit breaking capability, allowing it to protect installations where substantial prospective fault currents may be present.

The Ekip G Hi-Touch LSIG release extends this capability with advanced electronic protection suited to generator applications. Its long-time, short-time, instantaneous and earth-fault functions provide coordinated protection against a broad range of abnormal electrical conditions, while the Emax 2 architecture supports integration into sophisticated power distribution and energy-management systems.

Typical Applications

  • Generator protection and generator switchboards.
  • Main low-voltage switchboards and power distribution boards.
  • Industrial power generation and distribution systems.
  • Large manufacturing and process facilities.
  • Critical infrastructure and utility installations.
  • High-current incoming and feeder circuits.
  • Power systems with high prospective short-circuit currents.
  • Installations requiring advanced LSIG electronic protection.

Technical Specifications

Series SACE Emax 2
ABB order code 1SDA072000R1
Product type Air circuit breaker
Application Generator and low-voltage power distribution protection
Frame E6.2
Performance level V
Rated uninterrupted current (Iu) 5000 A
Number of poles 4
Neutral Full size
Version Fixed (F)
Trip unit Ekip G Hi-Touch LSIG
Release type Electronic
Protection functions L, S, I and G
Rated voltage (Ur) 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 150 kA
Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC 150 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 150 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 130 kA
Rated ultimate short-circuit breaking capacity (Icu) at 525 V AC 130 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 100 kA
Rated short-time withstand current (Icw) 100 kA
Terminal connection Rear horizontal
Installation Fixed switchboard mounting

Frequently Asked Questions

What is the ABB 1SDA072000R1 used for?

The ABB 1SDA072000R1 is a high-current Emax 2 air circuit breaker designed for generator protection, switching and protection of demanding low-voltage power distribution systems.

What is the current rating of the E6.2V/f 5000?

The breaker has a rated uninterrupted current of 5000 A.

What protection does the Ekip G Hi-Touch LSIG trip unit provide?

The Ekip G Hi-Touch LSIG electronic trip unit provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection, with functionality developed for demanding generator applications.

What is the breaking capacity of the ABB E6.2V/f 5000?

The E6.2V/f 5000 provides an ultimate short-circuit breaking capacity of up to 150 kA at 400–440 V AC, with a capacity of 100 kA at 690 V AC.

Is the ABB 1SDA072000R1 fixed or withdrawable?

This model is a fixed (F), four-pole air circuit breaker with full-size neutral and rear horizontal terminal connections.

Advanced Protection for Critical Power Systems

ABB SACE Emax 2 air circuit breakers combine high fault-interruption performance with sophisticated electronic protection, making the E6.2V platform a dependable choice for generator systems and critical high-current low-voltage power distribution.