Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071999R1 Emax 2 E6.2V/f 5000 is a 5000 A fixed four-pole air circuit breaker with a fully rated fourth pole, Ekip Hi-Touch LSIG electronic protection, 150 kA breaking capacity at 440 V AC and rear horizontal terminals for demanding low-voltage power distribution systems.
£42,302.27
The ABB E6.2V/f 5000 Ekip Hi-Touch LSIG 4p FHR, order code 1SDA071999R1, is a high-performance four-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range. Designed for demanding low-voltage power distribution, it combines a substantial 5000 A rated uninterrupted current with a fully rated fourth pole and exceptional short-circuit performance for industrial, commercial and infrastructure switchboards.
This Emax 2 circuit breaker incorporates the advanced Ekip Hi-Touch LSIG electronic trip unit, providing long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection. The comprehensive LSIG protection package supports selective coordination between protective devices while adding dedicated earth-fault protection for critical electrical distribution networks.
The E6.2V/f 5000 is a fixed four-pole breaker with a fully rated fourth pole and rear horizontal terminals. The V performance level provides an ultimate short-circuit breaking capacity of 150 kA at 440 V AC together with a rated short-time withstand current of 100 kA for 1 s, making it particularly suitable for high-current, high-fault-level main distribution systems.
Air circuit breakers such as the ABB SACE Emax 2 E6.2V/f provide protection, switching and isolation for high-current low-voltage electrical networks. The fully rated four-pole configuration is particularly suited to four-wire distribution systems where the fourth pole requires full current-carrying capability, while the V performance level provides exceptional breaking capability for installations with substantial prospective fault currents.
The Ekip Hi-Touch LSIG trip unit combines long-time overload, short-time selective, instantaneous short-circuit and earth-fault protection. Together with the breaker's 5000 A current rating, 150 kA ultimate breaking capacity at 440 V AC and 100 kA short-time withstand capability, the 1SDA071999R1 provides a robust solution for critical distribution systems requiring very high current capacity, advanced electronic protection, effective selectivity and earth-fault protection.
| Series | SACE Emax 2 |
|---|---|
| Order code / Product ID | 1SDA071999R1 |
| Product type | Air circuit breaker |
| ABB product group | Emax2 Air Circuit Breaker |
| Frame / subtype | E6.2V/f |
| Performance level | V |
| Rated uninterrupted current (Iu) | 5000 A |
| Number of poles | 4 |
| Fourth pole | Fully rated |
| Current type | AC |
| Ultimate short-circuit breaking capacity (Icu) | 150 kA at 440 V AC |
| Rated short-time withstand current (Icw) | 100 kA for 1 s |
| Trip unit | Ekip Hi-Touch LSIG |
| Release type | Electronic / solid-state |
| Protection functions | Long-time (L), short-time (S), instantaneous (I) and earth-fault (G) |
| Integrated earth-fault protection | Yes |
| Installation version | Fixed |
| Terminal configuration | Rear horizontal (FHR) |
| Application | Low-voltage power distribution, transformer, generator and installation protection |
| Standard | IEC 60947-2 |
The ABB 1SDA071999R1 is a 5000 A four-pole air circuit breaker used for protection, switching and isolation in high-current, high-fault-level low-voltage power distribution systems requiring a fully rated fourth pole and comprehensive LSIG electronic protection.
The Ekip Hi-Touch LSIG electronic trip unit provides long-time overload (L), short-time selective short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.
The E6.2V/f 5000 provides an ultimate short-circuit breaking capacity of 150 kA at 440 V AC, together with a rated short-time withstand current of 100 kA for 1 s.
LSI provides long-time overload, short-time and instantaneous short-circuit protection, while LSIG additionally includes earth-fault protection. The Ekip Hi-Touch LSIG fitted to the 1SDA071999R1 therefore provides comprehensive protection against overloads, short circuits and earth faults.
The ABB 1SDA071999R1 is a fixed-version air circuit breaker equipped with rear horizontal terminals for permanent integration into low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers are designed for demanding low-voltage distribution systems where very high current capacity, advanced electronic protection, effective fault selectivity and exceptional short-circuit performance are required.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.