Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071958R1 Emax 2 E6.2H/f 4000 is a 4000 A fixed four-pole air circuit breaker with a fully rated neutral, Ekip Hi-Touch LSI electronic protection, 100 kA breaking capacity at 440 V AC and rear horizontal terminals for demanding low-voltage power distribution systems.
£27,974.86
The ABB E6.2H/f 4000 Ekip Hi-Touch LSI 4p FHR, order code 1SDA071958R1, is a high-performance four-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range. Designed for demanding low-voltage power distribution, it combines a 4000 A rated current with a fully rated fourth pole and high short-circuit performance for industrial, commercial and infrastructure switchboards.
This Emax 2 circuit breaker incorporates the Ekip Hi-Touch LSI solid-state electronic trip unit, providing long-time overload, short-time selective short-circuit and instantaneous short-circuit protection. These LSI functions support accurate protection and selective coordination between upstream and downstream devices, helping isolate faults while maintaining continuity elsewhere in the electrical distribution system.
The E6.2H/f 4000 is a fixed four-pole breaker with full-size neutral and rear horizontal terminals. Its H performance level provides an ultimate short-circuit breaking capacity of 100 kA at 440 V AC together with a rated short-time withstand current of 100 kA for 1 s, making it suitable for high-current distribution systems with demanding fault-level and selectivity requirements.
Air circuit breakers such as the ABB SACE Emax 2 E6.2H/f provide protection, switching and isolation for high-current low-voltage electrical networks. The fully rated four-pole construction provides a full-size neutral pole, making this configuration suitable for installations where the neutral conductor must be switched and rated for the same current as the phase conductors.
The Ekip Hi-Touch LSI trip unit combines long-time overload, short-time selective and instantaneous short-circuit protection. Together with the breaker's 4000 A current rating, 100 kA breaking capacity at 440 V AC and 100 kA short-time withstand capability, the 1SDA071958R1 provides a robust solution for critical distribution systems requiring high fault performance and selective protection.
| Series | SACE Emax 2 |
|---|---|
| Order code / Product ID | 1SDA071958R1 |
| EAN | 8015644758080 |
| Product type | Air circuit breaker |
| ABB product group | Emax2 Air Circuit Breaker |
| Frame / subtype | E6.2H/f |
| Performance level | H |
| Rated current | 4000 A |
| Rated uninterrupted current (Iu) | 4000 A |
| Number of poles | 4 |
| Fourth pole | Fully rated / full-size neutral |
| Current type | AC |
| Ultimate short-circuit breaking capacity (Icu) | 100 kA at 440 V AC |
| Rated short-time withstand current (Icw) | 100 kA for 1 s |
| Trip unit | Ekip Hi-Touch LSI |
| Release type | Solid-state electronic |
| Protection functions | Long-time (L), short-time (S) and instantaneous (I) |
| Installation version | Fixed |
| Terminal configuration | Rear horizontal |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Electrical durability | 4000 operating cycles at ≤440 V AC; 4000 operating cycles at 500–690 V AC |
| Operating frequency for electrical durability | 10 cycles per hour |
| Mechanical durability | 12000 operating cycles |
| Product dimensions (W × H × D) | 1014 × 371 × 270 mm |
| Product net weight | 135 kg |
| Country of origin | Italy |
| Standard | IEC 60947-2 |
The ABB 1SDA071958R1 is a 4000 A four-pole air circuit breaker used for protection, switching and isolation in high-current low-voltage power distribution systems requiring a fully rated fourth pole.
The Ekip Hi-Touch LSI solid-state electronic trip unit provides long-time overload (L), short-time selective short-circuit (S) and instantaneous short-circuit (I) protection.
The E6.2H/f 4000 has an ultimate short-circuit breaking capacity of 100 kA at 440 V AC and a rated short-time withstand current of 100 kA for 1 s.
The E6.2H/f designation identifies an Emax 2 E6.2 H-performance breaker with a fully rated fourth pole, providing a full-size neutral pole in this four-pole configuration.
The 1SDA071958R1 is a fixed-version air circuit breaker supplied with rear horizontal terminals and four auxiliary contacts for integration into low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers are designed for demanding low-voltage distribution systems where high current capacity, advanced electronic protection, selective fault coordination and dependable short-circuit performance are required.