1SDA071933R1 ABB E6.2V 6300 Ekip Dip LSIG 4p FHR Air Circuit Breaker

1SDA071933R1 ABB E6.2V 6300 Ekip Dip LSIG 4p FHR Air Circuit Breaker

ABB 1SDA071933R1 Emax 2 E6.2V 6300 is a 6300 A four-pole fixed air circuit breaker with Ekip Dip LSIG electronic protection, integrated earth-fault protection, up to 150 kA short-circuit breaking capacity and rear horizontal terminals for demanding low-voltage power distribution systems.

SKU: 1SDA071933R1MPN: 1SDA071933R1
Price
List Price £63,204.87 ex VAT
Your Price (ex VAT) Save 25%
£47,403.65 25% OFF
You save £15,801.22 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £47,403.65
Trade pricing is personalised to your account

Manufacturer Lead Time

£47,403.65

Why Choose the ABB E6.2V 6300 Ekip Dip LSIG 4p FHR Air Circuit Breaker?

The ABB E6.2V 6300 Ekip Dip LSIG 4p FHR, order code 1SDA071933R1, is a high-performance four-pole air circuit breaker (ACB) designed for protection, switching and isolation in demanding low-voltage power distribution systems. Part of the ABB SACE Emax 2 series, it combines a substantial 6300 A rated current with very high short-circuit performance for major industrial, commercial and infrastructure installations.

This Emax 2 circuit breaker incorporates the Ekip Dip LSIG solid-state electronic trip unit, providing long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection. Protection settings are configured using DIP switches, providing dependable and straightforward adjustment for power distribution applications requiring comprehensive LSIG protection.

The E6.2V 6300 is a fixed, four-pole breaker with rear horizontal terminals. Rated for operation at up to 690 V AC, it provides an ultimate short-circuit breaking capacity of 150 kA at 380–440 V AC, 130 kA at 500–525 V AC and 100 kA at 690 V AC, making it particularly suitable for high-current, high-fault-level main distribution systems.

Key Advantages

  • Very high 6300 A rated current for major low-voltage power distribution systems.
  • Four-pole configuration for comprehensive switching, protection and isolation.
  • Ekip Dip LSIG electronic trip unit provides overload, short-circuit and earth-fault protection.
  • Short-time delayed protection supports selective coordination within complex distribution networks.
  • Exceptional 150 kA ultimate short-circuit breaking capacity at 380–440 V AC.
  • Integrated earth-fault protection helps provide comprehensive protection for distribution systems.
  • Fixed installation for permanent integration into low-voltage switchboards.
  • Rear horizontal terminals facilitate connection to high-current busbar systems.

Key Features

  • ABB SACE Emax 2 E6.2V air circuit breaker.
  • 6300 A rated uninterrupted current.
  • Four-pole configuration.
  • Ekip Dip LSIG solid-state trip unit.
  • Long-time overload (L) protection.
  • Short-time selective short-circuit (S) protection.
  • Instantaneous short-circuit (I) protection.
  • Integrated earth-fault (G) protection.
  • Overload protection adjustable from 0.4–1 × In.
  • Short-time protection adjustable from 0.6–10 × In.
  • Instantaneous protection adjustable from 1.5–15 × In.
  • Earth-fault protection adjustable from 0.1–1 × In.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 150 kA ultimate short-circuit breaking capacity at 380–440 V AC.
  • 130 kA ultimate short-circuit breaking capacity at 500–525 V AC.
  • 100 kA ultimate short-circuit breaking capacity at 690 V AC.
  • Fixed construction with rear horizontal terminals.
  • Supplied with four auxiliary change-over contacts and circuit-breaker open/closed position indication.

Comprehensive LSIG Protection for High-Capacity Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 E6.2V provide protection, switching and isolation for high-current low-voltage electrical networks. By detecting overloads, short circuits and earth faults, the breaker can disconnect the affected circuit to help protect cables, switchgear and connected equipment while supporting dependable operation of the wider distribution system.

The Ekip Dip LSIG trip unit combines long-time overload, short-time selective, instantaneous and earth-fault protection in a configurable electronic release. Combined with the E6.2V frame's 6300 A current rating and breaking capacity of up to 150 kA, the 1SDA071933R1 is particularly suited to critical high-power distribution applications where fault levels, selectivity and comprehensive circuit protection are key requirements.

Typical Applications

  • Industrial low-voltage main distribution switchboards.
  • Manufacturing plants and large production facilities.
  • Transformer protection and distribution systems.
  • Generator and critical power distribution systems.
  • Data centres and high-availability infrastructure.
  • Utilities and major infrastructure installations.
  • High-fault-level incoming supply protection.
  • Main and feeder circuits requiring comprehensive LSIG protection.

Technical Specifications

Series SACE Emax 2
Order code / Product ID 1SDA071933R1
EAN 8015644757830
Product type Air circuit breaker
ABB product group Emax2 Air Circuit Breaker
Frame / subtype E6.2V
Performance level V
Rated current 6300 A
Rated uninterrupted current (Iu) 6300 A
Number of poles 4
Current type AC
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Frequency 50 / 60 Hz
Ultimate short-circuit breaking capacity (Icu) 150 kA at 380–440 V AC; 130 kA at 500–525 V AC; 100 kA at 690 V AC
Trip unit Ekip Dip LSIG
Release type Electronic / solid-state
Protection functions Long-time (L), short-time (S), instantaneous (I) and earth-fault (G)
Overload release current setting 2520–6300 A
Short-time delayed short-circuit release setting 3780–63000 A
Instantaneous short-circuit release setting 9450–94500 A
Earth-fault protection Integrated
Earth-fault protection adjustment 0.1–1 × In
Protection adjustment method DIP switches
Installation version Fixed
Terminal configuration Rear horizontal
Main circuit connection Bolted
Auxiliary contacts 4 change-over contacts
Position indication Circuit breaker open / closed
Electrical durability 2000 cycles at ≤440 V AC; 2000 cycles at 500–690 V AC
Mechanical durability 12000 cycles
Product dimensions (W × H × D) 888 × 371 × 270 mm
Product net weight 112 kg
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071933R1 used for?

The ABB 1SDA071933R1 is a 6300 A four-pole air circuit breaker used for protection, switching and isolation in high-current, high-fault-level low-voltage power distribution systems.

What protection functions does the Ekip Dip LSIG trip unit provide?

The Ekip Dip LSIG electronic trip unit provides long-time overload (L), short-time selective short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.

What is the breaking capacity of the ABB E6.2V 6300?

The E6.2V 6300 provides an ultimate short-circuit breaking capacity of 150 kA at 380–440 V AC, 130 kA at 500–525 V AC and 100 kA at 690 V AC.

Is the 1SDA071933R1 a fixed or withdrawable circuit breaker?

The 1SDA071933R1 is a fixed-version circuit breaker equipped with rear horizontal terminals for permanent integration into low-voltage switchboards.

What does LSIG protection mean on the ABB E6.2V 6300?

LSIG denotes long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection. On the Ekip Dip LSIG release, these functions provide comprehensive electronic protection for demanding low-voltage distribution systems.

Trusted for High-Capacity Power Distribution

ABB SACE Emax 2 air circuit breakers are designed for demanding low-voltage distribution systems where very high current capacity, dependable electronic protection, effective selectivity and exceptional short-circuit performance are required.