1SDA071930R1 ABB E6.2H 6300 Ekip G Hi-Touch LSIG 4p FHR Air Circuit Breaker

1SDA071930R1 ABB E6.2H 6300 Ekip G Hi-Touch LSIG 4p FHR Air Circuit Breaker

ABB 1SDA071930R1 E6.2H 6300 Ekip G Hi-Touch LSIG four-pole fixed air circuit breaker for generator and power-distribution protection with a 6300 A rated uninterrupted current, 690 V AC operating voltage, integrated earth-fault protection and 100 kA ultimate short-circuit breaking capacity.

SKU: 1SDA071930R1MPN: 1SDA071930R1
Price
List Price £58,390.96 ex VAT
Your Price (ex VAT) Save 25%
£43,793.22 25% OFF
You save £14,597.74 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £43,793.22
Trade pricing is personalised to your account

Manufacturer Lead Time

£43,793.22

Why Choose the ABB E6.2H 6300 Ekip G Hi-Touch LSIG 4p FHR Air Circuit Breaker?

The ABB E6.2H 6300 Ekip G Hi-Touch LSIG 4p FHR, order code 1SDA071930R1, is a high-performance four-pole SACE Emax 2 air circuit breaker engineered for generator protection and demanding low-voltage power-distribution systems. Part of the ABB SACE Emax 2 E6.2 series, this fixed breaker combines a 6300 A rated uninterrupted current with the advanced Ekip G Hi-Touch LSIG electronic trip unit.

The E6.2H performance level provides a rated ultimate short-circuit breaking capacity of 100 kA at 440 V AC and a rated short-time withstand current of 100 kA for 1 s. Its Ekip G Hi-Touch LSIG release combines long-time overload, selective short-time, instantaneous short-circuit and earth-fault protection with generator-oriented protection and advanced monitoring capabilities.

This version is a four-pole fixed air circuit breaker with rear flat horizontal (FHR) terminals. Rated for operation up to 690 V AC, the 1SDA071930R1 combines very high current-carrying capability, comprehensive generator-oriented protection and sophisticated Ekip functionality for generator switchboards, industrial plants, data centres and other critical high-capacity electrical systems.

Key Advantages

  • High-current ABB SACE Emax 2 E6.2H air circuit breaker for generator and power-distribution applications.
  • 6300 A rated uninterrupted current for very high-capacity electrical systems.
  • 100 kA ultimate short-circuit breaking capacity at 440 V AC.
  • 100 kA short-time withstand current for 1 s supports demanding high-fault-level installations.
  • Ekip G Hi-Touch LSIG electronic trip unit provides comprehensive overload, short-circuit and earth-fault protection.
  • Generator-oriented Ekip G functionality supports generating sets and complex multi-source power systems.
  • Advanced measurement and power-quality capabilities support modern power-management architectures.
  • Four-pole fixed construction with rear flat horizontal terminals supports integration into high-current switchboards.

Key Features

  • ABB SACE Emax 2 E6.2H series.
  • 6300 A rated uninterrupted current.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • Four-pole configuration.
  • Ekip G Hi-Touch LSIG electronic trip unit.
  • Long-time overload protection.
  • Selective short-time short-circuit protection.
  • Instantaneous short-circuit protection.
  • Integrated earth-fault protection.
  • Generator-oriented protection functionality.
  • 100 kA Icu at 400/415/440/500/525/690 V AC.
  • 100 kA Icw for 1 s and 3 s.
  • 100% Icu rated service short-circuit breaking capacity (Ics).
  • Fixed (F) execution with rear flat horizontal terminals.
  • Bolted main-circuit connection.
  • Four auxiliary changeover contacts.
  • Switched-off indication.
  • Optional motor operator.
  • IP30 degree of protection.

Advanced Generator Protection for High-Capacity Power Systems

Very high-current generator and distribution networks require circuit breakers capable of carrying substantial continuous loads while safely managing severe fault conditions. The ABB E6.2H combines a 6300 A rated uninterrupted current, 100 kA ultimate short-circuit breaking capacity and 100 kA short-time withstand capability for both 1 s and 3 s, providing a robust protection platform for major generator incomers, busbars and distribution feeders.

The Ekip G Hi-Touch LSIG trip unit combines generator-oriented protection with advanced measurement, monitoring and power-quality functionality. Long-time, selective short-time, instantaneous and earth-fault functions protect critical equipment against a broad range of abnormal conditions, while the Ekip platform supports integration with modern automation and energy-management architectures.

Typical Applications

  • High-capacity generator protection and generator switchboards.
  • Standby and emergency power-generation systems.
  • Main incoming protection in very high-current low-voltage switchboards.
  • Industrial power-generation and distribution systems.
  • Data centres and critical power infrastructure.
  • Large manufacturing and process facilities.
  • High-current busbar and transformer distribution systems.
  • Multi-source networks requiring advanced LSIG protection and generator-oriented functionality.

Technical Specifications

Series SACE Emax 2 E6.2
Order code / MPN 1SDA071930R1
Product type Air circuit breaker (ACB)
Product group Emax 2 Air Circuit Breaker
Frame / performance level E6.2H
Rated uninterrupted current (Iu) 6300 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Number of poles 4
Neutral pole current 50% of Iu
Trip unit Ekip G Hi-Touch LSIG
Release technology Electronic
Protection functions Long-time, short-time, instantaneous and earth-fault (LSIG)
Generator-oriented protection Yes
Overload protection adjustment 2520–6300 A
Selective short-circuit protection adjustment 3780–63000 A
Instantaneous short-circuit protection adjustment 9450–94500 A
Integrated earth-fault protection Yes
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 525 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 100 kA
Rated service short-circuit breaking capacity (Ics) 100% of Icu
Rated short-time withstand current (Icw), 1 s 100 kA
Rated short-time withstand current (Icw), 3 s 100 kA
Execution Fixed
Main terminals Rear flat horizontal (FHR)
Main-circuit connection Bolted
Auxiliary changeover contacts 4
Switched-off indication Yes
Integrated motor operator No
Optional motor operator Yes
Degree of protection IP30
Power loss 767 W
Electrical durability 2000 cycles
Mechanical durability 12000 cycles
Product net weight 125 kg
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071930R1 used for?

The ABB 1SDA071930R1 is an Emax 2 air circuit breaker configured with an Ekip G Hi-Touch LSIG trip unit for protection and switching of very high-current generator and low-voltage power-distribution systems.

What is the current rating of the ABB E6.2H 6300?

The ABB E6.2H 6300 has a rated uninterrupted current of 6300 A and a rated operational voltage of 690 V AC.

What protection does the Ekip G Hi-Touch LSIG trip unit provide?

The Ekip G Hi-Touch LSIG electronic trip unit provides long-time overload, selective short-time, instantaneous short-circuit and integrated earth-fault protection together with generator-oriented protection and advanced monitoring capabilities.

What is the breaking capacity of the ABB 1SDA071930R1?

The E6.2H 6300 provides a rated ultimate short-circuit breaking capacity of 100 kA at 400–690 V AC and a rated short-time withstand current of 100 kA for both 1 s and 3 s.

Is the ABB 1SDA071930R1 fixed or withdrawable?

The 1SDA071930R1 is a fixed four-pole air circuit breaker equipped with rear flat horizontal terminals and bolted main-circuit connections for integration into high-current switchboards.

Trusted Protection for Generator and Critical Power Systems

ABB SACE Emax 2 air circuit breakers with Ekip G Hi-Touch protection combine very high current-carrying capability, generator-oriented electronic protection and advanced system supervision to provide dependable protection for generating sets and critical low-voltage power-distribution networks.