ABB 1SDA071930R1 E6.2H 6300 Ekip G Hi-Touch LSIG four-pole fixed air circuit breaker for generator and power-distribution protection with a 6300 A rated uninterrupted current, 690 V AC operating voltage, integrated earth-fault protection and 100 kA ultimate short-circuit breaking capacity.
£43,793.22
The ABB E6.2H 6300 Ekip G Hi-Touch LSIG 4p FHR, order code 1SDA071930R1, is a high-performance four-pole SACE Emax 2 air circuit breaker engineered for generator protection and demanding low-voltage power-distribution systems. Part of the ABB SACE Emax 2 E6.2 series, this fixed breaker combines a 6300 A rated uninterrupted current with the advanced Ekip G Hi-Touch LSIG electronic trip unit.
The E6.2H performance level provides a rated ultimate short-circuit breaking capacity of 100 kA at 440 V AC and a rated short-time withstand current of 100 kA for 1 s. Its Ekip G Hi-Touch LSIG release combines long-time overload, selective short-time, instantaneous short-circuit and earth-fault protection with generator-oriented protection and advanced monitoring capabilities.
This version is a four-pole fixed air circuit breaker with rear flat horizontal (FHR) terminals. Rated for operation up to 690 V AC, the 1SDA071930R1 combines very high current-carrying capability, comprehensive generator-oriented protection and sophisticated Ekip functionality for generator switchboards, industrial plants, data centres and other critical high-capacity electrical systems.
Very high-current generator and distribution networks require circuit breakers capable of carrying substantial continuous loads while safely managing severe fault conditions. The ABB E6.2H combines a 6300 A rated uninterrupted current, 100 kA ultimate short-circuit breaking capacity and 100 kA short-time withstand capability for both 1 s and 3 s, providing a robust protection platform for major generator incomers, busbars and distribution feeders.
The Ekip G Hi-Touch LSIG trip unit combines generator-oriented protection with advanced measurement, monitoring and power-quality functionality. Long-time, selective short-time, instantaneous and earth-fault functions protect critical equipment against a broad range of abnormal conditions, while the Ekip platform supports integration with modern automation and energy-management architectures.
| Series | SACE Emax 2 E6.2 |
|---|---|
| Order code / MPN | 1SDA071930R1 |
| Product type | Air circuit breaker (ACB) |
| Product group | Emax 2 Air Circuit Breaker |
| Frame / performance level | E6.2H |
| Rated uninterrupted current (Iu) | 6300 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 4 |
| Neutral pole current | 50% of Iu |
| Trip unit | Ekip G Hi-Touch LSIG |
| Release technology | Electronic |
| Protection functions | Long-time, short-time, instantaneous and earth-fault (LSIG) |
| Generator-oriented protection | Yes |
| Overload protection adjustment | 2520–6300 A |
| Selective short-circuit protection adjustment | 3780–63000 A |
| Instantaneous short-circuit protection adjustment | 9450–94500 A |
| Integrated earth-fault protection | Yes |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 525 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 100 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Rated short-time withstand current (Icw), 3 s | 100 kA |
| Execution | Fixed |
| Main terminals | Rear flat horizontal (FHR) |
| Main-circuit connection | Bolted |
| Auxiliary changeover contacts | 4 |
| Switched-off indication | Yes |
| Integrated motor operator | No |
| Optional motor operator | Yes |
| Degree of protection | IP30 |
| Power loss | 767 W |
| Electrical durability | 2000 cycles |
| Mechanical durability | 12000 cycles |
| Product net weight | 125 kg |
| Standard | IEC 60947-2 |
The ABB 1SDA071930R1 is an Emax 2 air circuit breaker configured with an Ekip G Hi-Touch LSIG trip unit for protection and switching of very high-current generator and low-voltage power-distribution systems.
The ABB E6.2H 6300 has a rated uninterrupted current of 6300 A and a rated operational voltage of 690 V AC.
The Ekip G Hi-Touch LSIG electronic trip unit provides long-time overload, selective short-time, instantaneous short-circuit and integrated earth-fault protection together with generator-oriented protection and advanced monitoring capabilities.
The E6.2H 6300 provides a rated ultimate short-circuit breaking capacity of 100 kA at 400–690 V AC and a rated short-time withstand current of 100 kA for both 1 s and 3 s.
The 1SDA071930R1 is a fixed four-pole air circuit breaker equipped with rear flat horizontal terminals and bolted main-circuit connections for integration into high-current switchboards.
ABB SACE Emax 2 air circuit breakers with Ekip G Hi-Touch protection combine very high current-carrying capability, generator-oriented electronic protection and advanced system supervision to provide dependable protection for generating sets and critical low-voltage power-distribution networks.