ABB 1SDA071927R1 Emax 2 E6.2H 6300 Ekip G Touch LSIG four-pole fixed air circuit breaker rated at 6300 A and 690 V AC with 100 kA breaking capacity and advanced generator, overload, short-circuit and earth-fault protection.
£43,120.84
The ABB 1SDA071927R1 is a high-capacity Emax 2 air circuit breaker (ACB) engineered for generator and demanding low-voltage power-distribution applications. Identified as the E6.2H 6300 Ekip G Touch LSIG 4p FHR, this four-pole fixed breaker combines a substantial 6300 A rated uninterrupted current with ABB’s Ekip G Touch LSIG solid-state electronic protection release.
As part of the ABB SACE Emax 2 E6.2H series, the breaker provides high short-circuit performance for critical industrial, generator and infrastructure installations. The Ekip G Touch LSIG release provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection, delivering comprehensive protection for high-current electrical systems.
With a rated operational voltage of 690 V AC, an ultimate short-circuit breaking capacity of 100 kA across 400–690 V AC and a short-time withstand current of 100 kA for 1 s and 3 s, the 1SDA071927R1 is engineered for installations with substantial prospective fault currents. Its four-pole fixed construction and rear flat horizontal terminals provide a robust configuration for permanent integration into high-capacity low-voltage switchboards.
The ABB Emax 2 E6.2H platform is designed for high-current low-voltage systems where substantial fault-interruption capability and selective protection are required. With a 6300 A current rating, 100 kA breaking capacity throughout the principal 400–690 V AC operating range and a 100 kA short-time withstand rating for up to three seconds, the E6.2H 6300 is suited to critical distribution points exposed to high prospective fault currents.
The Ekip G Touch LSIG electronic trip unit adds comprehensive protection suited to generator and power-distribution applications. Its long-time, short-time, instantaneous and earth-fault functions help protect generators, transformers, busbars, cables and connected equipment while supporting selective coordination, continuity of service and dependable operation of high-capacity electrical systems.
| Product group | Emax 2 Air Circuit Breaker |
|---|---|
| Range | SACE Emax 2 |
| Series | E6.2H |
| ABB order code / MPN | 1SDA071927R1 |
| EAN / GTIN | 8015644757779 |
| Product type | Air circuit breaker |
| Rated current (In) | 6300 A |
| Rated uninterrupted current (Iu) | 6300 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 525 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 100 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw) | 100 kA for 1 s / 100 kA for 3 s |
| Number of poles | 4 |
| Neutral pole current | 50% of Iu |
| Short-circuit performance level | H |
| Trip unit | Ekip G Touch LSIG |
| Release type | Solid-state electronic |
| Protection functions | LSIG |
| Overload release adjustment range | 2520–6300 A |
| Integrated earth-fault protection | Yes |
| Installation | Fixed |
| Terminal position | Rear |
| Terminal type | Rear flat horizontal |
| Main circuit connection | Bolt connection |
| Recommended main-circuit screw | M12 |
| Auxiliary contacts | 4 change-over contacts |
| Open / closed position indication | Yes |
| Degree of protection | IP30 |
| Motor drive integrated | No |
| Motor drive optional | Yes |
| Electrical durability | 2000 cycles |
| Mechanical durability | 12,000 cycles |
| Power loss | 767 W |
| Dimensions (W × H × D) | 888 × 371 × 270 mm |
| Net weight | 125 kg |
| Suitable for IT networks | Yes, up to 690 V |
| Standard | IEC 60947-2 |
The ABB 1SDA071927R1 is an Emax 2 air circuit breaker designed for high-current generator and low-voltage power-distribution applications requiring advanced overload, short-circuit and earth-fault protection.
The E6.2H 6300 has a rated uninterrupted current of 6300 A, making it suitable for major generator, industrial and infrastructure electrical systems.
The breaker provides an ultimate short-circuit breaking capacity of 100 kA at 400, 415, 440, 500, 525 and 690 V AC, together with a short-time withstand current of 100 kA for 1 s and 3 s.
The Ekip G Touch LSIG electronic trip unit provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and integrated earth-fault protection, with functionality suited to generator and power-distribution applications.
This model is a four-pole fixed air circuit breaker equipped with rear flat horizontal terminals and bolted main-circuit connections for permanent integration into compatible high-current low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers combine very high current-handling capability with advanced electronic protection, helping generator, industrial and infrastructure installations achieve dependable overload, short-circuit and earth-fault protection while supporting selectivity and continuity of service.