1SDA071923R1 ABB E6.2H 6300 Ekip Dip LSIG 4P FHR Air Circuit Breaker

1SDA071923R1 ABB E6.2H 6300 Ekip Dip LSIG 4P FHR Air Circuit Breaker

ABB 1SDA071923R1 is a SACE Emax 2 E6.2H 6300 A four-pole fixed air circuit breaker with rear flat horizontal terminals and an Ekip Dip LSIG solid-state electronic trip unit for comprehensive high-current low-voltage power distribution protection.

SKU: 1SDA071923R1MPN: 1SDA071923R1
Price
List Price £54,025.30 ex VAT
Your Price (ex VAT) Save 25%
£40,518.98 25% OFF
You save £13,506.33 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £40,518.98
Trade pricing is personalised to your account

Manufacturer Lead Time

£40,518.98

Why Choose the ABB 1SDA071923R1 Emax 2 Air Circuit Breaker?

The ABB 1SDA071923R1 is a high-current SACE Emax 2 E6.2H air circuit breaker engineered for protection and switching in demanding low-voltage power distribution systems. Configured as an E6.2H 6300 Ekip Dip LSIG 4p FHR, it combines a rated uninterrupted current of 6300 A with ABB's Ekip Dip LSIG solid-state electronic trip unit.

This four-pole fixed circuit breaker provides comprehensive LSIG protection functions, covering long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. The Ekip Dip release provides configurable electronic protection for very high-current distribution systems requiring dependable fault protection, selective coordination and integrated earth-fault protection.

The E6.2H performance level provides a rated ultimate short-circuit breaking capacity of 100 kA across 400–690 V AC, with a rated service short-circuit breaking capacity equal to 100% of Icu and a rated short-time withstand current of 100 kA for 1 s and 3 s. Its fixed four-pole construction features rear flat horizontal terminals and four change-over auxiliary contacts for integration into high-capacity switchboards.

Key Advantages

  • High-current ABB SACE Emax 2 E6.2H air circuit breaker for demanding low-voltage distribution systems.
  • 6300 A rated uninterrupted current for very high-capacity electrical installations.
  • 100 kA ultimate short-circuit breaking capacity across 400–690 V AC.
  • 100 kA short-time withstand current for 1 s and 3 s for robust fault-current performance.
  • Ekip Dip LSIG electronic trip unit provides overload, short-circuit and integrated earth-fault protection.
  • Four-pole fixed configuration with rear flat horizontal terminals for high-capacity switchboard integration.

Key Features

  • ABB SACE Emax 2 E6.2H series.
  • 6300 A rated uninterrupted current (Iu).
  • Four-pole configuration.
  • 50% neutral pole current.
  • Fixed mounting construction.
  • Rear flat horizontal terminals (FHR).
  • Ekip Dip LSIG solid-state electronic trip unit.
  • LSIG protection for long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault conditions.
  • 690 V AC rated operational voltage.
  • 100 kA Icu at 400–690 V AC.

Comprehensive LSIG Protection for Very High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 protect high-current low-voltage electrical networks against overloads, short circuits and earth faults while providing switching and isolation functions within power distribution assemblies. The E6.2H frame combines a substantial 6300 A continuous-current rating with 100 kA ultimate short-circuit breaking capacity across the 400–690 V AC range for demanding industrial and infrastructure installations.

The Ekip Dip LSIG electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. Combined with 100 kA short-time withstand capability for up to 3 s, the 1SDA071923R1 provides dependable protection and selective coordination for main distribution switchboards, very high-current feeders and critical low-voltage electrical systems.

Typical Applications

  • Main incoming protection for very high-current low-voltage switchboards.
  • Industrial power distribution systems.
  • High-capacity feeder protection.
  • Manufacturing and process industry electrical installations.
  • Commercial and infrastructure power distribution.
  • Critical systems requiring overload, short-circuit and earth-fault protection.

Technical Specifications

Series SACE Emax 2
Frame E6.2H
ABB order code 1SDA071923R1
Product type Air circuit breaker
Rated current (In) 6300 A
Rated uninterrupted current (Iu) 6300 A
Number of poles 4
Neutral pole current 50% of Iu
Trip unit Ekip Dip LSIG
Release type Solid-state electronic
Protection functions LSIG
Integrated earth-fault protection Yes
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 525 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 100 kA
Rated service short-circuit breaking capacity (Ics) 100% of Icu
Rated short-time withstand current (Icw), 1 s 100 kA
Rated short-time withstand current (Icw), 3 s 100 kA
Mounting version Fixed
Terminal arrangement Rear flat horizontal
Main circuit connection Bolt connection
Auxiliary contacts 4 change-over contacts
Circuit-breaker position indication Open/closed
Motor drive Optional
Integrated motor drive No
Integrated undervoltage release No
Degree of protection IP30
Power loss 767 W
Product width 888 mm
EAN 8015644757731
Standard IEC 60947-2
Product group Emax2 Air Circuit Breaker

Frequently Asked Questions

What is the ABB 1SDA071923R1 used for?

The ABB 1SDA071923R1 is a 6300 A four-pole air circuit breaker designed for protection and switching in very high-current low-voltage power distribution systems.

What trip unit is fitted to the ABB 1SDA071923R1?

The circuit breaker is fitted with an Ekip Dip LSIG solid-state electronic trip unit providing overload, short-circuit and earth-fault protection.

What protection functions does the Ekip Dip LSIG provide?

The LSIG configuration provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection.

What is the current rating of the ABB 1SDA071923R1?

The E6.2H circuit breaker has a rated uninterrupted current of 6300 A.

What is the breaking capacity of the ABB 1SDA071923R1?

The E6.2H 6300 configuration has a rated ultimate short-circuit breaking capacity of 100 kA at 400–690 V AC.

Does the ABB 1SDA071923R1 provide earth-fault protection?

Yes. Its Ekip Dip LSIG trip unit incorporates earth-fault protection alongside long-time, short-time and instantaneous short-circuit protection functions.

What is the short-time withstand rating of the ABB 1SDA071923R1?

The breaker has a rated short-time withstand current of 100 kA for both 1 s and 3 s.

Is the ABB 1SDA071923R1 fixed or withdrawable?

This model is a fixed four-pole circuit breaker equipped with rear flat horizontal terminals.

Trusted by Power Distribution Professionals Worldwide

ABB SACE Emax 2 air circuit breakers are engineered for reliable protection and switching of demanding low-voltage electrical networks, combining very high current-carrying capability, robust fault interruption performance and comprehensive electronic protection for industrial, commercial and infrastructure power distribution systems.