1SDA071903R1 ABB E6.2V 5000 Ekip Dip LSIG 4p FHR Air Circuit Breaker

1SDA071903R1 ABB E6.2V 5000 Ekip Dip LSIG 4p FHR Air Circuit Breaker

ABB 1SDA071903R1 Emax 2 E6.2V 5000 Ekip Dip LSIG four-pole fixed air circuit breaker rated at 5000 A and 690 V AC with up to 150 kA breaking capacity and adjustable overload, short-circuit and earth-fault protection.

SKU: 1SDA071903R1MPN: 1SDA071903R1
Price
List Price £47,496.24 ex VAT
Your Price (ex VAT) Save 25%
£35,622.18 25% OFF
You save £11,874.06 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £35,622.18
Trade pricing is personalised to your account

Manufacturer Lead Time

£35,622.18

Why Choose the ABB E6.2V 5000 Ekip Dip LSIG 4p FHR Air Circuit Breaker?

The ABB 1SDA071903R1 is a high-capacity Emax 2 air circuit breaker (ACB) designed for protection, switching and isolation in demanding low-voltage power-distribution systems. Identified as the E6.2V 5000 Ekip Dip LSIG 4p FHR, this four-pole fixed circuit breaker combines a substantial 5000 A rated current with ABB’s Ekip Dip LSIG electronic trip unit.

As part of the ABB SACE Emax 2 E6.2V series, the breaker provides exceptionally high short-circuit performance for critical industrial and infrastructure installations. The Ekip Dip LSIG release provides adjustable long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection, with protection settings configured through DIP switches.

With a rated operational voltage of 690 V AC, the E6.2V platform provides an ultimate short-circuit breaking capacity of 150 kA at 380–440 V AC, 130 kA at 500–525 V AC and 100 kA at 690 V AC. Its four-pole fixed construction and rear horizontal terminals provide a robust configuration for permanent integration into high-capacity low-voltage switchboards.

Key Advantages

  • High-capacity ABB Emax 2 E6.2V air circuit breaker for demanding low-voltage power distribution.
  • 5000 A rated current for major industrial and infrastructure installations.
  • 150 kA Icu at 380–440 V AC for systems with exceptionally high prospective fault currents.
  • 130 kA Icu at 500–525 V AC and 100 kA Icu at 690 V AC.
  • Four-pole configuration for switching and protection of three phases and neutral.
  • Ekip Dip LSIG electronic trip unit provides adjustable overload, short-circuit and earth-fault protection.
  • DIP-switch adjustment provides straightforward configuration of protection thresholds.
  • Fixed construction with rear horizontal terminals for permanent switchboard integration.

Key Features

  • ABB SACE Emax 2 E6.2V series.
  • 5000 A rated current.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 50 / 60 Hz operating frequency.
  • 150 kA Icu at 380–440 V AC.
  • 130 kA Icu at 500–525 V AC.
  • 100 kA Icu at 690 V AC.
  • Ekip Dip LSIG electronic protection release.
  • Long-time overload, short-time selective, instantaneous and earth-fault protection functions.
  • 2000–5000 A long-time overload adjustment range.
  • 3000–50000 A short-time protection adjustment range.
  • 7500–75000 A instantaneous protection adjustment range.
  • 500–5000 A earth-fault protection adjustment range.
  • Protection settings configured through DIP switches.
  • 4-pole fixed circuit breaker configuration.
  • Rear horizontal main terminals with bolted connection.
  • Four auxiliary change-over contacts.
  • IP30 degree of protection.

Comprehensive High-Capacity Circuit Protection

The ABB Emax 2 E6.2V platform is designed for high-current low-voltage systems where exceptional short-circuit performance and selective protection are required. With a 5000 A current rating and breaking capacity reaching 150 kA, the E6.2V 5000 is particularly suited to critical distribution positions exposed to very high prospective fault currents.

The Ekip Dip LSIG electronic trip unit provides adjustable long-time overload, short-time selective, instantaneous short-circuit and earth-fault protection. These functions help protect transformers, busbars, cables and connected equipment against a broad range of electrical faults while allowing protection characteristics to be coordinated with other devices for improved selectivity and continuity of service.

Typical Applications

  • Main incomer protection in high-current low-voltage switchboards.
  • Industrial power distribution systems.
  • Transformer and installation protection.
  • Manufacturing and process plants.
  • Data centres and critical power installations.
  • Utility and infrastructure electrical distribution.
  • Large electrical distribution panels and switchboards.
  • High-current installations requiring integrated earth-fault protection.

Technical Specifications

Product group Emax 2 Air Circuit Breaker
Range SACE Emax 2
Series E6.2V
ABB order code / MPN 1SDA071903R1
Product type Air circuit breaker
Rated current (In) 5000 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Frequency 50 / 60 Hz
Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC 150 kA
Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC 150 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 150 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC 130 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 100 kA
Number of poles 4
Short-circuit performance level V
Trip unit Ekip Dip LSIG
Release type Electronic
Protection functions LSIG
Long-time overload protection adjustment 0.4–1 × In
Long-time overload adjustment range 2000–5000 A
Short-time selective protection adjustment 0.6–10 × In
Short-time protection adjustment range 3000–50000 A
Instantaneous protection adjustment 1.5–15 × In
Instantaneous protection adjustment range 7500–75000 A
Earth-fault protection adjustment 0.1–1 × In
Earth-fault protection adjustment range 500–5000 A
Integrated earth-fault protection Yes
Protection setting method DIP switches
Installation Fixed
Terminal position Rear
Terminal configuration Rear horizontal
Main circuit connection Bolted connection
Auxiliary contacts 4 change-over contacts
Trip indication Yes
Motor drive integrated No
Motor drive optional Yes
Degree of protection IP30
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071903R1 used for?

The ABB 1SDA071903R1 is an Emax 2 air circuit breaker designed for high-current low-voltage switching, isolation and circuit protection in industrial, utility and infrastructure power-distribution systems.

What is the current rating of the ABB 1SDA071903R1?

The E6.2V 5000 has a rated current of 5000 A, making it suitable for major high-current electrical distribution systems.

What is the breaking capacity of the E6.2V 5000?

The breaker provides an ultimate short-circuit breaking capacity of 150 kA at 380–440 V AC, 130 kA at 500–525 V AC and 100 kA at 690 V AC.

What protection functions does the Ekip Dip LSIG provide?

The Ekip Dip LSIG electronic trip unit provides adjustable long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection, with the settings configured using DIP switches.

How is the ABB 1SDA071903R1 installed?

This model is a four-pole fixed air circuit breaker with rear horizontal terminals and bolted main-circuit connections for permanent integration into compatible high-current low-voltage switchboards.

Trusted High-Performance Power Protection

ABB SACE Emax 2 air circuit breakers combine exceptional high-current switching capability with configurable electronic protection, helping demanding industrial and infrastructure installations achieve dependable overload, short-circuit and earth-fault protection while supporting selectivity and continuity of service.