Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071903R1 Emax 2 E6.2V 5000 Ekip Dip LSIG four-pole fixed air circuit breaker rated at 5000 A and 690 V AC with up to 150 kA breaking capacity and adjustable overload, short-circuit and earth-fault protection.
£35,622.18
The ABB 1SDA071903R1 is a high-capacity Emax 2 air circuit breaker (ACB) designed for protection, switching and isolation in demanding low-voltage power-distribution systems. Identified as the E6.2V 5000 Ekip Dip LSIG 4p FHR, this four-pole fixed circuit breaker combines a substantial 5000 A rated current with ABB’s Ekip Dip LSIG electronic trip unit.
As part of the ABB SACE Emax 2 E6.2V series, the breaker provides exceptionally high short-circuit performance for critical industrial and infrastructure installations. The Ekip Dip LSIG release provides adjustable long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection, with protection settings configured through DIP switches.
With a rated operational voltage of 690 V AC, the E6.2V platform provides an ultimate short-circuit breaking capacity of 150 kA at 380–440 V AC, 130 kA at 500–525 V AC and 100 kA at 690 V AC. Its four-pole fixed construction and rear horizontal terminals provide a robust configuration for permanent integration into high-capacity low-voltage switchboards.
The ABB Emax 2 E6.2V platform is designed for high-current low-voltage systems where exceptional short-circuit performance and selective protection are required. With a 5000 A current rating and breaking capacity reaching 150 kA, the E6.2V 5000 is particularly suited to critical distribution positions exposed to very high prospective fault currents.
The Ekip Dip LSIG electronic trip unit provides adjustable long-time overload, short-time selective, instantaneous short-circuit and earth-fault protection. These functions help protect transformers, busbars, cables and connected equipment against a broad range of electrical faults while allowing protection characteristics to be coordinated with other devices for improved selectivity and continuity of service.
| Product group | Emax 2 Air Circuit Breaker |
|---|---|
| Range | SACE Emax 2 |
| Series | E6.2V |
| ABB order code / MPN | 1SDA071903R1 |
| Product type | Air circuit breaker |
| Rated current (In) | 5000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50 / 60 Hz |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 150 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC | 150 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 150 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC | 130 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 100 kA |
| Number of poles | 4 |
| Short-circuit performance level | V |
| Trip unit | Ekip Dip LSIG |
| Release type | Electronic |
| Protection functions | LSIG |
| Long-time overload protection adjustment | 0.4–1 × In |
| Long-time overload adjustment range | 2000–5000 A |
| Short-time selective protection adjustment | 0.6–10 × In |
| Short-time protection adjustment range | 3000–50000 A |
| Instantaneous protection adjustment | 1.5–15 × In |
| Instantaneous protection adjustment range | 7500–75000 A |
| Earth-fault protection adjustment | 0.1–1 × In |
| Earth-fault protection adjustment range | 500–5000 A |
| Integrated earth-fault protection | Yes |
| Protection setting method | DIP switches |
| Installation | Fixed |
| Terminal position | Rear |
| Terminal configuration | Rear horizontal |
| Main circuit connection | Bolted connection |
| Auxiliary contacts | 4 change-over contacts |
| Trip indication | Yes |
| Motor drive integrated | No |
| Motor drive optional | Yes |
| Degree of protection | IP30 |
| Standard | IEC 60947-2 |
The ABB 1SDA071903R1 is an Emax 2 air circuit breaker designed for high-current low-voltage switching, isolation and circuit protection in industrial, utility and infrastructure power-distribution systems.
The E6.2V 5000 has a rated current of 5000 A, making it suitable for major high-current electrical distribution systems.
The breaker provides an ultimate short-circuit breaking capacity of 150 kA at 380–440 V AC, 130 kA at 500–525 V AC and 100 kA at 690 V AC.
The Ekip Dip LSIG electronic trip unit provides adjustable long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection, with the settings configured using DIP switches.
This model is a four-pole fixed air circuit breaker with rear horizontal terminals and bolted main-circuit connections for permanent integration into compatible high-current low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers combine exceptional high-current switching capability with configurable electronic protection, helping demanding industrial and infrastructure installations achieve dependable overload, short-circuit and earth-fault protection while supporting selectivity and continuity of service.