ABB 1SDA071902R1 Emax 2 E6.2V 5000 Ekip Dip LSI four-pole fixed air circuit breaker rated at 5000 A and 690 V AC with up to 150 kA breaking capacity and adjustable long-time, short-time and instantaneous protection.
£35,110.60
The ABB 1SDA071902R1 is a high-capacity Emax 2 air circuit breaker (ACB) designed for protection, switching and isolation in demanding low-voltage power-distribution systems. Identified as the E6.2V 5000 Ekip Dip LSI 4p FHR, this four-pole fixed circuit breaker combines a substantial 5000 A rated uninterrupted current with ABB’s Ekip Dip LSI electronic trip unit.
As part of the ABB SACE Emax 2 E6.2V series, this breaker provides exceptionally high short-circuit performance for critical industrial and infrastructure installations. The Ekip Dip LSI release provides long-time overload, short-time selective short-circuit and instantaneous short-circuit protection, with straightforward electronic protection settings suited to high-current distribution networks.
With a rated operational voltage of 690 V AC, an ultimate short-circuit breaking capacity of 150 kA at 400–440 V AC, 130 kA at 500–525 V AC and 100 kA at 690 V AC, the 1SDA071902R1 is engineered for installations with very high prospective fault currents. Its four-pole fixed construction and rear flat horizontal terminals provide a robust configuration for permanent integration into high-capacity switchboards.
The ABB Emax 2 E6.2V platform is designed for high-current low-voltage systems where exceptional short-circuit performance and selective protection are required. With a 5000 A rated uninterrupted current, breaking capacity reaching 150 kA and a 100 kA short-time withstand rating for both one and three seconds, the E6.2V 5000 is well suited to critical distribution positions exposed to very high prospective fault currents.
The Ekip Dip LSI electronic trip unit provides adjustable long-time overload, short-time selective and instantaneous short-circuit protection. These functions help protect transformers, busbars, cables and connected equipment while allowing protection characteristics to be coordinated with other devices in the distribution system for improved selectivity and continuity of service.
| Product group | Emax 2 Air Circuit Breaker |
|---|---|
| Range | SACE Emax 2 |
| Series | E6.2V |
| ABB order code / MPN | 1SDA071902R1 |
| EAN / GTIN | 8015644757526 |
| Product type | Air circuit breaker |
| Rated current (In) | 5000 A |
| Rated uninterrupted current (Iu) | 5000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC | 150 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 150 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC | 130 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 100 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw) | 100 kA for 1 s / 100 kA for 3 s |
| Number of poles | 4 |
| Short-circuit performance level | V |
| Trip unit | Ekip Dip LSI |
| Release type | Electronic |
| Protection functions | LSI |
| Overload release adjustment range | 2000–5000 A |
| Short-time delayed short-circuit adjustment range | 3000–50000 A |
| Instantaneous short-circuit adjustment range | 7500–75000 A |
| Integrated earth-fault protection | No |
| Installation | Fixed |
| Terminal connection | Rear flat horizontal |
| Main circuit connection | Bolt connection |
| Recommended main-circuit screw | M12 |
| Tightening torque | 70 N·m |
| Auxiliary contacts | 4 change-over contacts |
| Open / closed position indication | Yes |
| Degree of protection | IP30 |
| Motor drive integrated | No |
| Motor drive optional | Yes |
| Power loss | 483 W |
| Suitable for IT networks | Yes, up to 690 V |
| Standard | IEC 60947-2 |
The ABB 1SDA071902R1 is an Emax 2 air circuit breaker designed for high-current low-voltage switching, isolation and circuit protection in industrial, utility and infrastructure power-distribution systems.
The E6.2V 5000 has a rated uninterrupted current of 5000 A, making it suitable for major high-current electrical distribution systems.
The breaker provides an ultimate short-circuit breaking capacity of 150 kA at 400–440 V AC, 130 kA at 500–525 V AC and 100 kA at 690 V AC.
The Ekip Dip LSI electronic trip unit provides adjustable long-time overload, short-time selective short-circuit and instantaneous short-circuit protection. This LSI version does not include integrated earth-fault protection.
This model is a four-pole fixed air circuit breaker equipped with rear flat horizontal terminals and bolted main-circuit connections for permanent integration into compatible high-current low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers combine exceptional high-current switching capability with configurable electronic protection, helping demanding industrial and infrastructure installations achieve dependable overload and short-circuit protection while supporting selectivity and continuity of service.