ABB 1SDA071880R1 E6.2V 4000 Ekip G Hi-Touch LSIG four-pole fixed air circuit breaker for generator and power-distribution protection with a 4000 A rated uninterrupted current, integrated earth-fault protection, 150 kA breaking capacity at 400 V AC and 100 kA short-time withstand current.
£26,501.05
The ABB E6.2V 4000 Ekip G Hi-Touch LSIG 4p FHR, order code 1SDA071880R1, is a high-performance four-pole SACE Emax 2 air circuit breaker engineered for generator protection and demanding low-voltage power-distribution systems. Part of the ABB SACE Emax 2 E6.2 series, this fixed breaker combines a 4000 A rated uninterrupted current with the advanced Ekip G Hi-Touch LSIG electronic trip unit.
The E6.2V performance level delivers exceptional fault-interruption capability, with a rated ultimate short-circuit breaking capacity of 150 kA at 400 V AC and a rated short-time withstand current of 100 kA for 1 s. Its Ekip G Hi-Touch LSIG trip unit combines long-time overload, selective short-time, instantaneous short-circuit and earth-fault protection with generator-oriented protection functions and advanced measurement capabilities.
This version is a four-pole fixed air circuit breaker equipped with rear horizontal (FHR) terminals. The combination of E6.2 construction, V-level breaking performance and the sophisticated Ekip G Hi-Touch platform makes the 1SDA071880R1 particularly suitable for generator switchboards, critical power systems, industrial plants and infrastructure where high prospective fault currents, selective coordination and detailed electrical supervision are required.
Generator-fed electrical networks have protection requirements that differ from conventional utility-fed distribution systems. The ABB E6.2V combines a 4000 A rated uninterrupted current, 150 kA ultimate breaking capacity at 400 V AC and 100 kA short-time withstand capability for 1 s, providing a robust platform for high-power generator and distribution circuits exposed to demanding fault conditions.
The Ekip G Hi-Touch LSIG trip unit combines generator-oriented protection with advanced measurement, monitoring and power-quality analysis. Its LSIG architecture helps protect generators, cables, busbars, transformers and other critical equipment against overload, short-circuit and earth-fault conditions, while the Hi-Touch platform supports sophisticated supervision and integration within modern energy-management and automation systems.
| Series | SACE Emax 2 E6.2 |
|---|---|
| Order code / MPN | 1SDA071880R1 |
| EAN / GTIN | 8015644757304 |
| Product type | Air circuit breaker (ACB) |
| Product group | Emax 2 Air Circuit Breaker |
| Frame / performance level | E6.2V |
| Rated uninterrupted current (Iu) | 4000 A |
| Rated voltage range | 220–690 V AC |
| Number of poles | 4 |
| Trip unit | Ekip G Hi-Touch LSIG |
| Release technology | Electronic |
| Protection functions | Long-time, short-time, instantaneous and earth-fault (LSIG) |
| Generator-oriented protection | Yes |
| Overload release adjustment range | 1600–4000 A |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 150 kA |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Execution | Fixed |
| Main terminals | Rear horizontal (FHR) |
| Main-circuit connection | Bolted connection |
| Frame size | E6.2 |
| Protection platform | Ekip G Hi-Touch |
| Power-quality monitoring | Integrated Network Analyzer |
| Application | Generator and low-voltage power-distribution protection |
The ABB 1SDA071880R1 is an Emax 2 air circuit breaker configured with an Ekip G Hi-Touch LSIG trip unit for high-current generator protection and demanding low-voltage power-distribution applications.
The ABB E6.2V 4000 has a rated uninterrupted current of 4000 A, with an overload release adjustment range of 1600–4000 A.
The Ekip G Hi-Touch LSIG electronic trip unit provides long-time overload, selective short-time, instantaneous short-circuit and earth-fault protection together with generator-oriented protection, advanced measurement and monitoring functionality.
The E6.2V 4000 has a rated ultimate short-circuit breaking capacity of 150 kA at 400 V AC and a rated short-time withstand current of 100 kA for 1 s.
The 1SDA071880R1 is a fixed four-pole air circuit breaker equipped with rear horizontal (FHR) terminals and a bolted main-circuit connection for integration into high-current switchboards.
ABB SACE Emax 2 air circuit breakers with Ekip G Hi-Touch protection combine exceptional fault-interruption performance, generator-oriented electronic protection and advanced power-system monitoring to provide dependable protection for generating sets and critical low-voltage distribution networks.