1SDA071862R1 ABB E6.2H 4000 Ekip Dip LSI 4p FHR Air Circuit Breaker

1SDA071862R1 ABB E6.2H 4000 Ekip Dip LSI 4p FHR Air Circuit Breaker

ABB 1SDA071862R1 Emax 2 E6.2H 4000 Ekip Dip LSI four-pole fixed air circuit breaker rated at 4000 A and 690 V AC with 100 kA breaking capacity and adjustable long-time, short-time and instantaneous protection.

SKU: 1SDA071862R1MPN: 1SDA071862R1
Price
List Price £29,277.37 ex VAT
Your Price (ex VAT) Save 25%
£21,958.03 25% OFF
You save £7,319.34 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £21,958.03
Trade pricing is personalised to your account

Manufacturer Lead Time

£21,958.03

Why Choose the ABB E6.2H 4000 Ekip Dip LSI 4p FHR Air Circuit Breaker?

The ABB 1SDA071862R1 is a high-performance Emax 2 air circuit breaker (ACB) designed for protection, switching and isolation in demanding low-voltage power-distribution systems. Identified as the E6.2H 4000 Ekip Dip LSI 4p FHR, this four-pole fixed circuit breaker combines a 4000 A rated current with ABB’s Ekip Dip LSI electronic trip unit.

As part of the ABB SACE Emax 2 series, the E6.2H provides substantial short-circuit performance for critical industrial and infrastructure installations. The Ekip Dip LSI release provides adjustable long-time overload, short-time selective short-circuit and instantaneous short-circuit protection, with protection settings configured using straightforward DIP switches.

With a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 100 kA across 380–690 V AC, the 1SDA071862R1 is engineered for installations with high prospective fault currents. Its four-pole fixed construction and rear horizontal terminals provide a robust configuration for permanent integration into high-current low-voltage switchboards and distribution assemblies.

Key Advantages

  • High-performance ABB Emax 2 air circuit breaker for demanding low-voltage power distribution.
  • 4000 A rated current for large industrial, commercial and infrastructure installations.
  • 100 kA Icu across 380–690 V AC for dependable interruption of high prospective fault currents.
  • Four-pole configuration for switching and protection of three phases and neutral.
  • Ekip Dip LSI electronic trip unit with adjustable overload and short-circuit protection.
  • DIP-switch configuration provides straightforward adjustment of the electronic protection functions.
  • Fixed construction with rear horizontal terminals for permanent switchboard installation.

Key Features

  • ABB SACE Emax 2 E6.2H series.
  • 4000 A rated current.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 50 / 60 Hz operating frequency.
  • 100 kA Icu at 380 V AC.
  • 100 kA Icu at 400–415 V AC.
  • 100 kA Icu at 440 V AC.
  • 100 kA Icu at 500–525 V AC.
  • 100 kA Icu at 690 V AC.
  • Ekip Dip LSI electronic protection release.
  • Long-time overload, short-time selective and instantaneous short-circuit protection.
  • Protection adjustment through DIP switches.
  • 4-pole fixed circuit breaker configuration.
  • Rear horizontal main terminals.
  • Designed in accordance with IEC 60947-2.

High-Capacity Power Distribution Protection

Air circuit breakers such as the ABB Emax 2 E6.2H provide switching, isolation and protection for high-current low-voltage electrical systems. The E6.2H 4000 combines a substantial 4000 A current rating with a 100 kA ultimate short-circuit breaking capacity across the 380–690 V AC range, making it particularly suitable for critical distribution points with high prospective fault currents.

The Ekip Dip LSI electronic trip unit provides adjustable long-time overload, short-time selective and instantaneous short-circuit protection. Its DIP-switch settings allow protection characteristics to be matched to the installation and coordinated with other protective devices, helping protect transformers, busbars, cables and connected equipment while supporting selectivity and continuity of service.

Typical Applications

  • Main incomer protection in high-current low-voltage switchboards.
  • Industrial power distribution systems.
  • Transformer and installation protection.
  • Manufacturing and process plants.
  • Data centres and critical power installations.
  • Commercial and infrastructure electrical distribution.
  • Large electrical distribution panels and switchboards.
  • Installations with high prospective short-circuit currents.

Technical Specifications

Product group Emax 2 Air Circuit Breaker
Range SACE Emax 2
Series E6.2H
ABB order code / MPN 1SDA071862R1
EAN 8015644757113
Product type Air circuit breaker
Rated current 4000 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Frequency 50 / 60 Hz
Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 100 kA
Number of poles 4
Short-circuit performance level H
Trip unit Ekip Dip LSI
Release type Electronic
Protection functions LSI
Long-time overload protection adjustment 0.4–1 × In
Short-time selective protection adjustment 0.6–10 × In
Instantaneous protection adjustment 1.5–15 × In
Integrated earth-fault protection No
Protection setting method DIP switches
Installation Fixed
Terminal connection Rear horizontal
Current type AC
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071862R1 used for?

The ABB 1SDA071862R1 is an Emax 2 air circuit breaker designed for high-current low-voltage switching, isolation and circuit protection in industrial, commercial and infrastructure power-distribution systems.

What is the current rating of the ABB 1SDA071862R1?

The E6.2H 4000 has a rated current of 4000 A, making it suitable for large high-current electrical distribution systems.

What is the breaking capacity of the E6.2H 4000?

The breaker provides an ultimate short-circuit breaking capacity of 100 kA across 380–690 V AC, including 100 kA at 400–415 V, 440 V and 690 V AC.

What protection functions does the Ekip Dip LSI provide?

The Ekip Dip LSI electronic trip unit provides adjustable long-time overload, short-time selective short-circuit and instantaneous short-circuit protection. Protection settings are configured using DIP switches.

How is the ABB 1SDA071862R1 installed?

This model is a four-pole fixed air circuit breaker equipped with rear horizontal terminals for permanent integration into compatible low-voltage switchboards and power-distribution assemblies.

Trusted High-Performance Power Protection

ABB SACE Emax 2 air circuit breakers combine high-current switching capability with configurable electronic protection, helping demanding industrial and infrastructure installations achieve dependable overload and short-circuit protection while supporting selectivity and continuity of service.